Emerson Dixell XM668D Скачать руководство пользователя страница 4

 

1592023040 XM668D GB r1.1 2011.07.05.doc 

XM668D  

          

4/14 

 

 

Action 

Button or 

display 

Notes 

Enter 
menu 

 

Press UP arrow for about 3 sec, the 

 icon will be 

ON. 

Waiting 
for action 

SEC 

The menu to change the section will be entered. 

SEC 

label will be displayed. 

Enter 
section 
list 

 

Press 

SET 

to confirm. The following list will be 

available to select the proper network function. 

Select 
proper 
function 

 

 

Or 

 

 

 

LOC 

ALL 

SE1 

SEn 

SE8 

To gain access only to the local device. 

To gain access to all the devices connected to the 

LAN. 

To gain access to the device with 1st 

Adr

 (*) 

… 

To gain access to the device with 8th 

Adr

 (*) 

Confirm 

 

Select and confirm an entry by pressing 

SET

 button. 

Exit menu 

 

Press 

SET

 and 

UP

 together or wait about 10 

seconds. 

(*) The devices on the LAN are indexed by using the 

Adr

 parameter (in ascending 

order).  
 

EXAMPLES: 

1. 

To modify the same parameter values in all the devices connected to the LAN: 
enter multimaster menu. Select and confirm 

ALL

. Exit from multimaster menu. 

Enter the programming menu and change the required parameter values. 
The new values will be changed on all devices connected to the LAN. 

2. 

To  modify  a  parameter  value  in  the  device  with  [

Adr  =  35

]:  find  the  relevant 

indexed section (the one linked to [

Adr = 35

]). Enter multimaster menu. Select 

and  confirm  this  section  from  the  multimaster  menu.  Exit  from  multimaster 
menu. Enter the programming menu and change the required parameter value. 

3. 

If the alarm 

nod

 is present: enter the multimaster menu. Select and confirm the 

LOC 

section. Exit from multimaster menu. 

 

  AT  THE  END  OF  THE  PROGRAMMING  PROCEDURE,  SELECT  THE 

SECTION “LOC”. IN THIS WAY THE ICON 

 

WILL BE SWITCHED OFF!! 

9.

 

COMMISSIONING 

9.1

 

CLOCK SETTING AND RTC ALARM RESET 

Parameter configuration: [

CbP = Y

] enable the clock, [

EdF =  rtC

] enable the  defrost 

from rtc 

Ld1...Ld6

 

BEGIN 

 

UP arrow (press once) to access the fast access 

menu 

Display 

HM

 identify the clock RTC submenu; press 

 

Display 

HUr 

= hour 

 press 

 to confirm/modify 

Min 

= minutes 

 press 

 to confirm/modify 

……  

don’t use

 others parameters if present. 

EXIT 

 

Press for about 10 sec. The operation resets the RTC 
alarm. 

 
Note:

 the 

rtC

 clock menu is present also on the second level of parameters. 

Warning

: if the board shows the 

rtF

 alarm, the device has to be changed. 

9.2

 

   ELECTRONIC VALVE SETTINGS 

Some parameters have to be checked: 

[1]

 

Superheat  temperature  probe

:  Ntc,  Ptc,  Pt1000  with  parameter 

P6C

.  The 

sensor has to be fixed at the end of the evaporator. 

[2]

 

Pressure  transducer

:  [4  to  20mA]  or  ratiometric 

P5C  =  420

  or 

5Vr

  with 

parameter 

P5C.

 

[3]

 

Range  of  measurement

:  check  the  parameter  of  conversion 

PA4

  and 

P20

  that 

are related to the transducer.  

TRANSDUCER

:  [-0.5/7Bar]  or  [0.5/8Bar  abs]  the  correct  setup  is  relative  pressure 

with  PA4  =  -0.5  and  P20  =  7.0.  The  [0.5/12Bar  abs]  the  correct  setup  is  relative 
pressure with PA4 = -0.5 and P20 = 11.00. 
 
Example of virtual pressure with unique [4 to 20mA] or [0 to 5V] transducer: 

Param. 

XM6x8D_1 

without transducer 

XM 

with 

transducer 

without transducer 

Adr 

n  

n + 1 

n + 2 

LPP 

LPP = n 

LPP = Y 

LPP = n 

P5C 

LAN or not connect 

the probe 

P5C= 420 or 0-5V 

LAN or not connect 

the probe 

PA4 

Not used 

-0.5 bar 

Not used 

P20 

Not used 

7.0 bar 

Not used 

 

[4]

 

From

 

EEV submenu

: select the correct kind of gas with 

FTY parameter.

 

[5]

  Use  the  following  parameters  to  setup  the  right  valve  driving,  according  to  the 

valve datasheet from the manufacturer. 

tEU 

Type of Stepper motor: 

[

uP

-

bP

] it permits to select the kind of valve. 

uP =

 5 - 

6  wires  unipolar  valves; 

bP  =

  4  wires  bipolar  valves; 

!!!!!  WARNING  !!!!!  by 

changing this parameter the valve has to be reinitialized. 

tEP 

Predefined  valve  selection: 

[0  to  10]  if  [

tEP  =  0

]  the  user  has  to  modify  all 

the  parameters  of  configuration  in  order  to  use  the  valve.  If 

tEP  is  different 

from  0

  the  device  performs  a  fast  configuration  of  the  following  parameters: 

LSt, uSt, Sr, CPP, CHd

. To select the right number please read the following 

table: 

 
 

tEP 

Model 

LSt 

(steps*10)

 

uSt 

(steps*10)

 

CPP 

(mA*10)

 

CHd 

(mA*10)

 

Sr 

(step/s)

 

Manual settings 

Par 

Par 

Par 

Par 

Par 

Alco EX4-EX5-EX6 

75 

50 

10 

500 

Alco EX7 

10 

160 

75 

25 

500 

Alco EX8 500 step/s 

10 

260 

80 

50 

500 

Danfoss ETS-25/50 

262 

10 

10 

300 

Danfoss ETS-100 

10 

353 

10 

10 

300 

Danfoss ETS-

250/400 

11 

381 

10 

10 

300 

Sporlan SEI .5 to 11 

159 

16 

200 

Sporlan SER 1.5 to 

20 

159 

12 

200 

Sporlan SEI 30 

319 

16 

200 

10 

Sporlan SER(I) G,J,K 

250 

12 

200 

11 

Sporlan SEI-50 

638 

16 

200 

12 

Sporlan SEH(I)-100 

638 

16 

200 

13 

Sporlan SEH(I)-175 

638 

16 

200 

 
 

If 

tEP is different from 0

 previous configuration of 

LSt, uSt, Sr, CPP  and CHd are 

overwritten. 

LSt 

Minimum  number  of  steps: 

[

0

  to 

USt

]  it  permits  to  select  the  minimum 

number  of  steps.  At  this  number  of  steps  the  valve  should  be  closed.  So  it’s 
necessary  the  reading  of  manufacturer  datasheet  to  set  correctly  this 
parameter.  It’s  the  minimum  number  of  steps  to  stay  in  advised  range  of 
functioning. 

!!!!! WARNING  !!!!!  By changing this parameter the valve has 

to be reinitialized. The device performs this procedure automatically and 
restarts its normal functioning when the programming mode ends.

 

USt 

Maximum number of steps: 

[LSt to 800*10] it permits to select the maximum 

number  of  steps.  At  this  number  of  steps  the  valve  should  be  completely 
opened.  Read  the  datasheet  provided  by  manufacturer  of  the  valve  to  set 
correctly this parameter. It’s the maximum number of steps to stay in advised 
range  of  functioning. 

!!!!!  WARNING  !!!!!  By  changing  this  parameter  the 

valve  has  to  be  reinitialized.  The  device  performs  this  procedure 
automatically and restarts its normal functioning when the programming 
mode ends.

 

Sr 

Step rate 

[10 to 600 step/sec] it’s the maximum speed to change step without 

losing  precision  (means  without  losing  steps).  It’s  advised  to  stay  under  the 
maximum speed. 

CPP  Current per phase (only bipolar valves): 

[0 to 100*10mA] it’s the maximum 

current per phase used to drive valve. It’s used 

only with bipolar valves

.

 

CHd  Holding  current  per  phase  (only  bipolar  valves): 

[0  to  100*10mA]  it’s  the 

current per phase when the valve is stopped for more than 4 minutes. It’s used 

only with bipolar valves

 

9.3

 

   ELECTRONIC VALVE FUNCTIONING 

ON/OFF TEMPERATURE REGULATION

 

[CrE = n]

 

1. 

The

 HY

 parameter is a differential [2°C default]. 

2. 

The temperature regulation is ON/OFF with valve stop at set point. 

3. 

The superheat is regulated to be closer to its set point. 

4. 

With more pauses normally also the humidity is bigger. 

5. 

Regulation pauses can be realized using 

Sti

 and 

Std 

parameters (during these 

pauses the valve is closed). 

 
COUNTINUOUS REGULATION OF THE TEMPERATURE [CrE=Y] (with superheat 
regulation)

1. 

The 

HY

  parameter  becomes  temperature  band  for  PI  control.  A  default  good 

value is 

5°C.

 

2. 

The  regulation  of  injection  is  continuous  and  the  cooling  output  is  always  on. 
The icon 

 is always ON excluding the defrost phase.  

3. 

The superheat is regulated following the 

SSH

 parameter. 

4. 

Regulation pauses can be realized using 

Sti

 and 

Std 

parameters (during these 

pauses the valve is closed). 

5. 

Increasing the 

Int

 integral time it is possible to decrease the speed of reaction 

of the regulator on the 

HY

 band. 

 

COUNTINUOUS  REGULATION  OF  THE  TEMPERATURE  [CrE=Y]  (without 
superheat regulation)

1. 

The 

HY

  parameters  become  temperature  band  for  PI  control.  A  default  good 

value is 

5°C.

 

2. 

The  regulation  of  injection  is  continuous  and  the  cooling  output  is  always  on. 
The icon 

 is always ON excluding the defrost phase. 

3. 

The  superheat  is  not  regulated  because  the  valve  is  at  the  end  of  the 
evaporator. At the beginning of the evaporator there is another valve. 

4. 

Regulation pauses can be realized using 

Sti

 and 

Std 

parameters (during these 

pauses the valve is closed). 

5. 

Increasing the 

Int

 integral time it is possible to decrease the speed of reaction 

of the regulator on the 

HY

 band. 

9.4

 

SYNCHRONIZED DEFROST 

The  synchronized  defrost  allow  to  manage  multiple  defrost  from  different  boards 
connected  through  the  LAN  connection.  In  this  way,  the  boards  can  perform 
simultaneous defrosts with the possibility to end them in a synchronized way. 

Содержание Dixell XM668D

Страница 1: ...on is with Dixell CX660 keyboard Figure 1a Figure 1b The CX660 keyboard shall be mounted on vertical panel in a 29x71 mm hole and fixed using the special bracket supplied as shown in fig 1a 1b The temperature range allowed for correct operation is 0 to 60 C Avoid places subject to strong vibrations corrosive gases excessive dirt or humidity The same recommendations apply to probes Let air circulat...

Страница 2: ...pressing UP ARROW button the user will be able to enter a fast selection menu and to read the value of the following parameters dPP measured pressure only on master device dP5 value of temperature obtained from pressure temperature conversion rPP pressure value read from remote location only for slave devices Examples of error messages dPP Err the local transducer read a wrong value the pressure i...

Страница 3: ...S TO PR2 To enter Pr2 programming menu 1 access the Pr1 menu by pressing both SET DOWN keys for 3 sec the first parameter label will be showed 2 press DOWN key untill the Pr2 label will be showed then press SET key 3 The blinking PAS label will be showed wait some seconds 4 Will be showed 0 with blinking 0 insert the password 321 using the keys UP and DOWN and confirming with SET key GENERAL STRUC...

Страница 4: ...0 CPP mA 10 CHd mA 10 Sr step s 0 Manual settings Par Par Par Par Par 1 Alco EX4 EX5 EX6 5 75 50 10 500 2 Alco EX7 10 160 75 25 500 3 Alco EX8 500 step s 10 260 80 50 500 4 Danfoss ETS 25 50 7 262 10 10 300 5 Danfoss ETS 100 10 353 10 10 300 6 Danfoss ETS 250 400 11 381 10 10 300 7 Sporlan SEI 5 to 11 0 159 16 5 200 8 Sporlan SER 1 5 to 20 0 159 12 5 200 9 Sporlan SEI 30 0 319 16 5 200 10 Sporlan ...

Страница 5: ...cond 18 MOP Maximum operating pressure threshold from MOP parameter The valve output decreases its opening of dML quantity every second 19 LSH Low superheating from LSH parameter and SHd delay The valve will be closed the alarm will be showed after SHd delay 20 HSH High superheating from HSH parameter and SHd delay Only display CLOCK ALARM 21 rtC Clock settings lost Defrost will be performed with ...

Страница 6: ...detected If ddP 0 this function is disabled Defrost ending When defrost is started via rtC the maximum duration of defrost is obtained from Md parameter and the defrost end temperature is obtained from dtE parameter and dtS if two defrost probes are selected If dPA and dPb are present and d2P Y the instrument stops the defrost procedure when dPA is higher than dtE temperature and dPb is higher tha...

Страница 7: ...l inputs 3 free of voltage Relay outputs Total current on loads MAX 16A Solenoid Valve relay SPST 5A 250Vac Defrost relay SPST 16A 250Vac Fan relay SPST 8A 250Vac Light relay SPST 16A 250Vac Alarm SPDT relay 8A 250Vac Aux SPST relay 8A 250Vac Outputs for valve bipolar or unipolar valves Optional output AnOUT DEPENDING ON THE MODELS PWM Open Collector outputs PWM or 12Vdc max 40mA Analog output 4 t...

Страница 8: ...efrost start 0 0 to 23h50min 143 nU 144 Holidays defrost start Sdn to 23h50min these parameters set the beginning of the eight programmable defrost cycles on holidays Ex when Sd2 3 4 the second defrost starts at 3 40 on holidays nU not used Format hours 10min resolution 10min Sd2 13 0 Holidays Second defrost start Sd1 to 23h50min 143 nU 144 Sd3 21 0 Holidays Third defrost start Sd2 to 23h50min 143...

Страница 9: ...d LSH SHY 0 1 C to 25 5 C 1 F to 45 F SHd 3 0 Delay of superheat alarm signaling 0 0 to 42min00sec 252 If a superheat alarm occurs the delay time SHd will have to expire before the controller shows an alarm Format min 10sec resolution 10sec FrC 0 Integration additive constant Fast recovery 0 to 100s Permits to increase integral time when SH value is below the set point If FrC 0 fast recovery funct...

Страница 10: ...e changes the display will be updated of 1 C 1 F when delay time expires Format min 10sec resolution 10sec rPA P1 Regulation probe A nP 0 P1 1 P2 2 P3 3 P4 4 P6 5 First probe used to regulate room temperature If rPA nP the regulation is performed with real value of rPb rPb nP Regulation probe B nP 0 P1 1 P2 2 P3 3 P4 4 P6 5 Second probe used to regulate room temperature If rPb nP the regulation is...

Страница 11: ...during the defrost Fnd 10 Fan delay after defrost 0 to 255min The time interval between the ending of the defrost and the starting of the evaporator fans FSt 10 0 Fan stop temperature 55 0 C to 50 0 C 67 F to 122 F Evaporator probe temperature above which the fan is always OFF FHY 1 0 Fan stop differential 0 1 C to 25 5 C 1 F to 45 F When stopped fan restarts when fan probe reaches FSt FHY value o...

Страница 12: ...0min 144 After powering on the instrument time interval between the detection of the temperature alarm condition and the alarm signaling Format hours 10min resolution 10min EdA 20 Alarm delay at the end of defrost 0 to 255min At the end of the defrost cycle time interval between the detection of the temperature alarm condition and the alarm signaling dot 20 Temperature alarm exclusion after door o...

Страница 13: ...en LiG light switched off AUS AUX switched off LEA both light and AUX switched off If nU then not used function LAN MANAGEMENT LMd Y Defrost Synchronization n Y n the section doesn t send a global defrost command Y the section sends a command to start defrost to other controllers dEM Y Defrost end Synchronization n Y n the end of the LAN defrosts are independent Y the end of the LAN defrosts are s...

Страница 14: ...ceived from master o5 0 P5 calibration 12 0 C to 12 0 C Allows to adjust possible offset of the probe 5 P6C PtM P6 configuration nP PtC ntC PtM nP not present PtC Ptc ntC ntc PtM Pt1000 o6 0 P6 calibration 12 0 C to 12 0 C Allows to adjust possible offset of the probe 6 SERVICE CLt ON OFF percentage C R O read only It shows the effective cooling time calculated by XM600 during regulation cooling t...

Отзывы: