1592009140  XW563L GB r1.2 03.08.2015 

                           XW563L 

3/6 

1r2

 = difference between P1 and P2 (P1-P2) 

rEd  Remote display: 

select which probe is displayed by the remote display:

  

P1

 = Thermostat probe 

P2

 = Evaporator probe 

P3

 = not used 

1r2

 = difference between P1 and P2 (P1-P2) 

DEFROST 
tdF   Defrost type:  

rE

 = electrical heater (Compressor OFF) 

rT

 = thermostat defrost. During the defrost time “MdF”, the heater switches On and 

OFF depending on the evaporator temperature and “dtE” value. 

in

 = hot gas (Compressor and defrost relays ON) 

EdF  Defrost mode:

    

in

 = 

interval mode

. The defrost starts when the time “

Idf

” is expired. 

Sd

 = 

Smartfrost mode

. The time IdF (interval between defrosts) is increased only 

when  the  compressor  is  running  (even  non  consecutively)  and  only  if  the 
evaporator  temperature  is  less  than  the  value  in  "

SdF

”  (set  point  for 

SMARTFROST).  

SdF  Set  point  for  SMARTFROST

:  (-30

30  °C/  -22

86  °F)  evaporator  temperature 

which allows the IdF counting (interval between defrosts) in SMARTFROST mode. 

dtE   Defrost termination temperature:

 (-50,0÷110,0°C; -58÷230°F) (Enabled only when 

the evaporator probe is present) sets the temperature measured by the evaporator 
probe which causes the end of defrost. 

IdF 

Interval  between  defrosts: 

(1÷120h)  Determines  the  time  interval  between  the 

beginning of two defrost cycles. 

MdF   (Maximum) duration of defrost: 

(0÷255 min) When 

P2P = n

, no evaporator probe, 

it  sets  the  defrost duration, when 

P2P  = y

, defrost end based on temperature, it 

sets the maximum length for defrost. 

dFd     Display during defrost:  

rt

 = real temperature;  

it

 = temperature reading at the defrost start; 

Set

 = set point; 

dEF

 = “dEF” label; 

dEG

 = “dEG” label;

 

dAd     Defrost display time out:

 (0

255 min) Sets the maximum time between the end of 

defrost and the restarting of the real room temperature display. 

dSd  Start  defrost  delay

:(0÷59min)  This  is  useful  when  different defrost start  times  are 

necessary to avoid overloading the plant.  

Fdt      Drain down time:

 (0÷60 min.) time interval between reaching defrost termination 

temperature  and  the  restoring  of  the  control’s  normal operation. This time allows 
the evaporator to eliminate water drops that might have formed due to defrost.

 

dPO    First defrost after start-up:   
 

= Immediately;  

n

 = after the IdF time 

dAF     Defrost delay after fast freezing: 

(0min÷23h 50min)  after a Fast Freezing cycle, 

the first defrost will be delayed for this time. 

 

FANS 
FnC    Fan operating mode: 

C-n

 = running with the compressor, OFF during the defrost;  

C-y

 = running with the compressor, ON during the defrost; 

O-n

 = continuous mode, OFF during the defrost; 

O-y

 = continuous mode, ON during the defrost; 

Fnd    Fan delay after defrost:

 (0÷255 min)

 

The time interval between the defrost end 

and evaporator fans start.

 

FSt  Fan stop temperature:

 (-50÷110°C; -58÷230°F) setting of temperature, detected 

by evaporator probe, above which the fan is always OFF. 

 

ALARMS 
ALC  Temperature alarm configuration 

rE

 = High and Low alarms related to Set Point  

Ab

 = High and low alarms related to the absolute temperature. 

ALU  High temperature alarm setting:

  

 

ALC= rE, 0 

 

50°C or 90°F 

 

ALC= Ab, ALL 

 110°C or 230°F 

 

when  this  temperature  is  reached  and  after  the  ALd  delay  time  the  HA  alarm  is 
enabled. 

ALL  Low temperature alarm setting:

 

 

ALC = rE , 0 

 50 °C or 90°F 

 

ALC = Ab , - 50°C or -58°F 

 ALU 

 

when  this  temperature  is  reached  and  after  the  ALd  delay  time,  the  LA  alarm  is 
enabled,. 

AFH  Temperature  alarm  and  fan  differential: 

(0,1÷25,5°C;  1÷45°F)  Intervention 

differential  for  temperature  alarm  set  point  and  fan  regulation  set  point,  always 
positive.

 

ALd  Temperature alarm delay:

 (0÷255 min) time interval between the detection of an 

alarm condition and the corresponding alarm signalling. 

dAO    Delay of temperature alarm at start-up:

 (0min÷23h 50min) time interval between 

the detection of the temperature alarm condition after the instrument power on and 
the alarm signalling.

 

EdA  Alarm delay at the end of defrost: 

(0

255 min) Time interval between the detection 

of the temperature alarm condition at the end of defrost and the alarm signalling. 

dot   Delay of temperature alarm after closing the door : 

(0

255 min) Time delay to 

signal the temperature alarm condition after closing the door. 

doA    Open door alarm delay:

(0÷254min,nu) delay between the detection of the open 

door condition and its alarm signalling: the flashing message “

dA

” is displayed. If 

doA=nu

 the door alarm will be not signalled. 

nPS      Pressure  switch  number:

  (0 

15)  Number  of  activation  of  the  pressure  switch, 

during the “

did

” interval, before signalling the alarm event (I2F= PAL). 

ANALOGUE OUTPUT 4÷20 mA (OPTIONAL) 
AOS  Analogue output start point: 

(-50÷110°C or -58°÷230°F). Sets the temperature at 

which the analogue output begins. 

APb  

Analogue output band width

:

 

(-50÷110°C or -58°÷230°F) sets the width of the 

regulation band for the analogue output. If APb is 

positive

 then it is above the start 

point and the kind of action is direct (condenser application). If APb is 

negative

 then it 

is below the start point and the kind of action is inverse (evaporator application).  

CAO  

Input type for the analogue output: 

four input types can be selected: 

P1

 = room probe temperature; 

P2

 = evaporator probe temperature; 

P3

 = temperature 

of the third probe 

1r2

= temperature difference between the room probe and the evaporator probe 

LAo  Minimum current output: 

(4÷20mA) 

PROBE INPUTS 
Ot 

Thermostat probe calibration: 

(-12.0

12.0°C/ -21

21°F) allows to adjust possible 

offset of the thermostat probe. 

OE    Evaporator probe calibration: 

(-12.0

12.0°C/ -21

21°F) allows to adjust possible 

offsets of the evaporator probe. 

P2P  Evaporator probe presence:  

   n

=  not  present:  the  defrost  stops  only  by  time; 

y=

  present:  the  defrost  stops  by 

temperature and time. 

HES  Temperature increase during the Energy Saving cycle :

 (-30,0°C 

 30,0°C / -

22÷86°F) sets the increasing value of the set point during the Energy Saving cycle.  

DIGITAL INPUTS 
odc  Compressor and fan status when open door:

  

no

 = normal; 

Fan

 = Fan OFF; 

CPr

 = Compressor OFF; 

 

F_C

 = Compressor and fan OFF.  

I1P      Door switch input polarity:

 

 

CL

 : the digital input is activated by closing the contact;

 

 

OP

 : the digital input is activated by opening the contact. 

I2P     Configurable digital input polarity:

 

 

   

CL

 : the digital input is activated by closing the contact;

 

 

   

OP

 : the digital input is activated by opening the contact 

 

 

I2F 

Digital input operating mode:

 configure the digital input function: 

EAL 

= generic alarm;

 

bAL 

= serious alarm mode;

 

PAL 

= Pressure switch;

 

dFr 

= Start defrost; 

AUS 

= Not used; 

Es 

= Energy Saving;

 

 

onF 

= remote On/OFF. 

 

did   Time interval/delay for digital input alarm:

(0

255 min.) Time interval to calculate 

the  number  of  the  pressure  switch  activation  when  I2F=PAL.  If  I2F=EAL  or  bAL 
(external alarms), “did” parameter defines the time delay between the detection and 
the successive signalling of the alarm. 

TO SET CURRENT TIME AND WEEKLY HOLIDAYS (3SEC.

 

 

afterward

 

 )

 

Hur  Current hour 

(0 ÷ 23 h) 

Min  Current minute

 (0 ÷ 59min) 

dAY  Current day

 (Sun ÷ SAt) 

Hd1  First weekly holiday 

(Sun ÷ nu) Set the first day of the week which follows the 

holiday times. 

Hd2  Second weekly holiday 

(Sun ÷ nu) Set the second day of the week which follows 

the holiday times. 

Hd3  Third weekly holiday 

(Sun ÷ nu) Set the third day of the week which follows the 

holiday times. 

 
N.B.   Hd1,Hd2,Hd3 

can be set also as

 “nu” 

value (Not Used).

  

TO SET ENERGY SAVING TIMES (3SEC.

 

 

afterward

 

 )

 

ILE 

Energy  Saving  cycle  start  during  workdays

:  (0  ÷  23h  50  min.)  During  the 

Energy  Saving  cycle  the  set  point  is  increased  by  the  value  in  HES  so  that  the 
operation set point is SET + HES.  

dLe  Energy  Saving  cycle  length  during  workdays

:  (0  ÷  24h  00  min.)  Sets  the 

duration of the Energy Saving cycle on workdays.  

ISE  Energy Saving cycle start on holidays

. (0 ÷ 23h 50 min.) 

dSE  Energy Saving cycle length on holidays

 (0 ÷ 24h 00 min.) 

HES  Temperature increase during the Energy Saving cycle 

(-30÷30°C / -54÷54°F) 

sets the increasing value of the set point during the Energy Saving cycle.  

 

Содержание Dixell WING XW563L

Страница 1: ...ing the o key pressed for about 3 seconds The compressor operates in continuous mode for the time set through the CCt parameter The cycle can be terminated before the end of the set time using the same activation key o for about 3 seconds 3 3 DEFROST Three defrost modes are available through the tdF parameter defrost with electrical heater hot gas or thermostatic defrost The defrost interval is co...

Страница 2: ...ch ON and OFF the light the auxiliary output and the instrument TO UNLOCK THE KEYBOARD Keep the o and n keys pressed together for more than 3s 4 11 ON OFF FUNCTION By pushing the ON OFF key the instrument shows OFF for 5 sec and the ON OFF LED is switched ON During the OFF status all the relays are switched OFF and the regulations are stopped if a monitoring system is connected it does not record ...

Страница 3: ...ignalling EdA Alarm delay at the end of defrost 0 255 min Time interval between the detection of the temperature alarm condition at the end of defrost and the alarm signalling dot Delay of temperature alarm after closing the door 0 255 min Time delay to signal the temperature alarm condition after closing the door doA Open door alarm delay 0 254min nu delay between the detection of the open door c...

Страница 4: ... the regulation are stopped When the digital input is ON the compressor is always OFF 7 5 CONFIGURABLE INPUT START DEFROST DFR It executes a defrost if there are the right conditions After the defrost is finished the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the Mdf safety time is expired 7 6 CONFIGURABLE INPUT ENERGY SAVING ES Th...

Страница 5: ...ure switch alarm Alarm output ON Other outputs OFF The alarm message is displayed until the alarm condition is recovery All the alarm messages are showed alternating with the room temperature except for the P1 which is flashing To reset the EE alarm and restart the normal functioning press any key the rSt message is displayed for about 3s 13 1 SILENCING BUZZER Once the alarm signal is detected the...

Страница 6: ...110 C 58 230 F 0 32 Pr2 APb Analogue output band width 50 0 110 C 58 230 F 0 Pr2 CAO Input type for the analogue output P1 1r2 P1 Pr2 LAo Minimum current for analog output 4 20 4 Pr2 ANALOGUE INPUTS Ot Thermostat probe calibration 12 0 12 0 C 21 21 F 0 Pr1 OE Evaporator probe calibration 12 0 12 0 C 21 21 F 0 Pr2 P2P Evaporator probe presence n y y Pr2 HES Temperature increase during the Energy Sa...

Отзывы: