Emerson Dixell XM668D Скачать руководство пользователя страница 5

 

1592023040 XM668D GB r1.1 2011.07.05.doc 

XM668D  

          

5/14 

 

  The 

Adr

  parameter  cannot  be  duplicated  because  in  this  case  the  defrost 

cannot be correctly managed. 
 

BEGIN 

 

Press for 3 sec, the 

rtC

 or other will be showed. 

The measurement unit blinks. 

Find Adr 

 

Press more than once the DOWN arrow to find the 

Adr 

parameter, the press 

SET

Modify 

Adr 

 or 

 

Set the value of 

Adr

 parameter, then press 

SET

 to 

confirm the parameter. 

EXIT 

 

Press  the  two  keys  together  to  exit  from  menu  or 
wait for about 10 sec. 

 

The 

LSn

 and 

LAn

 parameter are only to show the actual settings (read only). Se the 

following example of configuration

 

 

 

DAILY DEFROST FROM RTC: [CbP = Y] and [EdF = rtC]

 

 
idF

 

Parameter

: for safety reason force the  value  of 

idF

 at +1 respect to  the interval 

between  two 

Ld

  parameters.  The 

idF

  timer is reinitialized  after  defrost  and  at  every 

power-on. 

DEFROST  START:

  at  the  time  selected  by  the  parameters 

Ld1 

to 

Ld6

  or 

Sd1 

to 

Sd6

DEFROST END: 

if the probes reach the 

dtE

 temperature

 

or for maximum 

MdF

 time. 

SAFETY and rtC or rtF ALARM: 

with clock alarm

 

the device will use the parameter 

idF, dtE

 and 

MdF

 

WARNING: don’t set [EdF=rtC] and [CPb=n]. 
 
MULTIMASTER DEFROST

: all the probes with clock 

 

Table for example 

Par. 

Unit A (RTC)

 

Unit B (RTC)

 

Unit C (RTC) 

Adr 

N + 1 

N + 2 

EdF 

rtC (clock) 

rtC (clock) 

rtC (clock) 

CbP 

IdF 

9 hours safety 

9 hours safety 

9 hours safety 

MdF 

45 min safety 

45 min safety 

45 min safety 

dtE 

12°C safety 

12°C safety 

12°C safety 

Ld1 

06:00    1°  

06:00    1°  

06:00    1°  

Ld2 

14:00    2°  

14:00    2°  

14:00    2°  

Ld3 

22:00   3°  

22:00   3°  

22:00   3°  

10.

 

DISPLAY MESSAGES 

 

 

Display  Causes 

Notes 

 

 

KEYBOARD 

 

nod 

No display: the keyboard is trying 
to work with another board that is 
not working or not present 

Press for 3 sec UP arrow, enter 
the 

SEC

 menu and select 

LOC

 

entry. 

Pon 

Keyboard is unlocked 

 

PoF 

Keyboard is locked 

 

rSt 

Alarm reset 

Alarm output deactivated 

noP, nP 

nA 

Not present (configuration) 
Not available (evaluation) 

 

 

 

ALARM FROM PROBE INPUT 

 

P1 

P2 

P3 

P4 

P5 

P6 

PPF 

CPF 

Sensor brake down, value out of 
range or sensor incorrectly 
configured 

P1C

P2C 

to 

P6C

 

PPF

 can be showed by slaves of 

pressure that don’t receive the 
value of pressure. 
 

CPF

 is showed when the remote 

probe 4 is not working. 

P1

: the cooling output works 

with 

Con

 and 

COF

With defrost probe on error the 
defrost is performed only at 
interval. 
 
For

 P5

P6

 and 

PPF

: the 

percentage of the valve 
opening is fixed at 

PEO

 value. 

 

 

TEMPERATURE ALARM 

 

HA 

Temperature alarm from parameter 
ALU on probe 

rAL

 

LA 

Temperature alarm from parameter 
ALL on probe 

rAL

 

HAd 

Alarm from parameter 

dLU

 on 

probe defrost probe [

dPa

 / 

dPb

]. 

 

10 

LAd 

Alarm from parameter 

dLU

 on 

probe defrost probe [

dPa

 / 

dPb

]. 

 

11 

HAF 

Alarm from parameter 

FLU

 on 

probe defrost probe [

FPa

 / 

FPb

]. 

 

12 

LAF 

Alarm from parameter 

FLL

 on 

probe defrost probe [

FPa

 / 

FPb

]. 

 

 

 

DIGITAL INPUT ALARM 

 

13 

dA 

Door open alarm from input 

i1F

i2F

 or 

i3F

 = after delay 

d1d

d2d

 

or 

d3d

Cooling relay and fan follow the 

odc

 parameter. Cooling restart 

as specified on 

rrd

 parameter. 

14 

EA 

Generic alarm from digital input 

i1F

,

i2F

,

i3F=EAL

 

15 

CA 

Severe alarm of regulation lock 
from digital input 

i1F

,

i2F

,

i3F=bAL

Regulation output OFF. 

16 

PAL 

Pressure switch lock 

i1F

i2F

 o 

i3F

 

PAL

All the outputs are OFF. 

 

 

ELECTRONIC VALVE ALARM 

 

17 

LOP 

Minimum operating pressure 
threshold from 

LOP

 parameter. 

The valve output increases its 
opening of 

dML

 quantity every 

second. 

18 

MOP 

Maximum operating pressure 
threshold from MOP parameter. 

The valve output decreases its 
opening of 

dML

 quantity every 

second. 

19 

LSH 

Low superheating from 

LSH

 

parameter and 

SHd

 delay. 

The valve will be closed; the 
alarm will be showed after 

SHd

 

delay. 

20 

HSH 

High superheating from 

HSH

 

parameter and 

SHd

 delay. 

Only display. 

 

 

CLOCK ALARM 

 

21 

rtC 

Clock settings lost. 

Defrost will be performed with 

IdF

 till restoring the settings of 

RTC. 

22 

rtF 

Clock damaged. 

Defrost will be performed with 

IdF

 

 

OTHERS 

 

23 

EE 

EEPROM serious problem. 

Output OFF. 

24 

Err 

Error with upload/download 
parameters. 

Repeat the operation. 

25 

End 

Parameters have been correctly 
transferred.  

 

10.1

 

ALLARM RECOVERY 

Probe  alarms 

P1

P2

P3

  and 

P4

  start  some  seconds  after  the  fault  in  the  related 

probe;  they  automatically  stop  some  seconds  after  the  probe  restarts  normal 
operation. Check connections before replacing the probe. 
Temperature  alarms 

HA

LA

HA2

  and 

LA2

  automatically  stop  as  soon  as  the 

temperature returns to normal values. 
Alarms 

EA

 and 

CA 

(with 

i1F

 = 

bAL

)

 

recover as soon as the digital input is disabled. 

Alarm 

CA

 (with 

i1F

 = 

PAL

) recovers only by 

switching off and on

 the instrument. 

11.

 

USE OF THE PROGRAMMING “HOT KEY“ 

The  XM  units  can  UPLOAD  or  DOWNLOAD  the  parameter  list  from  its  own  E2 
internal  memory  to  the 

HOT-KEY 

and  vice-versa  through  a  TTL  connector.  Using 

HOT-KEY the Adr will not changed

11.1

 

DOWNLOAD (FROM THE HOT-KEY TO THE INSTRUMENT) 

1. 

Turn  OFF  the  instrument  by  means  of  the  ON/OFF  key,  insert  the 

HOT-KEY 

and then turn the unit ON. 

2. 

Automatically  the  parameter  list  of  the 

HOT-KEY 

is  downloaded  into  the 

controller  memory:  the 

doL

  message  is  blinking.  After  10  seconds  the 

instrument will restart working with the new parameters. At the end of the  data 
transfer  phase  the  instrument  displays  the  following  messages: 

End

  for  right 

programming.  The  instrument  starts  regularly  with  the  new  programming. 

Err

 

for failed programming.  In this case turn the unit off and then on if you want to 
restart the download again or remove the 

HOT-KEY 

to abort the operation. 

11.2

 

UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”) 

1. 

When  the  XM  unit  is  ON,  insert  the 

HOT-KEY 

and  push  è  key;  the 

uPL 

message appears. 

2. 

The UPLOAD begins; the 

uPL

 message is blinking. 

3. 

Remove  the 

HOT-KEY

.

 

At  the  end  of  the  data  transfer  phase  the  instrument 

displays the following messages: 

 

End

 = right programming; 

 

Err

 = failed programming. In this case push 

SET

 key if  you  want to restart the 

programming again or remove the not programmed 

HOT-KEY

12.

 

CONTROLLING LOADS 

12.1

 

THE COOLING OUTPUT 

The  regulation  is  performed  according  to  the  temperature  measured  by  the 
thermostat probe that can be  physical probe or  virtual probe obtained  by a  weighted 
average between two probes following the formula: 
 

value_for_room_regulation = (rPA*rPE + rPb*(100-rPE))/100 

 
If the temperature increases and reaches set point plus differential the solenoid valve 
is  opened  and  then  it  is  closed  when  the  temperature  reaches  the  set  point  value 
again.In  case  of  fault  in  the  thermostat  probe  the  opening  and  closing  time  of 
solenoid valve is configured by 

Con

 and 

CoF

 parameters. 

12.2

 

STANDARD REGULATION AND CONTINUOUS REGULATION 

The  regulation  can  be  performed  in  three  ways:  the  goal  of  the  first  way  (

standard 

regulation

)  is  reaching  the  best  superheat  via  a  classic  temperature  regulation 

obtained using hysteresis. The second way permits to use the valve to realize an high 
performance  temperature  regulation  with  a  good  factor  of  superheat  precision. 

This 

Содержание Dixell XM668D

Страница 1: ...on is with Dixell CX660 keyboard Figure 1a Figure 1b The CX660 keyboard shall be mounted on vertical panel in a 29x71 mm hole and fixed using the special bracket supplied as shown in fig 1a 1b The temperature range allowed for correct operation is 0 to 60 C Avoid places subject to strong vibrations corrosive gases excessive dirt or humidity The same recommendations apply to probes Let air circulat...

Страница 2: ...pressing UP ARROW button the user will be able to enter a fast selection menu and to read the value of the following parameters dPP measured pressure only on master device dP5 value of temperature obtained from pressure temperature conversion rPP pressure value read from remote location only for slave devices Examples of error messages dPP Err the local transducer read a wrong value the pressure i...

Страница 3: ...S TO PR2 To enter Pr2 programming menu 1 access the Pr1 menu by pressing both SET DOWN keys for 3 sec the first parameter label will be showed 2 press DOWN key untill the Pr2 label will be showed then press SET key 3 The blinking PAS label will be showed wait some seconds 4 Will be showed 0 with blinking 0 insert the password 321 using the keys UP and DOWN and confirming with SET key GENERAL STRUC...

Страница 4: ...0 CPP mA 10 CHd mA 10 Sr step s 0 Manual settings Par Par Par Par Par 1 Alco EX4 EX5 EX6 5 75 50 10 500 2 Alco EX7 10 160 75 25 500 3 Alco EX8 500 step s 10 260 80 50 500 4 Danfoss ETS 25 50 7 262 10 10 300 5 Danfoss ETS 100 10 353 10 10 300 6 Danfoss ETS 250 400 11 381 10 10 300 7 Sporlan SEI 5 to 11 0 159 16 5 200 8 Sporlan SER 1 5 to 20 0 159 12 5 200 9 Sporlan SEI 30 0 319 16 5 200 10 Sporlan ...

Страница 5: ...cond 18 MOP Maximum operating pressure threshold from MOP parameter The valve output decreases its opening of dML quantity every second 19 LSH Low superheating from LSH parameter and SHd delay The valve will be closed the alarm will be showed after SHd delay 20 HSH High superheating from HSH parameter and SHd delay Only display CLOCK ALARM 21 rtC Clock settings lost Defrost will be performed with ...

Страница 6: ...detected If ddP 0 this function is disabled Defrost ending When defrost is started via rtC the maximum duration of defrost is obtained from Md parameter and the defrost end temperature is obtained from dtE parameter and dtS if two defrost probes are selected If dPA and dPb are present and d2P Y the instrument stops the defrost procedure when dPA is higher than dtE temperature and dPb is higher tha...

Страница 7: ...l inputs 3 free of voltage Relay outputs Total current on loads MAX 16A Solenoid Valve relay SPST 5A 250Vac Defrost relay SPST 16A 250Vac Fan relay SPST 8A 250Vac Light relay SPST 16A 250Vac Alarm SPDT relay 8A 250Vac Aux SPST relay 8A 250Vac Outputs for valve bipolar or unipolar valves Optional output AnOUT DEPENDING ON THE MODELS PWM Open Collector outputs PWM or 12Vdc max 40mA Analog output 4 t...

Страница 8: ...efrost start 0 0 to 23h50min 143 nU 144 Holidays defrost start Sdn to 23h50min these parameters set the beginning of the eight programmable defrost cycles on holidays Ex when Sd2 3 4 the second defrost starts at 3 40 on holidays nU not used Format hours 10min resolution 10min Sd2 13 0 Holidays Second defrost start Sd1 to 23h50min 143 nU 144 Sd3 21 0 Holidays Third defrost start Sd2 to 23h50min 143...

Страница 9: ...d LSH SHY 0 1 C to 25 5 C 1 F to 45 F SHd 3 0 Delay of superheat alarm signaling 0 0 to 42min00sec 252 If a superheat alarm occurs the delay time SHd will have to expire before the controller shows an alarm Format min 10sec resolution 10sec FrC 0 Integration additive constant Fast recovery 0 to 100s Permits to increase integral time when SH value is below the set point If FrC 0 fast recovery funct...

Страница 10: ...e changes the display will be updated of 1 C 1 F when delay time expires Format min 10sec resolution 10sec rPA P1 Regulation probe A nP 0 P1 1 P2 2 P3 3 P4 4 P6 5 First probe used to regulate room temperature If rPA nP the regulation is performed with real value of rPb rPb nP Regulation probe B nP 0 P1 1 P2 2 P3 3 P4 4 P6 5 Second probe used to regulate room temperature If rPb nP the regulation is...

Страница 11: ...during the defrost Fnd 10 Fan delay after defrost 0 to 255min The time interval between the ending of the defrost and the starting of the evaporator fans FSt 10 0 Fan stop temperature 55 0 C to 50 0 C 67 F to 122 F Evaporator probe temperature above which the fan is always OFF FHY 1 0 Fan stop differential 0 1 C to 25 5 C 1 F to 45 F When stopped fan restarts when fan probe reaches FSt FHY value o...

Страница 12: ...0min 144 After powering on the instrument time interval between the detection of the temperature alarm condition and the alarm signaling Format hours 10min resolution 10min EdA 20 Alarm delay at the end of defrost 0 to 255min At the end of the defrost cycle time interval between the detection of the temperature alarm condition and the alarm signaling dot 20 Temperature alarm exclusion after door o...

Страница 13: ...en LiG light switched off AUS AUX switched off LEA both light and AUX switched off If nU then not used function LAN MANAGEMENT LMd Y Defrost Synchronization n Y n the section doesn t send a global defrost command Y the section sends a command to start defrost to other controllers dEM Y Defrost end Synchronization n Y n the end of the LAN defrosts are independent Y the end of the LAN defrosts are s...

Страница 14: ...ceived from master o5 0 P5 calibration 12 0 C to 12 0 C Allows to adjust possible offset of the probe 5 P6C PtM P6 configuration nP PtC ntC PtM nP not present PtC Ptc ntC ntc PtM Pt1000 o6 0 P6 calibration 12 0 C to 12 0 C Allows to adjust possible offset of the probe 6 SERVICE CLt ON OFF percentage C R O read only It shows the effective cooling time calculated by XM600 during regulation cooling t...

Отзывы: