1592023130 XM670K_XM679K GB r4.2 26.06.2017.docx
XM670K - XM679K
4/10
11.
COMMISSIONING
11.1
CLOCK SETTING AND RTC ALARM RESET
If the clock is present: [
EdF = rtC
] enable the defrost from rtc [
Ld1
to
Ld6
].
BEGIN
UP arrow (press once) to access the fast access menu
Display
HM
identify the clock RTC submenu; press
Display
HUr
= hour
press
to confirm/modify
Min
= minutes
press
to confirm/modify
……
don’t use
others parameters if present.
EXIT
Press for about 10 sec. The operation resets the RTC alarm.
Note:
the
rtC
clock menu is present also on the second level of parameters.
Warning
: if the board shows the
rtF
alarm, the device has to be changed.
11.2
ELECTRONIC VALVE SETTINGS
–
ONLY FOR XM679K
Some parameters have to be checked:
[1]
Superheat temperature probe
: Ntc, Ptc, Pt1000 with parameter
P6C
. The sensor has to be fixed at the end
of the evaporator.
[2]
Pressure transducer
: [4 to 20mA] or ratiometric
P5C = 420
or
5Vr
with parameter
P5C.
[3]
Range of measurement
: check the parameter of conversion
PA4
and
P20
that are related to the transducer.
TRANSDUCER
: [-0.5/7Bar] or [0.5/8Bar abs] the correct setup is relative pressure with PA4 = -0.5 and P20 = 7.0.
The [0.5/12Bar abs] the correct setup is relative pressure with PA4 = -0.5 and P20 = 11.00.
Example of virtual pressure with unique [4 to 20mA] or [0 to 5V] transducer:
Param.
XM6x9K_1
without transducer
XM
with
transducer
X
without
transducer
Adr
n
n + 1
n + 2
LPP
LPP = n
LPP = Y
LPP = n
P5C
LAN or not connect the
probe
P5C= 420 or 0-5V
LAN or not connect the
probe
PA4
Not used
-0.5 bar
Not used
P20
Not used
7.0 bar
Not used
[4]
From
EEV submenu
: select the correct kind of gas with
FTY parameter.
[5]
Use the following parameters to setup the right valve driving, according to the valve datasheet from the
manufacturer.
12.
KIND OF REGULATION FOR SUPERHEAT: SELF ADAPTIVE OR
MANUAL OPERATING MODE
12.1
GENERAL CONSIDERATIONS: SELF ADAPTIVE OR MANUAL SH CONTROL
The controller is able to regulate the superheat in manual or self adaptive mode, according to the value of the
parameter
AMS, autotuing enabling.
With
AMS = n: the normal SH regulation is performed
With
AMS = y: the self adaptive SH regulation is performed
12.2
MANUAL OPERATING MODE - AMS = NO
The temperature and SH regulation can be performed in 2 ways according to the value of the parameter CrE:
on/off or continuous. See below in details.Standard temperature regulation
12.2.1 ON/OFF TEMPERATURE REGULATION [CrE = n]
1.
Temperature regulation is ON/OFF and it depends on the SET point and HY parameter (dfferential) Valve
is closed when the temperature reaches the set point and open when the temperature is higher than set
point + differential.
2.
The superheat is regulated to be closer to its set point.
3.
With more pauses normally also the humidity is bigger.
4.
Regulation pauses can be realized using
Sti
and
Std
parameters (during these pauses the valve is closed).
12.2.2 COUNTINUOUS REGULATION OF THE TEMPERATURE [CrE = Y] (with
superheat regulation):
1.
The
HY
parameter becomes temperature band for PI control. A default good value is
6°C.
2.
The regulation of injection is continuous and the cooling output is always on. The icon
is always ON
excluding the defrost phase.
3.
The superheat is regulated following the
SSH
parameter.
4.
Regulation pauses can be realized using
Sti
and
Std
parameters (during these pauses the valve is closed).
5.
Increasing the
Int
integral time it is possible to decrease the speed of reaction of the regulator on the
HY
band.
12.3
SELF ADAPTIVE OPERATING MODE
–
AMS = YES
Auto-adaptive means to find and maintain the condition of the lowest super heating according to the load and
environmental conditions present in a given time on the evaporator.
The parameter
AMS
enables the self adaptive mode for the superheat regulation.
In this functioning the values of Pb and inC parameter are automatically set by the controller according to the kind
of applications and the response of the system.
With the
AMS = YES, CrE
must be set at
NO
.
The self adaptive algorithm does not affect
, the functions related to the forced opening of the valve in special
situation such as:
Forced opening of the valve at start of regulation,
parameter
SFd
(percentage) and
SFd
(time).
Forced opening of the valve after defrost,
parameter
oPd
(percentage) and
Pdd
(time).
12.4
MINIMUM STABLE SUPERHEAT SEARCH - AMS = YES, ATU = YES
With the parameter
ATU,
the minimum stable superheat search function is enabled
.
With ATU = yES
controllers start searching the mimimum stable value for the SH, the minimum admitted value in
any case is LSH + 2°C (4°F).
Please take it in consideration, before setting LSH value.
12.5
VALVE CAPACITY REDUCING
–
MNF PARAMETER
Thanks to the parameter MnF it’s possible to reduce the capacity of the valve, to fine tune the valve to the
evaporator.
The regulation band is not affected from the modification of the MnF parameter.
See below the behaviour of the capcity of the valve, when the MnF parameter is adjusted.
NOTE: during the soft start phase (oPE, SFd), MnF parameter is not taken in consideration and the
capacity of the valve is set by the parameters oPE and oPd,
respectively
.
12.6
PRESSURE FILTERING
–
SUB PARAMETER
For a good SH regulation, it’s important to use a filtered value of the pressure.
This can be done by the parameter Sub.
Suggested values:
From 1-5 evaporators for each racks: Sub = 20
From 6-30 evaporators for each racks: Sub = 15
More than 30 evaporators for each racks: Sub =10
13.
DISPLAY MESSAGES
Display
Causes
Notes
KEYBOARD
1
nod
No display: the keyboard is trying to work with
another board that is not working or not
present
Press for 3 sec UP arrow, enter the
SEC
menu and select
LOC
entry.
2
Pon
Keyboard is unlocked
3
PoF
Keyboard is locked
4
rSt
Alarm reset
Alarm output deactivated
5
noP, nP
nA
Not present (configuration)
Not available (evaluation)
6
noL
The keyboard is not able to communicate with
the XM670-XM679K
Verify the connection. Call the Service
ALARM FROM PROBE INPUT
6
P1
P2
P3
P4
P5
P6
PPF
CPF
Sensor brake down, value out of range or
sensor incorrectly configured
P1C
,
P2C
to
P6C
.
PPF
can be showed by slaves of pressure
that don’t receive the value of pressure.
CPF
is showed when the remote probe 4 is
not working.
P1
: the cooling output works with
Con
and
COF
,
With defrost probe on error the defrost is
performed only at interval.
For
P5
,
P6
and
PPF
: the percentage of
the valve opening is fixed at
PEO
value.
TEMPERATURE ALARM
7
HA
Temperature alarm from parameter ALU on
probe
rAL
.
Outputs unchanged.
8
LA
Temperature alarm from parameter ALL on
probe
rAL
.
Outputs unchanged.
"HAd
Defrost high temperature
Outputs unchanged.
"LAd”
Defrost low temperature
Outputs unchanged.
"FAd”
Fan low temperature
Outputs unchanged.
"HAF”
Fan high temperature
Outputs unchanged.
DIGITAL INPUT ALARM
13
dA
Door open alarm from input
i1F
,
i2F
or
i3F
=
after delay
d1d
,
d2d
or
d3d
.
Cooling relay and fan follow the
odc
parameter. Cooling restart as specified
on
rrd
parameter.
14
EA
Generic alarm from digital input
i1F
,
i2F
,
i3F
=
EAL
.
15
CA
Severe alarm of regulation lock from digital
input
i1F
,
i2F
,
i3F
=
bAL
.
Regulation output OFF.
16
PAL
Pressure switch lock
i1F
,
i2F
o
i3F
=
PAL
.
All the outputs are OFF.
ELECTRONIC VALVE ALARM
17
LOP
Minimum operating pressure threshold from
LOP
parameter.
The valve output increases its opening of
dML
quantity every second.
18
MOP
Maximum operating pressure threshold from
MOP parameter.
The valve output decreases its opening
of
dML
quantity every second.
19
LSH
Low superheating from
LSH
parameter and
SHd
delay.
The valve will be closed; the alarm will
be showed after
SHd
delay.
20
HSH
High superheating from
HSH
parameter and
SHd
delay.
Only display.
CLOCK ALARM
21
rtC
Clock settings lost.
Defrost will be performed with
IdF
till
restoring the settings of RTC.
22
rtF
Clock damaged.
Defrost will be performed with
IdF
.
OTHERS
23
EE
EEPROM serious problem.
Output OFF.
24
Err
Error with upload/download parameters.
Repeat the operation.
25
End
Parameters have been correctly transferred.
13.1
ALLARM RECOVERY
Probe alarms
P1
,
P2,
P3
and
P4
start some seconds after the fault in the related probe; they automatically stop
some seconds after the probe restarts normal operation. Check connections before replacing the probe.
Temperature alarms
HA
,
LA,
HA2
and
LA2
automatically stop as soon as the temperature returns to normal
values.
Alarms
EA
and
CA
(with
i1F
=
bAL
)
recover as soon as the digital input is disabled. Alarm
CA
(with
i1F
=
PAL
)
recovers only by
switching off and on
the instrument.