1592009140  XW563L GB r1.2 03.08.2015 

                           XW563L 

4/6 

TO SET DEFROST TIMES (3SEC.

 

 

afterward

 

 )

 

Ld1÷Ld8 Workday defrost start

 (0 ÷ 23h 50 min.) These parameters set the beginning of 

the eight programmable defrost cycles during workdays. Ex. When 

Ld2

 = 12.4 the 

second defrost starts at 12.40 during workdays.  

Sd1÷Sd8 Holiday defrost start

 (0 ÷ 23h 50 min.) These parameters set the beginning of 

the  eight  programmable  defrost  cycles  on  holidays.  Ex.  When 

Sd2

  =  3.4  the 

second defrost starts at 3.40 on holidays.  

N.B. :  

To disable a defrost cycle set it to “nu”(not used).  

Ex. 

 If

 Ld6

=nu

 ; 

 the sixth defrost cycle is disabled 

OTHER 
Adr   RS485 serial address 

(1÷247)

Identifies the instrument address when connected 

to a ModBUS compatible monitoring system. 

Rel   Release software:

 (read only) Software version of the microprocessor. 

Ptb   Parameter table:

 (read only) it shows the original code of the 

dIXEL

 parameter 

map. 

Prd    Probes display: 

(read only) display the temperature values of the evaporator probe    

Pb2 . 

Pr2      Access to the protected parameter list 

(read only). 

7.

 

DIGITAL INPUTS 

The Wing series can support up to 2 free contact digital inputs. One is always configured 
as door switch, the second is programmable in seven different configurations by the “

I2F

” 

parameter. 

7.1

 

DOOR SWITCH INPUT  

It  signals  the  door  status  and  the  corresponding  relay  output  status  through  the  “

odc

” 

parameter: 

no

 = normal (any change); 

Fan

 = Fan OFF; 

CPr

 = Compressor OFF; 

F_C

 = Compressor and fan OFF. 

Since  the  door  is  opened,  after  the  delay  time  set  through  parameter  “

dOA

”,  the  alarm 

output is enabled and the display shows the message “

dA

”. The alarm stops as soon as 

the external digital input is disabled again. During this time and then for the delay “

dot

” 

after closing the door, the high and low temperature alarms are disabled. 

7.2

 

CONFIGURABLE INPUT - GENERIC ALARM (EAL) 

As  soon  as  the  digital  input  is  activated  the  unit  will  wait  for  “

did

”  time  delay  before 

signalling  the  “

EAL

”  alarm  message.  The  outputs  status  don’t  change.  The  alarm  stops 

just after the digital input is de-activated. 
 

7.3

 

CONFIGURABLE INPUT - SERIOUS ALARM MODE (BAL) 

When the digital input is activated, the unit will wait for “

did

” delay before signalling the 

BAL

” alarm message. The relay outputs are switched OFF. The alarm will stop as soon 

as the digital input is de-activated. 
 

7.4

 

CONFIGURABLE INPUT - PRESSURE SWITCH (PAL) 

If  during  the  interval  time  set  by  “

did

”  parameter,  the  pressure  switch  has  reached  the 

number of activation of  the “

nPS

” parameter, the “

PAL

” pressure alarm message will be 

displayed. The compressor and the regulation are stopped. When the digital input is ON 
the compressor is always OFF. 

7.5

 

CONFIGURABLE INPUT - START DEFROST (DFR) 

It  executes  a  defrost  if  there  are  the  right  conditions.  After  the  defrost  is  finished,  the 
normal regulation will restart only if the digital input is disabled otherwise the instrument will 
wait until the “Mdf” safety time is expired. 

7.6

 

CONFIGURABLE INPUT - ENERGY SAVING (ES) 

The Energy Saving function allows to change the set point value as the result of the SET+ 
HES (parmeter) sum. This function is enabled until the digital input is activated. 

7.7

 

CONFIGURABLE INPUT -  REMOTE ON/OFF (ONF) 

This function allows to switch ON and OFF the instrument. 

7.8

 

DIGITAL INPUTS POLARITY  

The digital inputs polarity depends on “

I1P

” and “

I2P

” parameters. 

 

CL

 : the digital input is activated by closing the contact.

 

 

OP

 : the digital input is activated by opening the contact 

 

8.

 

INSTALLATION AND MOUNTING 

Instruments 

XW563L 

shall be mounted on vertical panel, in a 150x31 mm hole, and fixed 

using  two  screws 

  3  x  2mm.  To  obtain  an  IP65  protection  grade  use  the  front  panel 

rubber gasket (mod. RG-L). The temperature range allowed for correct operation is 0 - 60 
°C. Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity. 
The same recommendations apply to probes. Let the air circulate by the cooling holes. 
 
 
 

8.1

 

CUT OUT 

 

165

150

31

+0.5

-0

+0

.5

-0

+1

-1

Ø3 x2

 

8.2

 

MOUNTING WITH KEYBOARD COVER OPENING DOWNWARD 

 
 

CLICK!

1

2

2

3

3

1

1

 

8.3

 

MOUNTING WITH KEYBOARD COVER OPENING UPWARD 

 
 

CLICK!

1

2

2

2

3

3

1

1

 

9.

 

ELECTRICAL CONNECTIONS 

The  instruments  are  provided  with  screw  terminal  block  to  connect  cables  with  a  cross 
section up to 2,5 mm

for the digital and analogue inputs. Relays and power supply have a 

Faston  connection  (6,3mm).  Heat-resistant  cables  have  to  be  used.  Before  connecting 
cables make sure the power supply complies with the instrument’s requirements. Separate 
the  probe  cables  from  the  power  supply  cables,  from  the  outputs  and  the  power 
connections.  Do  not  exceed  the  maximum  current  allowed  on  each  relay,  in  case  of 
heavier loads use a suitable external relay. 

9.1

 

PROBE CONNECTIONS 

The  probes shall be mounted with the bulb upwards to prevent damages due to casual 
liquid infiltration. It is recommended to place the thermostat probe away from air streams to 
correctly  measure  the  average  room  temperature.  Place  the  defrost  termination  probe 
among the evaporator fins in the coldest place, where most ice is formed, far from heaters 
or from the warmest place during defrost, to prevent premature defrost termination. 

 

10.

 

RS485 SERIAL LINE 

The  RS485  connector  allows  to  connect  the  unit  to  a  network  line 

ModBUS-RTU

 

compatible as the Dixell monitoring system XJ500 (Version 3.0). 
 

Содержание Dixell WING XW563L

Страница 1: ...ing the o key pressed for about 3 seconds The compressor operates in continuous mode for the time set through the CCt parameter The cycle can be terminated before the end of the set time using the same activation key o for about 3 seconds 3 3 DEFROST Three defrost modes are available through the tdF parameter defrost with electrical heater hot gas or thermostatic defrost The defrost interval is co...

Страница 2: ...ch ON and OFF the light the auxiliary output and the instrument TO UNLOCK THE KEYBOARD Keep the o and n keys pressed together for more than 3s 4 11 ON OFF FUNCTION By pushing the ON OFF key the instrument shows OFF for 5 sec and the ON OFF LED is switched ON During the OFF status all the relays are switched OFF and the regulations are stopped if a monitoring system is connected it does not record ...

Страница 3: ...ignalling EdA Alarm delay at the end of defrost 0 255 min Time interval between the detection of the temperature alarm condition at the end of defrost and the alarm signalling dot Delay of temperature alarm after closing the door 0 255 min Time delay to signal the temperature alarm condition after closing the door doA Open door alarm delay 0 254min nu delay between the detection of the open door c...

Страница 4: ... the regulation are stopped When the digital input is ON the compressor is always OFF 7 5 CONFIGURABLE INPUT START DEFROST DFR It executes a defrost if there are the right conditions After the defrost is finished the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the Mdf safety time is expired 7 6 CONFIGURABLE INPUT ENERGY SAVING ES Th...

Страница 5: ...ure switch alarm Alarm output ON Other outputs OFF The alarm message is displayed until the alarm condition is recovery All the alarm messages are showed alternating with the room temperature except for the P1 which is flashing To reset the EE alarm and restart the normal functioning press any key the rSt message is displayed for about 3s 13 1 SILENCING BUZZER Once the alarm signal is detected the...

Страница 6: ...110 C 58 230 F 0 32 Pr2 APb Analogue output band width 50 0 110 C 58 230 F 0 Pr2 CAO Input type for the analogue output P1 1r2 P1 Pr2 LAo Minimum current for analog output 4 20 4 Pr2 ANALOGUE INPUTS Ot Thermostat probe calibration 12 0 12 0 C 21 21 F 0 Pr1 OE Evaporator probe calibration 12 0 12 0 C 21 21 F 0 Pr2 P2P Evaporator probe presence n y y Pr2 HES Temperature increase during the Energy Sa...

Отзывы: