1592031000 Univ-R4 GB - r1.1 - 2012.07.23 Universal-R
8/20
Description
Label
Adjustment Range
Factory defaults with parameter “tC” 1- 7
Defrost termination temperature
-55 to 50
C;
-67 to 122°F
8.0°C
46°F
8.0°C
46°F
8.0°C
46°F
8.0°C
46°F
8.0°C
46°F
Maximum duration of defrost
(second evaporator)
0 to 255 min
30
Defrost termination temperature
(second evaporator)
-55 to 50
C;
-67 to 122°F
8.0°C
46°F
Display during defrost
0 = Real temp.
1 = Temp. at defrost start
2 = Set Point
3 = “DEF” label
4 = “DEG” label
3
3
3
3
3
Defrost display time out
0 to 255 min
10
10
10
10
10
Defrost type (forced)
0 = Electrical
1 = Hot Gas
0
0
0
0
Drain down time
0 to 255 min
0
0
2
2
First defrost after power on
1 = Immediate
0 = After normal interval
0
0
0
0
0
Evaporator fan operating mode
0 to 3
(1 = Fan always on apart from during
defrost. See section 10 for info. on other
settings )
1
1
Evaporator fan stop temperature
-55 to 50
C;
-67 to 122°F
25°C;
77°F
25°C;
77°F
Evaporator fan delay after defrost
0 to 255 min
7
7
Fan ON time
0 to 15 min
0
0
Fan Off time
0 to 15 min
0
0
Thermostat probe calibration
-12.0 to 12.0
C;
-21 to 21
F
0.0°C;
0°F
0.0°C;
0°F
0.0°C;
0°F
0.0°C;
0°F
0.0°C;
0°F
0.0°C;
0°F
0.0°C;
0°F
Evaporator probe presence
0 = evaporator probe not present
1 = evaporator probe present
1
1
1
Evaporator probe calibration
-12.0 to 12.0
C;
-21 to 21
F
0.0°C;
0°F
0.0°C;
0°F
0.0°C;
0°F
Third probe presence
0 = third probe not present,
1 = third probe present.
1
1
1
1
1
1
Third probe calibration
-12.0 to 12.0
C;
-21 to 21
F
0.0°C;
0°F
0.0°C;
0°F
0.0°C;
0°F
0.0°C;
0°F
0.0°C;
0°F
0.0°C;
0°F
Display Resolution
0 = With decimal point
1 = No decimal point
0
0
0
0
0
0
0
Temperature measurement unit
(°C/°F)
0 =
Celsius
1 =
Fahrenheit
0
0
0
0
0
0
0
Instrument display
0 = Thermostat probe
1 = Evaporator probe
2 = Third probe
3 = SET-POINT
0
0
0
0
0
0
0
Display delay
0 to 20min0sec, res. 10sec
0
0
0
0
0
0
0
Type of action
0 = cooling
1 = heating
0
0
Compressor ON time with faulty
probe
0 to 255 min
15
15
15
15
15
15
0
Compressor OFF time with faulty
probe
0 to 255 min
30
30
30
30
30
30
30
Alarm muting configuration for
buzzer & relay
0 = Mute buzzer only
1 = Mute buzzer & relay
1
1
1
1
1
1
1
Digital input configuration
0 = Start defrost
1 = Door switch
2 = Auxiliary relay
3 = Energy saving
4 = Remote On/OFF
5 = Generic alarm
6 = Serious alarm
5
5
5
5
5
5
5