1592009140  XW563L GB r1.2 03.08.2015 

                           XW563L 

6/6 

16.

 

DEFAULT SETTING VALUES 

 

Label  Name 

  Range 

Default  Level

 

 

REGULATION 

 

°C/°F  XW563L 

Set 

Set point 

LS÷US 

-5.0 

--- 

Hy 

Differential 

0,1÷25,5 °C / 1÷45°F 

2.0 

Pr1 

LS 

Minimum set point 

 -50,0°C÷SET   

-58°F÷SET 

-30.0 

Pr2 

US 

Maximum set point 

SET ÷ 110°C  

SET ÷ 230°F 

20.0 

Pr2 

OdS  Outputs activation delay at start up 

0÷255 min. 

Pr2 

AC 

Anti-short cycle delay 

0÷30 min. 

Pr1 

CCt 

Compressor  ON  time  during  fast 
freezing 

0 ÷ 23h 50 min. 

0.0 

Pr2 

COn  Compressor  ON  time  with  faulty 

probe 

0÷255 min. 

15 

Pr2 

COF  Compressor  OFF  time  with  faulty 

probe 

0÷255 min. 

30 

Pr2 

 

DISPLAY 

 

 

 

CF 

Temperature measurement unit 

°C ÷ °F 

°C 

Pr2 

rES 

Resolution (integer/decimal point) 

in ÷ de 

de 

Pr1 

Lod 

Local display  

P1 ÷ 1r2 

P1 

Pr2 

rED 

Remote display 

P1 ÷ 1r2 

P1 

Pr2 

 

DEFROST 

 

 

 

tdF 

Defrost type 

rE,  rT,  in  

rE 

Pr1 

EdF  Defrost mode 

In, Sd 

in 

Pr2 

SdF  Set point for SMART DEFROST 

-30 ÷ +30°C  

-22÷+86°F 

Pr2 

dtE 

Defrost  termination  temperature 
(1°Evaporator) 

-50,0÷110°C 

-58÷230°F 

8.0 

Pr1 

IdF 

Interval between defrost cycles 

1÷120h 

Pr1 

MdF  (Maximum) length for 1° defrost 

0÷255 min. 

30 

Pr1 

dFd 

Displaying during defrost 

rt, it, SEt, dEF, dEG 

it 

Pr2 

dAd 

MAX display delay after defrost 

0÷255 min. 

30 

Pr2 

dSd 

Start defrost delay 

0÷59min 

Pr2 

Fdt 

Draining time 

0÷60 min. 

Pr2 

dPO  First defrost after start up 

n ÷ y 

Pr2 

dAF  Defrost delay after fast freezing 

0 ÷ 23h 50 min. 

2.0 

Pr2 

 

FANS 

 

 

 

FnC  Fans operating mode 

C-n, C-y, O-n, O-y  

O-n 

Pr2 

Fnd 

Fans delay after defrost 

0÷255 min. 

10 

Pr2 

FSt 

Fans stop temperature 

-50,0÷110°C 

 -58÷230°F 

2.0 

Pr2 

 

ALARMS 

 

 

 

ALC  Temperature alarms configuration 

rE÷Ab 

rE 

Pr2 

ALU  MAXIMUM temperature alarm 

-50,0÷110°C 

-58÷230°F 

10.0 

Pr1 

ALL 

minimum temperature alarm 

-50,0÷110°C 

 -58÷230°F 

10.0 

Pr1 

AFH  Temperature 

alarm 

and 

fan 

differential 

0,1÷25,5 °C  

1÷45°F 

2.0 

Pr2 

ALd 

Temperature alarm delay 

0÷255 min. 

15 

Pr2 

dAO  Delay of temperature alarm at start up 

0 ÷ 23h 50 min. 

1.3 

Pr2 

EdA  Alarm delay at the end of defrost  

0÷255 min. 

30 

Pr2 

dot 

Delay  of  temperature  alarm  after 
closing the door  

0÷255 min. 

15 

Pr2 

dOA  Open door alarm delay  

0÷254 min.,nu 

15 

Pr2 

nPS  Pressure switch activation number 

0÷15 

Pr2 

 

ANALOGUE  OUTPUT  4÷20mA 
(Optional) 

 

 

 

AOS  Analogue output start point 

-50,0÷110°C /  

-58÷230°F 

0/32 

Pr2 

APb  Analogue output band width 

-50,0÷110°C/ 

 -58÷230°F 

Pr2 

CAO  Input type for the analogue output 

P1÷1r2 

P1 

Pr2 

LAo 

Minimum current for analog output  

4÷20 

Pr2 

 

ANALOGUE INPUTS 

 

 

 

Ot 

Thermostat probe calibration 

-12,0÷12,0°C 

-21÷21°F 

Pr1 

OE 

Evaporator probe calibration 

-12,0÷12,0°C 

-21÷21°F 

Pr2 

P2P  Evaporator probe presence 

n ÷ y 

Pr2 

HES  Temperature  increase  during  the 

Energy Saving cycle  

-30÷30°C 

-22÷86°F 

Pr2 

 

DIGITAL INPUTS 

 

 

 

Odc  Open door control  

no, Fan, CPr, F_C 

FAn 

Pr2 

I1P 

Door switch polarity 

CL÷OP 

cL 

Pr2 

I2P 

Configurable digital input polarity 

CL÷OP 

cL 

Pr2 

i2F 

Digital input configuration 

EAL, bAL, PAL, dFr,  

AUS, ES, OnF 

EAL 

Pr2 

dId 

Digital input alarm delay 
 

0÷255 min. 

Pr2 

 

TIME AND WEEKLY HOLIDAYS

 

 

 

 

Hur 

Current hour 

0 ÷ 23 

Pr2 

Min 

Current minute 

0 ÷ 59 

Pr2 

dAY  Current day 

Sun ÷ SAt 

Sun 

Pr2 

Hd1  First weekly holiday 

Sun÷ SAt – nu 

nu 

Pr2 

Hd2  Second weekly holiday 

Sun÷ SAt – nu 

nu 

Pr2 

Hd3  Third weekly holiday 

Sun÷ SAt – nu 

nu 

Pr2 

 

ENERGY SAVING TIMES 

 

 

 

ILE 

Energy  Saving  cycle  start  during 
workdays 

0 ÷ 23h 50 min. 

Pr2 

dLE 

Energy  Saving  cycle  length  during 
workdays 

0 ÷ 24h 00 min. 

Pr2 

ISE 

Energy Saving cycle start on holidays 

0 ÷ 23h 50 min. 

Pr2 

dSE  Energy  Saving  cycle  length  on 

holidays 

0 ÷ 24h 00 min. 

Pr2 

HES  Temperature  increase  during  the 

Energy Saving cycle 

-30÷30°C / -54÷54°F 

Pr2 

 

DEFROST TIMES 

 

 

 

Ld1 

1

st

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

6.0 

Pr2 

Ld2 

2

nd

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

13.0 

Pr2 

Ld3 

3

rd

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

21.0 

Pr2 

Ld4 

4

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Ld5 

5

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Ld6 

6

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Ld7 

7

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Ld8 

8

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Sd1 

1

st

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

6.0 

Pr2 

Sd2 

2

nd

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

13.0 

Pr2 

Sd3 

3

rd

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

21.0 

Pr2 

Sd4 

4

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Sd5 

5

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Sd6 

6

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Sd7 

7

th

 holiday defrost start 

0 ÷ 23h 50  min. - nu 

nu 

Pr2 

Sd8 

8

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

 

OTHER 

 

 

 

Adr 

Serial address 

0÷247 

Pr1 

rEL 

Software release 

- - - 

1.0 

Pr2 

Ptb 

Map code 

- - - 

- - - 

Pr2 

Prd 

Probes display 

Pb1÷Pb2 

- - - 

Pr2 

Pr2   Access parameter list 

- - - 

 

Pr2 

 
 
 
 
 

 
 

 

Содержание Dixell WING XW563L

Страница 1: ...ing the o key pressed for about 3 seconds The compressor operates in continuous mode for the time set through the CCt parameter The cycle can be terminated before the end of the set time using the same activation key o for about 3 seconds 3 3 DEFROST Three defrost modes are available through the tdF parameter defrost with electrical heater hot gas or thermostatic defrost The defrost interval is co...

Страница 2: ...ch ON and OFF the light the auxiliary output and the instrument TO UNLOCK THE KEYBOARD Keep the o and n keys pressed together for more than 3s 4 11 ON OFF FUNCTION By pushing the ON OFF key the instrument shows OFF for 5 sec and the ON OFF LED is switched ON During the OFF status all the relays are switched OFF and the regulations are stopped if a monitoring system is connected it does not record ...

Страница 3: ...ignalling EdA Alarm delay at the end of defrost 0 255 min Time interval between the detection of the temperature alarm condition at the end of defrost and the alarm signalling dot Delay of temperature alarm after closing the door 0 255 min Time delay to signal the temperature alarm condition after closing the door doA Open door alarm delay 0 254min nu delay between the detection of the open door c...

Страница 4: ... the regulation are stopped When the digital input is ON the compressor is always OFF 7 5 CONFIGURABLE INPUT START DEFROST DFR It executes a defrost if there are the right conditions After the defrost is finished the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the Mdf safety time is expired 7 6 CONFIGURABLE INPUT ENERGY SAVING ES Th...

Страница 5: ...ure switch alarm Alarm output ON Other outputs OFF The alarm message is displayed until the alarm condition is recovery All the alarm messages are showed alternating with the room temperature except for the P1 which is flashing To reset the EE alarm and restart the normal functioning press any key the rSt message is displayed for about 3s 13 1 SILENCING BUZZER Once the alarm signal is detected the...

Страница 6: ...110 C 58 230 F 0 32 Pr2 APb Analogue output band width 50 0 110 C 58 230 F 0 Pr2 CAO Input type for the analogue output P1 1r2 P1 Pr2 LAo Minimum current for analog output 4 20 4 Pr2 ANALOGUE INPUTS Ot Thermostat probe calibration 12 0 12 0 C 21 21 F 0 Pr1 OE Evaporator probe calibration 12 0 12 0 C 21 21 F 0 Pr2 P2P Evaporator probe presence n y y Pr2 HES Temperature increase during the Energy Sa...

Отзывы: