1592023130 XM670K_XM679K GB r4.2 26.06.2017.docx 

XM670K - XM679K  

          9/10 

 

SFd 

0.3 

Pr1 

Start function duration 

0 ÷ 42.0(252)   (min.10sec) 

OPd 

85 

Pr1 

Opening percentage after defrost 
phase 

0 ÷ 100 

Pdd 

0.3 

Pr1 

Post defrost function duration 

0 ÷ 42.0(252)   (min.10sec) 

MnF 

100 

Pr1 

Maximum opening percentage at 
normale functioning 

0 ÷ 100 

dCL 

Pr1 

Delay before stopping valve 
regulation 

0 ÷ 255 s 

Fot 

nu 

Pr1 

Forced opening percentage 

0 ÷ 100 - "nu"(101) 

PA4 

-0.5 

Pr2 

Probe value at 4 mA or at 0V 

BAR : [PrM=rEL] -1.0 ÷ P20       

[PRM=Abs] 0.0 ÷ P20                                              

PSI : [PrM=rEL] -14 ÷ P20          

[PRM=Abs]  0 ÷ P20                                                  

dKP : [PrM=rEL] -10 ÷ P20         

[PRM=Abs] 0 ÷ P20 

P20 

11.0 

Pr2 

Probe value at 20 mA or at 5V 

BAR : [PrM=rEL] PA4 ÷ 50.0    

[PrM=AbS] PA4 ÷ 50.0                                             

PSI :    [PrM=rEL] PA4 ÷ 725     

[PrM=AbS] PA4 ÷ 725                                          

dKP :   [PrM=rEL] PA4 ÷ 500    

[PrM=AbS] PA4 ÷ 500 

LPL 

-0.5 

Pr1 

Lower pressure limit for superheat 
regulation 

PA4 ÷ P20 

MOP 

11.0 

Pr1 

Maximum operating pressure 
threshold 

LOP ÷ P20 

LOP 

-0.5 

Pr1 

Lowest operating pressure 
threshold 

PA4 ÷ MOP 

dML 

30 

Pr1 

Delta MOP-LOP opening variation 

0 ÷ 100 

MSH 

80.0 

Pr1 

Maximum superheat alarm 
threshold 

[LSH ÷ 80,0°C]     [LSH ÷ 144°F] 

LSH 

2.0 

Pr1 

Minimum superheat alarm 
threshold 

[0.0 ÷ MSH °C]       [0 ÷ MSH °F] 

SHy 

2.0 

Pr2 

Superheat alarm hysteresis 

[0.1°C ÷ 25.5°C] [1°F ÷ 45°F] 

SHd 

3.0 

Pr1 

Superheat alarm activation delay 

0 ÷ 42.0(252)   (min.10sec) 

FrC 

100 

Pr1 

Fast-recovery costant 

0 ÷ 100 

SUb 

10 

Pr2 

Pressure filter  

0÷100 

SLb 

Pr2 

Reaction time 

0÷255s 

Defrost 

dPA 

P2 

Pr1 

Defrost probe A 

nP(0) - P1(1) - P2(2) - P3(3) - 

P4(4) - P5(5) 

dPb 

nP 

Pr1 

Defrost probe B 

nP(0) - P1(1) - P2(2) - P3(3) - 

P4(4) - P5(5) 

dPE 

100 

Pr1 

Virtual probe percentage (defrost 
temperature) 

0  ÷ 100 (100=dPA, 0=dPb) 

tdF 

EL 

Pr1 

Defrost type 

EL(0) - in(0) 

EdF 

in 

Pr1 

Defrost mode: Clock or interval 

rtc(0) - in(1) 

Srt 

150 

Pr1 

Heater set point during defrost 

[-55.0°C ÷ 150°C] [-67°F ÷ 

302°F] 

Hyr 

2.0 

Pr1 

Differential for heater 

[0.1°C ÷ 25.5°C] [1°F ÷ 45°F] 

tod 

255 

Pr1 

Time out for heater 

0 ÷ 255 (min.) 

dtP 

0.1 

Pr1 

Minimum temperature difference 
to start defrost 

[0.1°C ÷ 50.0°C]     [1°F ÷ 90°F] 

ddP 

60 

Pr1 

Delay before starting defrost 

0 ÷ 60 (min.) 

d2P 

Pr1 

Defrost with two probes 

n(0) 

– Y(1) 

dtE 

8.0 

Pr1 

Defrost termination temperature 
(Probe A) 

[-55.0°C ÷ 50.0°C] [-67°F ÷ 

122°F] 

dtS 

8.0 

Pr1 

Defrost termination temperature 
(Probe B) 

[-55.0°C ÷ 50.0°C] [-67°F ÷ 

122°F] 

idF 

Pr1 

Interval between defrosts 

0 ÷ 120 (hours) 

MdF 

30 

Pr1 

Defrost Maximum duration 

0 ÷ 255 (min.) 

dSd 

Pr1 

Start defrost delay 

0 ÷ 255 (min.) 

dFd 

it 

Pr1 

Display during defrost 

rt(0) - it(1) - SEt(2) - dEF(3) 

dAd 

30 

Pr1 

Defrost display time out 

0 ÷ 255 (min.) 

Fdt 

Pr1 

Drain down time 

0 ÷ 255 (min.) 

dPo 

Pr1 

Defrost at start-up 

n(0) 

– Y(1) 

dAF 

0.0 

Pr1 

Defrost delay after continuous 
cycle 

0 ÷ 24.0(144)    (hours.10min) 

 

 

 

 

 

Fan 

FPA 

P2 

Pr1 

Fan probe A 

nP(0) - P1(1) - P2(2) - P3(3) - 

P4(4) - P5(5) 

FPb 

nP 

Pr1 

Fan probe B 

nP(0) - P1(1) - P2(2) - P3(3) - 

P4(4) - P5(5) 

FPE 

100 

Pr1 

Virtual probe percentage (fan 
management) 

0  ÷ 100 (100=FPA, 0=FPb) 

FnC 

O-n 

Pr1 

Fan operating mode 

C-n(0) - O-n(1) - C-y(2) - O-y(3) 

Fnd 

10 

Pr1 

Fan delay after defrost 

0 ÷ 255 (min.) 

FCt 

10 

Pr1 

Temperature differential to avoid 
short cycles of fans 

[0.0°C ÷ 50.0°C] [0°F ÷ 90°F] 

FSt 

2.0 

Pr1 

Fan stop temperature 

[-55.0°C ÷ 50.0°C] [-67°F ÷ 

122°F] 

FHy 

1.0 

Pr1 

Fan stop differential 

[0.1°C ÷ 25.5°C] [1°F ÷ 45°F] 

Fod 

Pr1 

Fan activation time after defrost 
(without compressor) 

0 ÷ 255 (min.) 

Fon 

Pr1 

Fan ON time 

0÷15 (min.) 

FoF 

Pr1 

Fan OFF time 

0÷15 (min.) 

trA 

UAL 

Pr2 

Kind of regulation for modulating 
output 

UAL(0) - rEG(1) - AC(2) 

SOA 

80 

Pr2 

Fixed speed for fan 

AMi ÷ AMA 

SdP 

30.0 

Pr2 

Default Dew Point value 

[-55.0°C ÷ 50.0°C] [-67°F ÷ 

122°F] 

ASr 

1.0 

Pr2 

Differential for fan / offset for anti 
sweat heater 

[-25.5°C ÷ 25.5°C] [-45°F ÷ 45°F] 

PbA 

5.0 

Pr2 

Proportional band for modulating 
output 

[0.1°C ÷ 25.5°C] [1°F ÷ 45°F] 

AMi 

Pr2 

Minimum output for modulating 
output 

0 ÷ AMA 

AMA 

100 

Pr2 

Maximum output for modulating 
output 

AMi ÷ 100 

AMt 

Pr2 

Time with fan at maximum speed 

0 ÷ 255 s 

Alarm 

rAL 

P1 

Pr1 

Probe for temperature alarm 

nP(0) - P1(1) - P2(2) - P3(3) - 

P4(4) - P5(5) - tEr(6) 

ALC 

Ab 

Pr1 

Temperature alarm configuration 

rE(0) - Ab(1) 

ALU 

10 

Pr1 

High temperature alarm setting 

[0.0°C ÷ 50.0°C o ALL ÷ 150.0°] 

[0°F ÷ 90°F o ALL ÷ 302°F] 

ALL 

-30 

Pr1 

Low temperature alarm setting 

[0.0°C ÷ 50.0°C  o  -55,0°C ÷ 

ALU]    [0°F ÷ 90°F  o   -67°F ÷ 

ALU°F] 

AHy 

1.0 

Pr1 

Differential for temperature alarm 

[0.1°C ÷ 25.5°C] [1°F ÷ 45°F] 

ALd 

15 

Pr1 

Temperature alarm delay 

0 ÷ 255 (min.) 

dLU 

150 

Pr2 

High temperature alarm setting 
(defrost probe) 

[0.0°C ÷ 50.0°C o dLL ÷ 150.0°] 

[0°F ÷ 90°F o dLL ÷ 302°F] 

dLL 

-55 

Pr2 

Low temperature alarm setting 
(defrost probe) 

[0.0°C ÷ 50.0°C  o  -55,0°C ÷ 

dLU]    [0°F ÷ 90°F  o   -67°F ÷ 

dLU°F] 

dAH 

1.0 

Pr2 

Differential for temperature alarm 
(defrost probe) 

[0.1°C ÷ 25.5°C] [1°F ÷ 45°F] 

ddA 

15 

Pr2 

Temperature alarm delay (defrost 
probe) 

0 ÷ 255 (min.) 

FLU 

150 

Pr2 

High temperature alarm setting 
(fan probe) 

[0.0°C ÷ 50.0°C o FLL ÷ 150.0°] 

[0°F ÷ 90°F o FLL ÷ 302°F] 

FLL 

-55 

Pr2 

Low temperature alarm setting 
(fan probe) 

[0.0°C ÷ 50.0°C  o  -55,0°C ÷ 

FLU]    [0°F ÷ 90°F  o   -67°F ÷ 

FLU°F] 

FAH 

1.0 

Pr2 

Differential for temperature alarm 
(fan probe) 

[0.1°C ÷ 25.5°C] [1°F ÷ 45°F] 

FAd 

15 

Pr2 

Temperature alarm delay (fan 
probe) 

0 ÷ 255 (min.) 

dAo 

1.3 

Pr1 

Delay of temperature alarm at 
start-up 

0 ÷ 24.0(144)    (hours.10min) 

EdA 

30 

Pr1 

Alarm delay at the end of defrost 

0 ÷ 255 min 

dot 

15 

Pr1 

Temperature alarm exclusion after 
door open 

0 ÷ 255 min 

Sti 

nu 

Pr2 

Stop regulation interval 

"nu"(0) ÷ 24.0(144)    

(hour.10min) 

Std 

Pr2 

Stop duration 

1 ÷ 255 min 

oA6 

AUS 

Pr2 

Sixth relay output configuration 

CPr(0) - dEF(1) - FAn(2) - ALr(3) 

- LiG(4) - AUS(5) - db(6) - 

OnF(7) 

CoM 

Cur 

Pr2 

Modulating output configuration 

CUr(0) - tEn(1) - PM5(2) - 

PM6(3) - oA7(4) 

AOP 

cL 

Pr1 

Alarm relay polarity 

OP(0) - CL(1) 

iAU 

Pr1 

Auxiliary output indipendent from 
ON/OFF state 

n(0) 

– Y(1) 

Digital Inputs 

i1P 

cL 

Pr1 

Digital input 1 polarity 

OP(0) - CL(1) 

i1F 

dor 

Pr1 

Digital input 1 configuration 

EAL(0) - bAL(1) - PAL(2) - dor(3) 

- dEF(4) - AUS(5) -LiG(6) - 

OnF(7) - Htr(8) - FHU(9) - 

ES(10) - Hdy(11) 

d1d 

15 

Pr1 

Digital input 1 activation delay 

0 ÷ 255 (min.) 

i2P 

cL 

Pr1 

Digital input 2 polarity 

OP(0) - CL(1) 

i2F 

LiG 

Pr1 

Digital input 2 configuration 

EAL(0) - bAL(1) - PAL(2) - dor(3) 

- dEF(4) - AUS(5) -LiG(6) - 

OnF(7) - Htr(8) - FHU(9) - 

ES(10) - Hdy(11) 

d2d 

Pr1 

Digital input 2 activation delay 

0 ÷ 255 (min.) 

i3P 

cL 

Pr1 

Digital input 3 polarity 

OP(0) - CL(1) 

i3F 

ES 

Pr1 

Digital input 3 configuration 

EAL(0) - bAL(1) - PAL(2) - dor(3) 

- dEF(4) - AUS(5) -LiG(6) - 

OnF(7) - Htr(8) - FHU(9) - 

ES(10) - Hdy(11) 

d3d 

Pr1 

Digital input 3 activation delay 

0 ÷ 255 (min.) 

nPS 

15 

Pr1 

Number of pressure switch 
activation before lock 

0 ÷ 15 

OdC 

F-C 

Pr1 

Compressor and fan status when 
open door 

no(0) - FAn(1) - CPr(2) - F-C(3) 

rrd 

30 

Pr1 

Outputs restart after door open 
alarm 

0 ÷ 255 (min.) 

Содержание Dixell XM670K

Страница 1: ...nstruments are equipped with the HOTKEY connector that permits to be programmed in a simple way Direct serial output RS485 ModBUS RTU compatible permits a simple XWEB interfacing RTC are available as options The HOTKEY connector can be used to connect X REP display Depending on the model 4 INSTALLATION AND MOUNTING This device can operate without any user interface but normal application is with D...

Страница 2: ... to 10Vdc Use CABCJ15 to perform the connections It s located near the terminal 39 on a 2 pin connector It s possible to use the output to control anti sweat heaters through a chopped phase controller XRPW500 500watt or family XV D or XV K 6 QUICK REFERENCE GUIDE HOW TO RUN THE SELF ADAPTIVE REGULATION IN 4 STEPS 1 After wiring the XM679K set the proper gas via Fty parameter Pre set gas is R404A 2...

Страница 3: ...c set point if the functions are enabled Exit Pressed together or wait the timeout of about 60 sec 10 MENU FOR MULTIMASTER FUNCTION SEC The function section SEC is enabled when icon is lit It allows entering in the remote programming mode from a keyboard not physically connected to the board through the LAN functionality Action Button or display Notes Enter menu Press UP arrow for about 3 sec the ...

Страница 4: ...of regulation parameter SFd percentage and SFd time Forced opening of the valve after defrost parameter oPd percentage and Pdd time 12 4 MINIMUM STABLE SUPERHEAT SEARCH AMS YES ATU YES With the parameter ATU the minimum stable superheat search function is enabled With ATU yES controllers start searching the mimimum stable value for the SH the minimum admitted value in any case is LSH 2 C 4 F Pleas...

Страница 5: ...ing to LMd parameter Selecting dPA and dPb probes and by changing the dtP and ddP parameters the defrost can be started when the difference between dPA and dPb probes is lower than dtP for all ddP time This is useful to start defrost when a low thermal exchange is detected If ddP 0 this function is disabled Defrost ending When defrost is started via rtc the maximum duration of defrost is obtained ...

Страница 6: ...pressure exceeds maximum operating pressure value instrument signals situation with MOP alarm related to PrM parameter LOP Lowest Operating Pressure threshold PA4 P20 bar psi kPA 10 if the suction pressure comes down to this value a low pressure alarm is signalled with LOP alarm related to PrM parameter dML delta MOP LOP 0 100 when a MOP alarm occurs valve will close of the dML percentage every cy...

Страница 7: ...ion dor door open dEF defrost activation AUS auxiliary activation LiG light activation OnF switch on off the instrument Htr change type of action FHU not used ES activate energy saving Hdy activate holiday function d3d Time interval delay for digital input alarm 0 255 min Time interval to calculate the number of the pressure switch activation when i3F PAL If i3F EAL or bAL external alarms d3d para...

Страница 8: ... for failed programming In this case turn the unit off and then on if you want to restart the download again or remove the Hot key to abort the operation 18 2 UPLOAD FROM THE INSTRUMENT TO THE HOT KEY 1 When the XM unit is ON insert the Hot key and push UP key 2 The UPLOAD begins the uPL message is blinking 3 Remove the Hot Key At the end of the data transfer phase the instrument displays the foll...

Страница 9: ...5 F Fod 0 Pr1 Fan activation time after defrost without compressor 0 255 min Fon 0 Pr1 Fan ON time 0 15 min FoF 0 Pr1 Fan OFF time 0 15 min trA UAL Pr2 Kind of regulation for modulating output UAL 0 rEG 1 AC 2 SOA 80 Pr2 Fixed speed for fan AMi AMA SdP 30 0 Pr2 Default Dew Point value 55 0 C 50 0 C 67 F 122 F ASr 1 0 Pr2 Differential for fan offset for anti sweat heater 25 5 C 25 5 C 45 F 45 F PbA...

Страница 10: ...ving ESP P1 Pr1 Energy saving probe selection nP 0 P1 1 P2 2 P3 3 P4 4 P5 5 tEr 6 HES 0 0 Pr1 Temperature increasing during Energy Saving 30 0 C 30 0 C 54 F 54 F PEL n Pr1 Energy saving activation when Light switched off n 0 Y 1 L A N Management LMd y Pr2 Defrost Synchronisation n 0 Y 1 dEM y Pr2 Defrost end Synchronisation n 0 Y 1 LSP n Pr2 SET POINT Synchronisation n 0 Y 1 LdS n Pr2 Display Sync...