Emerson Dixell XM668D Скачать руководство пользователя страница 8

 

1592023040 XM668D GB r1.1 2011.07.05.doc 

XM668D  

          

8/14 

 

DEFAULT PARAMETER MAP 

The numbers of the first column are simple indexes that are unrelated to the position on the device menu. The total amount of parameters can be different depending on the 
applications. 

SUBMENUS

: the parameters O1...O24 of the clock belongs to 

rtC

 label; V1...V30 

ELECTRON

IC VALVE belongs to EEV. 

 

 

LABEL 

VALUE 

DESCRIPTION 

RANGE 

NOTES 

 

rtC 

 

CLOCK  AND  DEFROST 

By  pressing  SET  it’s 

possible to enter on RTC submenu 

 

Access to CLOCK submenu (if present)

 

 

CbP 

Clock Presence 

n; Y 

 

Hur 

- - - 

Hours. 

- - - 

 

Min 

- - - 

Minutes. 

- - - 

 

dAY 

- - - 

Day of the week. 

Sun(0); SAt(6) 

 

Hd1 

nU 

First weekly day. 

Sun(0); SAt(6); nu(7) 

Set  the  first  day  of  the  week  which  follows  the  holiday 
times. 

 

Hd2 

nU 

Second weekly day. 

Sun(0); SAt(6); nu(7) 

Set  the  second  day  of  the  week  which  follows  the 
holiday times. 

 

Hd3 

nU 

Third weekly day. 

Sun(0); SAt(6); nu(7) 

Set the third day of the week which follows the holiday 
times. 

 

iLE 

0.0 

Energy saving cycle start during workdays. 

0.0 to 23h50min (143) 

During  the  Energy  Saving  cycle  the  set  point  is 
increased by the value in 

HES

 so that the operation set 

point is 

[SET + HES].  

Format

: hours.10min, 

resolution

: 10min. 

 

dLE 

0.0 

Energy saving cycle length during workdays. 

0.0 to 24h00min (144) 

Set  the  duration  of  the  Energy  Saving  cycle  on 
workdays.  

Format

: hours.10min, 

resolution

: 10min. 

 

iSE 

0.0 

Energy saving cycle start during holidays. 

0.0 to 23h50min (143) 

Format

: hours.10min, 

resolution

: 10min. 

 

dSE 

0.0 

Energy saving cycle length during holidays. 

0.0 to 24h00min (144) 

Format

: hours.10min, 

resolution

: 10min. 

 

HES 

0.0 

Temperature increasing during Energy Saving cycle 
(Day/Night). 

[-30.0°C to 30.0°C]  

[-54°F to 54°F] 

Set  the  increasing  value  of  the  set-point  during  the 
Energy Saving cycle. 

 

Ld1  

6.0 

Workdays First defrost start. 

0.0 to 23h50min (143)  

nU (144) 

Workdays  defrost  start:  [Ldn  to  23h50min]

  these 

parameters 

set 

the 

beginning 

of 

the 

eight 

programmable  defrost  cycles  during  workdays. 

Ex:

 

when 

[Ld2  =  12.4]

  the  second  defrost  starts  at  12.40 

during workdays.  

nU 

= not used.  

Format

: hours.10min, 

resolution

: 10min. 

 

Ld2  

13.0 

Workdays Second defrost start. 

Ld1 to 23h50min (143)  

nU (144) 

 

Ld3  

21.0 

Workdays Third defrost start. 

Ld2 to 23h50min (143)  

nU (144) 

 

Ld4 

nU 

Workdays Fourth defrost start. 

Ld3 to 23h50min (143)  

nU (144) 

 

Ld5 

nU 

Workdays Fifth defrost start. 

Ld4 to 23h50min (143)  

nU (144) 

 

Ld6 

nU 

Workdays Sixth defrost start. 

Ld5 to 23h50min (143)  

nU (144) 

 

Sd1  

6.0 

Holidays First defrost start. 

0.0 to 23h50min (143)  

nU (144) 

Holidays  defrost  start:  [Sdn  to  23h50min]

  these 

parameters 

set 

the 

beginning 

of 

the 

eight 

programmable  defrost  cycles  on  holidays. 

Ex:

  when 

[Sd2  =  3.4]

  the  second  defrost  starts  at  3.40  on 

holidays.  

nU 

= not used.  

Format

: hours.10min, 

resolution

: 10min. 

 

Sd2  

13.0 

Holidays Second defrost start. 

Sd1 to 23h50min (143)  

nU (144) 

 

Sd3  

21.0 

Holidays Third defrost start. 

Sd2 to 23h50min (143)  

nU (144) 

 

Sd4 

nU 

Holidays Fourth defrost start. 

Sd3 to 23h50min (143)  

nU (144) 

 

Sd5 

nU 

Holidays Fifth defrost start. 

Sd4 to 23h50min (143)  

nU (144) 

 

Sd6 

nU 

Holidays Sixth defrost start. 

Sd5 to 23h50min (143)  

nU (144) 

 

EEU 

 

ELECTRONIC VALVE  

 

By  pressing  SET  you  can  enter  electronic  expansion 
valve submenu. 

 

FtY 

404 

Kind of gas. 

R22(0); 134(1); 404(2); 407(3);  

410(4); 507(5); CO2(6) 

Type  of  gas  used  by  plant. 

Fundamental  parameter 

for correct functioning of all system

 

SSH 

8.0 

Superheat set point. 

[0.1°C to 25.5°C] 

[1°F to 45°F] 

This is the value used to regulate superheat. 

 

Pb 

6.0 

Proportional band. 

[0.1°C to 60.0°C] 

 [1°F to 108°F] 

The valve changes its opening on the band 

[SSH

SSH 

+  Pb]

.  At 

SSH

  value  of  superheat  the  valve  will  be  at 

0%  (without  integral  contribution)  and  at 

[SSH  +  Pb]

 

value of superheat the valve will be at 

MnF

. For values 

bigger  than 

[SSH  +  Pb]

  the  valve  is  completely 

opened. 

 

inC 

120 

Integration time for superheat regulation. 

 0 to 255s 

 

PEO 

50 

Valve opening in case of error on probes P5 or P6. 

0 to 100% 

If  a  temporary  probe  error  occurs,  valve  opening 
percentage is 

PEo 

until 

PEd 

time is elapsed. 

 

OPE 

85 

Start opening percentage for the time 

SFd

0 to 100% 

Opening valve percentage when start function is active. 
This phase duration is 

SFd 

time. 

 

SFd 

1.3 

Duration of soft start phase with opening at 

OPE

0.0 to 42min00sec (252) 

Set  start  function  duration  and  post-defrost  duration. 

During this phase the alarms are neglected.  
Format

: min.10sec, 

resolution

: 10 sec. 

 

OPd 

100 

Post  defrost  opening  percentage  for  all  the  time 

PddB

0 to 100% 

Opening  valve  percentage  when  after  defrost  function 
is active. This phase duration is 

Pdd 

time. 

 

Pdd 

1.3 

Duration of post defrost phase. 

0.0 to 42min00sec (252) 

Set  start  function  duration  and  post-defrost  duration. 

During this phase the alarms are neglected.  
Format

: min.10sec, 

resolution

: 10 sec. 

 

MnF 

100 

Maximum  percentage  of  opening  admitted  (during 
normal functioning). 

0 to 100% 

During  regulation  it  sets  the  maximum  valve  opening 
percentage. 

 

Fot 

nU 

Manual opening. 

0 to 100% 

nU 

It  permits  to  force  the  valve  opening  to  the  specified 
value. This value overwrites the one calculated by  PID 
algorithm.  

!!!! WARNING !!!! 
It  must  be  [Fot  =  nU]  to  have  correct  superheat 
regulation.

 

Содержание Dixell XM668D

Страница 1: ...on is with Dixell CX660 keyboard Figure 1a Figure 1b The CX660 keyboard shall be mounted on vertical panel in a 29x71 mm hole and fixed using the special bracket supplied as shown in fig 1a 1b The temperature range allowed for correct operation is 0 to 60 C Avoid places subject to strong vibrations corrosive gases excessive dirt or humidity The same recommendations apply to probes Let air circulat...

Страница 2: ...pressing UP ARROW button the user will be able to enter a fast selection menu and to read the value of the following parameters dPP measured pressure only on master device dP5 value of temperature obtained from pressure temperature conversion rPP pressure value read from remote location only for slave devices Examples of error messages dPP Err the local transducer read a wrong value the pressure i...

Страница 3: ...S TO PR2 To enter Pr2 programming menu 1 access the Pr1 menu by pressing both SET DOWN keys for 3 sec the first parameter label will be showed 2 press DOWN key untill the Pr2 label will be showed then press SET key 3 The blinking PAS label will be showed wait some seconds 4 Will be showed 0 with blinking 0 insert the password 321 using the keys UP and DOWN and confirming with SET key GENERAL STRUC...

Страница 4: ...0 CPP mA 10 CHd mA 10 Sr step s 0 Manual settings Par Par Par Par Par 1 Alco EX4 EX5 EX6 5 75 50 10 500 2 Alco EX7 10 160 75 25 500 3 Alco EX8 500 step s 10 260 80 50 500 4 Danfoss ETS 25 50 7 262 10 10 300 5 Danfoss ETS 100 10 353 10 10 300 6 Danfoss ETS 250 400 11 381 10 10 300 7 Sporlan SEI 5 to 11 0 159 16 5 200 8 Sporlan SER 1 5 to 20 0 159 12 5 200 9 Sporlan SEI 30 0 319 16 5 200 10 Sporlan ...

Страница 5: ...cond 18 MOP Maximum operating pressure threshold from MOP parameter The valve output decreases its opening of dML quantity every second 19 LSH Low superheating from LSH parameter and SHd delay The valve will be closed the alarm will be showed after SHd delay 20 HSH High superheating from HSH parameter and SHd delay Only display CLOCK ALARM 21 rtC Clock settings lost Defrost will be performed with ...

Страница 6: ...detected If ddP 0 this function is disabled Defrost ending When defrost is started via rtC the maximum duration of defrost is obtained from Md parameter and the defrost end temperature is obtained from dtE parameter and dtS if two defrost probes are selected If dPA and dPb are present and d2P Y the instrument stops the defrost procedure when dPA is higher than dtE temperature and dPb is higher tha...

Страница 7: ...l inputs 3 free of voltage Relay outputs Total current on loads MAX 16A Solenoid Valve relay SPST 5A 250Vac Defrost relay SPST 16A 250Vac Fan relay SPST 8A 250Vac Light relay SPST 16A 250Vac Alarm SPDT relay 8A 250Vac Aux SPST relay 8A 250Vac Outputs for valve bipolar or unipolar valves Optional output AnOUT DEPENDING ON THE MODELS PWM Open Collector outputs PWM or 12Vdc max 40mA Analog output 4 t...

Страница 8: ...efrost start 0 0 to 23h50min 143 nU 144 Holidays defrost start Sdn to 23h50min these parameters set the beginning of the eight programmable defrost cycles on holidays Ex when Sd2 3 4 the second defrost starts at 3 40 on holidays nU not used Format hours 10min resolution 10min Sd2 13 0 Holidays Second defrost start Sd1 to 23h50min 143 nU 144 Sd3 21 0 Holidays Third defrost start Sd2 to 23h50min 143...

Страница 9: ...d LSH SHY 0 1 C to 25 5 C 1 F to 45 F SHd 3 0 Delay of superheat alarm signaling 0 0 to 42min00sec 252 If a superheat alarm occurs the delay time SHd will have to expire before the controller shows an alarm Format min 10sec resolution 10sec FrC 0 Integration additive constant Fast recovery 0 to 100s Permits to increase integral time when SH value is below the set point If FrC 0 fast recovery funct...

Страница 10: ...e changes the display will be updated of 1 C 1 F when delay time expires Format min 10sec resolution 10sec rPA P1 Regulation probe A nP 0 P1 1 P2 2 P3 3 P4 4 P6 5 First probe used to regulate room temperature If rPA nP the regulation is performed with real value of rPb rPb nP Regulation probe B nP 0 P1 1 P2 2 P3 3 P4 4 P6 5 Second probe used to regulate room temperature If rPb nP the regulation is...

Страница 11: ...during the defrost Fnd 10 Fan delay after defrost 0 to 255min The time interval between the ending of the defrost and the starting of the evaporator fans FSt 10 0 Fan stop temperature 55 0 C to 50 0 C 67 F to 122 F Evaporator probe temperature above which the fan is always OFF FHY 1 0 Fan stop differential 0 1 C to 25 5 C 1 F to 45 F When stopped fan restarts when fan probe reaches FSt FHY value o...

Страница 12: ...0min 144 After powering on the instrument time interval between the detection of the temperature alarm condition and the alarm signaling Format hours 10min resolution 10min EdA 20 Alarm delay at the end of defrost 0 to 255min At the end of the defrost cycle time interval between the detection of the temperature alarm condition and the alarm signaling dot 20 Temperature alarm exclusion after door o...

Страница 13: ...en LiG light switched off AUS AUX switched off LEA both light and AUX switched off If nU then not used function LAN MANAGEMENT LMd Y Defrost Synchronization n Y n the section doesn t send a global defrost command Y the section sends a command to start defrost to other controllers dEM Y Defrost end Synchronization n Y n the end of the LAN defrosts are independent Y the end of the LAN defrosts are s...

Страница 14: ...ceived from master o5 0 P5 calibration 12 0 C to 12 0 C Allows to adjust possible offset of the probe 5 P6C PtM P6 configuration nP PtC ntC PtM nP not present PtC Ptc ntC ntc PtM Pt1000 o6 0 P6 calibration 12 0 C to 12 0 C Allows to adjust possible offset of the probe 6 SERVICE CLt ON OFF percentage C R O read only It shows the effective cooling time calculated by XM600 during regulation cooling t...

Отзывы: