1592009140  XW563L GB r1.2 03.08.2015 

                           XW563L 

5/6 

11.

 

TTL SERIAL LINE 

The TTL connector allows to upload and download the parameter list of the “

HOT KEY

“. 

 

12.

 

USE OF THE PROGRAMMING “HOT KEY “ 

The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal 
memory to the 

“Hot Key” 

and vice-versa. 

 

12.1

 

DOWNLOAD (FROM THE “HOT KEY” TO THE INSTRUMENT) 

1.

 

Turn OFF the instrument by means of the ON/OFF key insert the 

“Hot Key” 

and 

then turn the Wing ON. 

2.

 

Automatically  the  parameter  list  of  the 

“Hot  Key”

  is  downloaded  into  the  Wing 

memory, the “

DoL

” message is blinking. After 10 seconds the instrument will restart 

working with the new parameters. 

3.

 

Turn OFF the instrument remove the 

“Hot Key” 

then turn it ON again. 

At the end of the data transfer phase the instrument displays the following messages: 

end

 “ for right programming. The instrument starts regularly with the new programming. 

err

” for failed programming. In this case turn the unit off and then on if you want to restart 

the download again or remove the “

Hot key

” to abort the operation. 

 

 

12.2

 

UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”) 

1.

 

Turn OFF the instrument by means of the ON/OFF key then turn it ON again. 

2.

 

When  the  Wing  unit    is  ON,  insert  the  “

Hot  key

”  and  push 

o

  key;  the   

"uPL" 

message appears. 

3.

 

Push “

SET”

 key to start the UPLOAD; the “

uPL

” message is blinking. 

4.

 

Turn OFF the instrument remove the 

“Hot Key” 

 then turn it ON again. 

At the end of the data transfer phase the instrument displays the following messages: 

end

 “ for right programming. 

err

”  for  failed  programming.  In  this  case  push  “SET”  key  if  you  want  to  restart  the 

programming again or remove the not programmed “

Hot key

”. 

 

13.

 

ALARM SIGNALS 

Messag

Cause 

Outputs 

“P1”  Thermostat probe failure 

Alarm  output  ON;  Compressor  output 
according to parameters “COn” and “COF” 

“P2”  Evaporator probe failure 

Alarm output ON; Other outputs unchanged 

“HA”  Maximum temperature alarm 

Alarm output ON; Other outputs unchanged 

“LA”  Minimum temperature alarm 

Alarm output ON; Other outputs unchanged 

“EE”   Data or memory failure 

Alarm output ON; Other outputs unchanged 

“dA”  Defrost timeout alarm 

Alarm output ON; Other outputs unchanged 

“dAL”  Door switch alarm 

Alarm output ON; Other outputs unchanged 

“EAL”  External alarm 

Alarm output ON; Other outputs unchanged 

“BAL”  Serious external alarm 

Alarm output ON; Other outputs OFF 

“rtc”  Real time clock alarm 

Alarm output ON; Other outputs unchanged; 
Defrosts according to par. “

IdF

” 

“PAL”  Pressure switch alarm 

Alarm output ON; Other outputs OFF

 

The alarm message is displayed until the alarm condition is recovery. 
All the alarm messages are showed alternating with the room temperature except for the 
“P1” which is flashing. 
To  reset  the  “EE”  alarm  and  restart  the  normal  functioning  press  any  key,  the  “

rSt

” 

message is displayed for about 3s. 

13.1

 

SILENCING BUZZER 

Once the alarm signal is detected the buzzer can be silenced by pressing any key.  

13.2

 

 “EE” ALARM 

The Dixell instruments are provided with an internal check for the data integrity. Alarm “EE” 
flashes  when  a  failure  in  the  memory  data  occurs.  In  such  cases  the  alarm  output  is 
enabled. 

13.3

 

ALARM RECOVERY 

Probe alarms : “

P1

” (probe1 faulty) and “

P2

”; they automatically stop 10s after the probe 

restarts normal operation. Check connections before replacing the probe. 
Temperature  alarms  “

HA

”  and  “

LA

”  automatically  stop  as  soon  as  the  thermostat 

temperature returns to normal values or when the defrost starts. 
Door switch alarm “

dA

”  stop as soon as the door is closed. 

External alarms “

EAL

”, “

BAL

”  stop as soon as the external digital input is disabled “

PAL

” 

alarm is recovered by switching OFF the instrument. 
 
 
 
 
 
 

14.

 

TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case: 

facia 38x185 mm; depth 76mm 

Mounting :

 panel mounting in a 150x31 mm panel cut-out with two screws. 

 3 x 2mm. 

 

Distance between the holes 165mm 

Protection: 

IP20.

 

Frontal protection:

 IP65 with frontal gasket mod RG-L. (optional) 

Connections: 

Screw terminal block 

 2,5 mm

2

 heat-resistant wiring and 6,3mm Faston 

 

 

Optional

 disconnectable terminal blocks (

max.12A

Power supply: 

230Vac or. 110Vac 

 10% 

 

Power absorption: 

7VA max.

 

Display

: 3 digits, red LED, 14,2 mm high.  

Inputs

: 2 NTC probes 

Digital inputs

: 2 free voltage 

Relay outputs:

 

compressor:

 relay SPST 8(3) A, 250Vac  

light: 

relay SPST 16(3) A, 250Vac (or 

optional

 relay SPST 16(3) A, special for fluorescent 

lights) 

fans:

 relay SPST 8(3) A, 250Vac

 

defrost:

 relay SPDT 16(3) A, 250Vac  

Other output :

 alarm buzzer, “Hot Key “output  

Serial output :

 RS485 standard  

Communication protocol:

 Modbus - RTU

 

Data storing

: on the non-volatile memory (EEPROM). 

Kind of action: 

1B. 

Pollution grade: 

normal 

Software class: 

A.

 

Operating temperature: 

0÷60 °C. 

Storage temperature: 

-25÷60 °C.  

Relative humidity:

 20

85% (no condensing) 

Measuring and regulation range: NTC probe: 

-40÷110°C (-58÷230°F) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable). 

Accuracy (ambient temp. 25°C)

:  ±0,5 °C ±1 digit 

 

15.

 

CONNECTIONS 

15.1

 

XW563L 

The analog output is optional 

R

oo

m

17 18 19

21 22 23

Co

nf

. I

np

.

Do

or

D

ef

20

6

12

7

13

8 9 10 11

14 15 16

L

N

Comp

Fan

Light

16(6)A

250V

~

8(3)A

250V

~

16(6)A

250V

~

8(3)A

250V

~

Def

NC

24

RS 485

25 26

27 28

29 30 31 32

Analog

Out

 

 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

Содержание Dixell WING XW563L

Страница 1: ...ing the o key pressed for about 3 seconds The compressor operates in continuous mode for the time set through the CCt parameter The cycle can be terminated before the end of the set time using the same activation key o for about 3 seconds 3 3 DEFROST Three defrost modes are available through the tdF parameter defrost with electrical heater hot gas or thermostatic defrost The defrost interval is co...

Страница 2: ...ch ON and OFF the light the auxiliary output and the instrument TO UNLOCK THE KEYBOARD Keep the o and n keys pressed together for more than 3s 4 11 ON OFF FUNCTION By pushing the ON OFF key the instrument shows OFF for 5 sec and the ON OFF LED is switched ON During the OFF status all the relays are switched OFF and the regulations are stopped if a monitoring system is connected it does not record ...

Страница 3: ...ignalling EdA Alarm delay at the end of defrost 0 255 min Time interval between the detection of the temperature alarm condition at the end of defrost and the alarm signalling dot Delay of temperature alarm after closing the door 0 255 min Time delay to signal the temperature alarm condition after closing the door doA Open door alarm delay 0 254min nu delay between the detection of the open door c...

Страница 4: ... the regulation are stopped When the digital input is ON the compressor is always OFF 7 5 CONFIGURABLE INPUT START DEFROST DFR It executes a defrost if there are the right conditions After the defrost is finished the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the Mdf safety time is expired 7 6 CONFIGURABLE INPUT ENERGY SAVING ES Th...

Страница 5: ...ure switch alarm Alarm output ON Other outputs OFF The alarm message is displayed until the alarm condition is recovery All the alarm messages are showed alternating with the room temperature except for the P1 which is flashing To reset the EE alarm and restart the normal functioning press any key the rSt message is displayed for about 3s 13 1 SILENCING BUZZER Once the alarm signal is detected the...

Страница 6: ...110 C 58 230 F 0 32 Pr2 APb Analogue output band width 50 0 110 C 58 230 F 0 Pr2 CAO Input type for the analogue output P1 1r2 P1 Pr2 LAo Minimum current for analog output 4 20 4 Pr2 ANALOGUE INPUTS Ot Thermostat probe calibration 12 0 12 0 C 21 21 F 0 Pr1 OE Evaporator probe calibration 12 0 12 0 C 21 21 F 0 Pr2 P2P Evaporator probe presence n y y Pr2 HES Temperature increase during the Energy Sa...

Отзывы: