![Emerson Dixell XM668D Скачать руководство пользователя страница 2](http://html.mh-extra.com/html/emerson/dixell-xm668d/dixell-xm668d_installing-and-operating-instructions_102149002.webp)
1592023040 XM668D GB r1.1 2011.07.05.doc
XM668D
2/14
5-6 WIRES VALVES (UNIPOLAR)
Connection
numbering
SPORLAN
SAGINOMIYA
45
ORANGE
ORANGE
46
RED
RED
47
YELLOW
YELLOW
48
BLACK
BLACK
49 – Common
GRAY
GRAY
AFTER MAKING THE CONNECTION, PLEASE SWITCH OFF AND ON THE
CONTROLLER IN ORDER TO BE SURE OF THE RIGHT POSITIONING OF THE
VALVE.
4.4
ABSOLUTE MAXIMUM POWER
XM668D
is able to drive a wide range of stepper valves, on the following table are
indicated the maximum values of current that the actuator can supply to the stepper
wiring. The
TF20D
dIXEL
transformer
has to be used.
NOTE:
the
electrical power absorption of the valve can be unrelated to refrigeration
power that valve has. Before using the actuator, please read the technical manual of
the valve supplied by the manufacturer and check the maximum current used to drive
the valve in order to verify that they are lower than those indicated below.
V
A
L
V
E
T
Y
P
E
BIPOLAR VALVES
(4 wires)
Maximum Current
0.9A
UNIPOLAR VALVES
(5-6 wires)
Maximum Current
0.33A
4.5
KEYBOARD DISPLAY CX660
The
XM668D
board can operate also without keyboard.
Polarity:
Terminal [
34
] [-]
Terminal [
35
] [+]
Use shielded cable in
case of long distance.
4.6
SYNCHRONIZED DEFROST – MAXIMUM 8 SECTIONS
Follow next steps to create a LAN connection, which is a necessary condition to
perform synchronized defrost (also called master-slave functioning):
1) Connect a shielded cable between terminals [
38
] [-] and [
39
] [+] for a
maximum
of 8 sections
;
2) The value of parameter
Adr
is the number to identify each electronic board.
Address duplication is not permitted
, in this case the synchronized defrost
and the communication with monitoring system is not guaranteed (the
Adr
is
also the ModBUS address). For example, a correct configuration could be the
following:
If the LAN is well connected, the green LED will be ON. If the green LED blinks
then the connection is wrongly configured.
4.7
SENSORS FOR SUPERHEAT CONTROL
Temperature probe:
Pb6
terminals [
19
] - [
20
] without
any polarity.
Select the kind of sensor with
P6C
parameter.
Pressure transducer: Pb5
terminals:
[
21
] = input of the signal; [
22
] = Power Supply for
4to20mA transducer; [
20
] = GND; [
23
] = +5Vdc power
supply for ratiometric pressure transducer.
Select the configuration of the transducer with parameter
P5C
.
4.8
HOW TO USE ONLY ONE PRESSURE TRANSDUCER ON MULTIPLEXED
APPLICATIONS
A working LAN connection is required (green LED lit on all XM668D boards of the
same LAN). Connect and configure a pressure transducer only on
one
XM668D of
the network. Afterwards, the value of pressure read by the unique transducer
connected will be available to each device connected to the same LAN.
By pressing
UP ARROW
button, the user will be able to enter a fast selection menu
and to read the value of the following parameters:
dPP
= measured pressure (only on master device);
dP5
= value of temperature obtained from pressure
temperature conversion;
rPP
= pressure value read from remote location (only for slave devices).
Examples of error messages:
dPP = Err
the local transducer read a wrong value, the pressure is out of the
bounds of the pressure transducer or the
P5C
parameter is wrong. Check all
these options and eventually change the transducer;
rPF
the remote pressure transducer is on error situation. Check the status of the
onboard GREEN LED: if this LED is OFF the LAN is not working, otherwise
check the remote transducer.
LAST CHECKS ABOUT SUPERHEAT
On the fast access menu:
dPP
is the value read by the gauge;
dP6
is the value read by the temperature probe, temperature of the gas on the outlet
section of the evaporator;
SH
is the value of the superheat. The
nA
or
Err
messages mean that the superheat
has no sense in that moment and its value is not available.
4.9
HOW TO CONNECT MONITORING SYSTEM
1)
Terminals [
36
] [-] and [
37
] [+].
2)
Use shielded twisted cable. For
example Belden® 8762 o 8772 or cat 5
cables.
3)
Maximum distance 1Km.
4)
Don’t connect the shield to the earth or
to GND terminals of the device, avoid
accidental contacts by using insulating
tape.
Only one device for each LAN has to be connected to the RS485 connection.
The value of parameter
Adr
is the number to identify each electronic board.
Address
duplication is not permitted
, in this case the synchronized defrost and the
communication with monitoring system is not guaranteed (the
Adr
is also the
ModBUS address).
4.10
DIGITAL INPUTS
1)
The terminals from [
30
] to [
33
] are all
free of voltage;
2)
Use shielded cable for distance higher
than one meter;
For each input, has to be configured: the
polarity of activation, the function of the input
and the delay of signaling.
The parameters to perform this configuration are
i1P
,
i1F
,
i1d
respectively for
polarity, functioning and delay. The
i1P
can be:
cL
= active when closed;
oP
= active
when opened. The
i1F
parameter can be:
EAL
= external alarm,
bAL
= serious lock
alarm,
PAL
= pressure switch alarm,
dor
= door switch,
dEF
= external defrost,
AUS
= auxiliary activation command,
LiG
= light activation,
OnF
= board On/OFF,
FHU
=
don’t use this configuration,
ES
= day/night,
HdY
= don’t use this configuration. Then
there is
i1d
parameter for delay of activation. For the others digital inputs there are a
set of the same parameters:
i2P
,
i2F
,
i2d
,
i3P
,
i3F
,
i3d
.
4.11
ANALOG OUTPUT
Selectable between 4 to 20mA and
0 to 10Vdc.
Use CABCJ15 to perform the
connections
It’s located near the terminal [
39
] on a 2-pin connector. It’s possible to use the output
to control anti-sweat heaters through a chopped phase controller XRPW500
(500watt) or family XV...D or XV...K.