Emerson Dixell XM668D Скачать руководство пользователя страница 10

 

1592023040 XM668D GB r1.1 2011.07.05.doc 

XM668D  

          

10/14 

 

 

CCt 

0.0 

Continuous cycle duration. 

0.0 to 24h00min (144) 

Compressor  ON  time  during  continuous  cycle: 

allows  to  set  the  length  of  the  continuous  cycle: 
compressor  stays  on  without  interruption  for  the 

CCt

 

time.  It  can  be  used,  for  instance,  when  the  room  is 
filled with new products.  

Format

: hours.10min, 

resolution

: 10min. 

 

CCS 

0.0 

Continuous cycle set point. 

[-55.0°C to 150.0°C] 

[-67°F to 302°F] 

Set point for continuous cycle:

 used value during the 

continuous cycle. 

 

Con 

15 

Compressor ON time with faulty probe. 

0 to 255min 

Solenoid  valve  ON  time  with  faulty  probe: 

time 

during  which  the  solenoid  valve  is  active  in  case  of 
faulty thermostat probe. With 

COn = 0

 solenoid valve is 

always OFF. 

 

CoF 

30 

Compressor OFF time with faulty probe. 

0 to 255min 

Solenoid  valve  OFF  time  with  faulty  probe: 

time 

during  which  the  solenoid  valve  is  off  in  case  of  faulty 
thermostat  probe.  With 

COF  =  0

  solenoid  valve  is 

always active. 

 

CF 

°C 

Temperature measurement unit. 

°C(0); °F(1) 

°C 

= Celsius;  

°F

 = Fahrenheit.  

!!! 

WARNING !!!  

When  the  measurement  unit  changes, 

all  parameters 

with temperature values 

will have to be checked

 

PrU 

rE 

Pressure Mode. 

rE(0); Ab(1) 

It defines the mode to evaluate the pressure values.  
!!! 

WARNING 

!!!  

PrU

  value  is  used  for  all  the  pressure  parameters.  If 

[PrU  =  rE]

  all  pressure  parameters  are  in  relative 

pressure unit, if 

[PrU = Ab]

 all pressure parameters are 

in absolute pressure unit. 

 

PMU 

bAr 

Pressure measurement unit. 

bAr(0); PSI(1); MPA(2) 

It selects the pressure measurement units. 

MPA

 means 

the value of pressure measured by kPA*10. 

 

rES 

dE 

Resolution (only °C). 

dE; in 

It sets decimal point display.

 

in

 = 1°C;  

dE

 = 0.1 °C. 

 

Lod 

tEr 

Local display: default display. 

nP(0); P1(1); P2(2);  
P3(3); P4(4); P5(5);  

P6(6); tEr(7); dEF(8) 

It selects which probe is displayed by the instrument.  

nP 

= no probe; 

P1,  P2,  P3,  P4

P5

P6

tEr  = 

virtual  probe  for 

thermostat; 

dEF = 

virtual probe for defrost. 

 

rEd 

tEr 

Remote display: default display. 

nP(0); P1(1); P2(2);  
P3(3); P4(4); P5(5);  

P6(6); tEr(7); dEF(8) 

It selects which probe is displayed by the X-REP.  

nP 

= no probe;

 

P1,  P2,  P3,  P4

P5

P6

tEr  = 

virtual  probe  for 

thermostat;  

dEF = 

virtual probe for defrost. 

 

dLY 

Display delay. 

0.0 to 24h00min (144) 

When  the  temperature  changes,  the  display  will  be 
updated of 1°C / 1°F when delay time expires.  

Format

: min.10sec, 

resolution

: 10sec. 

 

rPA 

P1 

Regulation probe A. 

nP(0); P1(1); P2(2);  

P3(3); P4(4); P6(5) 

First  probe  used  to  regulate  room  temperature.  If 

[rPA 

=  nP]

  the  regulation  is  performed  with  real  value  of 

rPb

 

rPb 

nP 

Regulation probe B. 

nP(0); P1(1); P2(2);  

P3(3); P4(4); P6(5) 

Second  probe  used  to  regulate  room  temperature.  If 

[rPb  =  nP]

  the  regulation  is  performed  with  real  value 

of 

rPA

 

rPE 

100 

Virtual probe percentage (room temperature). 

0 to 100% 

It  defines  the  percentage  of  the 

rPA

  respect  to 

rPb

The  value  used  to  regulate  room  temperature  is 
obtained by: 
 

value_for_room = (rPA*rPE + rPb*(100-rPE))/100

 

 

 

 

DEFROST 

 

 

 

dPA 

P2 

Defrost probe A. 

nP(0); P1(1); P2(2);  

P3(3); P4(4); P6(5) 

First probe used for defrost. If 

[rPA = nP]

 the regulation 

is performed with real value of 

dPb

 

dPb 

nP 

Defrost probe B. 

nP(0); P1(1); P2(2);  

P3(3); P4(4); P6(5) 

Second  probe  used  for  defrost.  If 

[rPB  =  nP]

  the 

regulation is performed with real value of 

dPA

 

dPE 

100 

Virtual probe percentage (defrost temperature). 

0 to 100% 

It  defines  the  percentage  of  the 

dPA

  respect  to 

dPb

The  value  used  to  regulate  room  temperature  is 
obtained by: 
 

value_for_defrost= (dPA*dPE + dPb*(100-dPE))/100

 

 

tdF 

EL 

Defrost kind. 

EL; in 

EL

 = defrost with electrical heater;  

in

 = hot gas defrost. 

 

EdF 

in 

Defrost mode. 

rtC; in 

rtC 

=

 

defrost  activation  via  RTC  with 

Ld1

Ld2

  ... 

parameters;  

in 

=

 

defrost activation with 

idF 

parameter. 

 

dtP 

0.1 

Difference between two probes to activate the 
defrost. 

[0.1°C to 25.5°C] 

[1°F to 45°F] 

If  the  difference  between  two  defrost  probes  stays 
lower  than 

dtP, 

for  all 

ddP 

time,  the  defrost  will  be 

activated. 

 

ddP 

60 

Delay before activation of differential defrost (

dtP

). 

0 to 60min 

See “Differential desfrost” in par. 12.3. 

 

d2P 

End defrost control with two probes. 

n; Y 

=  only  the 

dPA

  probe  is  used  to  defrost 

management;  

=  the  instrument  stops  the  defrost  when 

dPA

  is 

higher  than 

dtE

  temperature  and 

dPb

  is  higher  than 

dtS

 temperature. 

 

dtE 

8.0 

End defrost temperature on probe A (

dPA

). 

[-55.0°C to 50.0°C] 

 [-67°F to 122°F] 

Set the temperature measured by the evaporator probe 

dPA 

which stops the defrost. 

N.B.: parameter enabled 

only when the evaporator probe is present. 

 

dtS 

8.0 

End defrost temperature on probe B (

dPb

). 

[-55.0°C to 50.0°C]  

 [-67°F to 122°F] 

Set the temperature measured by the evaporator probe 

dPb 

which stops the defrost. 

N.B.: parameter enabled 

only when the evaporator probe is present.

 

Содержание Dixell XM668D

Страница 1: ...on is with Dixell CX660 keyboard Figure 1a Figure 1b The CX660 keyboard shall be mounted on vertical panel in a 29x71 mm hole and fixed using the special bracket supplied as shown in fig 1a 1b The temperature range allowed for correct operation is 0 to 60 C Avoid places subject to strong vibrations corrosive gases excessive dirt or humidity The same recommendations apply to probes Let air circulat...

Страница 2: ...pressing UP ARROW button the user will be able to enter a fast selection menu and to read the value of the following parameters dPP measured pressure only on master device dP5 value of temperature obtained from pressure temperature conversion rPP pressure value read from remote location only for slave devices Examples of error messages dPP Err the local transducer read a wrong value the pressure i...

Страница 3: ...S TO PR2 To enter Pr2 programming menu 1 access the Pr1 menu by pressing both SET DOWN keys for 3 sec the first parameter label will be showed 2 press DOWN key untill the Pr2 label will be showed then press SET key 3 The blinking PAS label will be showed wait some seconds 4 Will be showed 0 with blinking 0 insert the password 321 using the keys UP and DOWN and confirming with SET key GENERAL STRUC...

Страница 4: ...0 CPP mA 10 CHd mA 10 Sr step s 0 Manual settings Par Par Par Par Par 1 Alco EX4 EX5 EX6 5 75 50 10 500 2 Alco EX7 10 160 75 25 500 3 Alco EX8 500 step s 10 260 80 50 500 4 Danfoss ETS 25 50 7 262 10 10 300 5 Danfoss ETS 100 10 353 10 10 300 6 Danfoss ETS 250 400 11 381 10 10 300 7 Sporlan SEI 5 to 11 0 159 16 5 200 8 Sporlan SER 1 5 to 20 0 159 12 5 200 9 Sporlan SEI 30 0 319 16 5 200 10 Sporlan ...

Страница 5: ...cond 18 MOP Maximum operating pressure threshold from MOP parameter The valve output decreases its opening of dML quantity every second 19 LSH Low superheating from LSH parameter and SHd delay The valve will be closed the alarm will be showed after SHd delay 20 HSH High superheating from HSH parameter and SHd delay Only display CLOCK ALARM 21 rtC Clock settings lost Defrost will be performed with ...

Страница 6: ...detected If ddP 0 this function is disabled Defrost ending When defrost is started via rtC the maximum duration of defrost is obtained from Md parameter and the defrost end temperature is obtained from dtE parameter and dtS if two defrost probes are selected If dPA and dPb are present and d2P Y the instrument stops the defrost procedure when dPA is higher than dtE temperature and dPb is higher tha...

Страница 7: ...l inputs 3 free of voltage Relay outputs Total current on loads MAX 16A Solenoid Valve relay SPST 5A 250Vac Defrost relay SPST 16A 250Vac Fan relay SPST 8A 250Vac Light relay SPST 16A 250Vac Alarm SPDT relay 8A 250Vac Aux SPST relay 8A 250Vac Outputs for valve bipolar or unipolar valves Optional output AnOUT DEPENDING ON THE MODELS PWM Open Collector outputs PWM or 12Vdc max 40mA Analog output 4 t...

Страница 8: ...efrost start 0 0 to 23h50min 143 nU 144 Holidays defrost start Sdn to 23h50min these parameters set the beginning of the eight programmable defrost cycles on holidays Ex when Sd2 3 4 the second defrost starts at 3 40 on holidays nU not used Format hours 10min resolution 10min Sd2 13 0 Holidays Second defrost start Sd1 to 23h50min 143 nU 144 Sd3 21 0 Holidays Third defrost start Sd2 to 23h50min 143...

Страница 9: ...d LSH SHY 0 1 C to 25 5 C 1 F to 45 F SHd 3 0 Delay of superheat alarm signaling 0 0 to 42min00sec 252 If a superheat alarm occurs the delay time SHd will have to expire before the controller shows an alarm Format min 10sec resolution 10sec FrC 0 Integration additive constant Fast recovery 0 to 100s Permits to increase integral time when SH value is below the set point If FrC 0 fast recovery funct...

Страница 10: ...e changes the display will be updated of 1 C 1 F when delay time expires Format min 10sec resolution 10sec rPA P1 Regulation probe A nP 0 P1 1 P2 2 P3 3 P4 4 P6 5 First probe used to regulate room temperature If rPA nP the regulation is performed with real value of rPb rPb nP Regulation probe B nP 0 P1 1 P2 2 P3 3 P4 4 P6 5 Second probe used to regulate room temperature If rPb nP the regulation is...

Страница 11: ...during the defrost Fnd 10 Fan delay after defrost 0 to 255min The time interval between the ending of the defrost and the starting of the evaporator fans FSt 10 0 Fan stop temperature 55 0 C to 50 0 C 67 F to 122 F Evaporator probe temperature above which the fan is always OFF FHY 1 0 Fan stop differential 0 1 C to 25 5 C 1 F to 45 F When stopped fan restarts when fan probe reaches FSt FHY value o...

Страница 12: ...0min 144 After powering on the instrument time interval between the detection of the temperature alarm condition and the alarm signaling Format hours 10min resolution 10min EdA 20 Alarm delay at the end of defrost 0 to 255min At the end of the defrost cycle time interval between the detection of the temperature alarm condition and the alarm signaling dot 20 Temperature alarm exclusion after door o...

Страница 13: ...en LiG light switched off AUS AUX switched off LEA both light and AUX switched off If nU then not used function LAN MANAGEMENT LMd Y Defrost Synchronization n Y n the section doesn t send a global defrost command Y the section sends a command to start defrost to other controllers dEM Y Defrost end Synchronization n Y n the end of the LAN defrosts are independent Y the end of the LAN defrosts are s...

Страница 14: ...ceived from master o5 0 P5 calibration 12 0 C to 12 0 C Allows to adjust possible offset of the probe 5 P6C PtM P6 configuration nP PtC ntC PtM nP not present PtC Ptc ntC ntc PtM Pt1000 o6 0 P6 calibration 12 0 C to 12 0 C Allows to adjust possible offset of the probe 6 SERVICE CLt ON OFF percentage C R O read only It shows the effective cooling time calculated by XM600 during regulation cooling t...

Отзывы: