Parameter  FSt  sets  the  fan  stop  temperature.  This  is  the  maximum  temperature,  detected  by  the  evaporator  probe,  above  which  the 
evaporator fans will stop. 
Leave FSt above ambient temperature during commissioning to avoid fan short cycle.  
After finishing the defrost phase, there is a stand still drain time, set by parameter Fdt. When this period has expired, the refrigeration cycle 
commence but the evaporator fans remain off until Fnd (fan delay) times out.  

14.

 

SPECIAL APPLICATIONS – DEAD BAND CONTROL 

14.1

 

DEAD BAND CONTROL (COOLING & HEATING) 

With [oAC = 1], the compressor relay controls cooling as normal but the 4th (auxiliary) relay is used to control a heater. The value entered in 
parameter HY will now be set equal on both sides of the SET POINT. Example: if [HY = 1

°

C] that will create a 2

°

C Dead Band. 

At  [SET  POINT  +  HY],  cooling  switches  on.  At  [SET  POINT  –  HY],  heating  switches  on.  Either  cooling  or  heating  switch  off  when 
temperature returns to SET POINT

15.

 

ALARMS 

Message  Message – Mode 

Cause 

Outputs 

EE 

Flashing 

Data or memory failure 

Alarm output ON; Other outputs unchanged. 

P1 

Flashing 

Thermostat probe failure 

Alarm output ON; Compressor output according to parameters Con 
and CoF

P2 

Alternating with room temperature 

Evaporator probe failure 

Alarm output ON; Other outputs unchanged; End defrost is timed. 

P3 

Alternating with room temperature 

Second evaporator probe failure 

Alarm output ON; Other outputs unchanged; End defrost is timed. 

HA 

Alternating with room temperature 

High temperature alarm 

Alarm output ON; Other outputs unchanged. 

LA 

Alternating with room temperature 

Minimum temperature alarm 

Alarm output ON; Other outputs unchanged. 

HA2 

Alternating with room temperature 

Condenser max temp alarm 

Alarm output ON; Other outputs unchanged. 

LA2 

Alternating with room temperature 

Condenser max temp alarm 

Alarm output ON; Other outputs unchanged. 

dA 

Alternating with room temperature 

Door open alarm 

Alarm output ON: Outputs re-start if parameter rrd = 1

EA 

Alternating with room temperature 

Generic external alarm 

Alarm output ON; Other outputs unchanged. 

bAL 

Alternating with room temperature 

Serious external alarm 

Alarm output ON; Other outputs OFF. 

 

15.1

 

MUTING ALARM BUZZER & RELAY 

The alarm buzzer can be muted, by pressing any button. The controller will briefly show the reset “rES” label. Parameter tbA defines how 
the alarm relay will respond to the muting of the buzzer. 

-

 

tbA = 0: the alarm relay will remain active until the alarm condition is rectified; 

-

 

tbA = 1: the alarm relay de-activates when the buzzer is muted. 

 In either case, the display will flash an alarm label until the condition is rectified. 
 

15.2

 

ALARM “EE” 

The  Dixell  Universal-R  is  provided  with  an  internal  watchdog  verifying  data  and  memory  integrity.  Alarm  “EE”  will  flash  after  detecting a 
failure in data or in the internal memory. In this case, the alarm output is enabled. 
 
WHAT TO DO 

1.

 

Cancel the alarm by pressing a key.  

2.

 

Check the value of all parameters and restore correct values when wrong. 

3.

 

Check the correct instrument operation and in case of further errors replace it. 

15.3

 

ALARM RECOVERY 

Probe  alarms  “P1”,  “P2”  and  “P3”  start  30 seconds after a fault in probe is detected; they automatically stop 30 seconds after the probe 
restarts normal operation. Check connections before replacing the probe. 
Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature returns to normal values and when defrost 
starts. Temperature alarms “HA2” and “LA2” automatically stop as soon as the condenser temperature returns to normal values. 

16.

 

REMOVING SECURITY LEVEL PROTECTION  

It  is  possible  to  allow  access  to  any  parameter  from  Pr1  level.  To  do  this,  go  into  Pr2 as previously described. Scroll to the label of the 
parameter you require and then press the SET and DOWN buttons in quick succession. The decimal point LED will be on indicating that 
access to this particular parameter is now possible from Pr1 level. Its label will now appear when in Pr1 programming level and its value can 
be altered. To restore security level protection, use the same procedure (the decimal point LED will go out after pressing both buttons). 

Содержание Dixell Universal-R

Страница 1: ...UNIVERSAL R ...

Страница 2: ...dedicated button during a fixed time interval at start up NEW FRONT FASCIA DESIGN Display with illuminated icons to indicate loads alarms status indications Six buttons give direct access to main functions and menu DOUBLE EVAPORATOR DEFROST FUNCTION A new feature allows defrost control of twin evaporators The 4th AUX relay and probe 3 Pb3 control defrost of the second evaporator Only when both hav...

Страница 3: ...FEATURES OF THE UNIVERSAL R ___________________________________________________16 11 THERMOSTAT OVERRIDE not available when parameter tC 1 or 7 ______________________________16 12 DEFROST TYPES _________________________________________________________________________16 13 EVAPORATOR FAN CONTROL only when parameter tC 5 or 6 __________________________________16 14 SPECIAL APPLICATIONS DEAD BAND CON...

Страница 4: ...he wires for probes electrical loads and the power supply are separated and far enough away to each other without crossing or intertwining In case of applications in industrial environments the use of mains filters our mod DIXL930 in parallel with inductive loads could be useful Heating applications Do not exceed 105 C with the NTC probes supplied For higher temperatures up to a maximum of 150 C u...

Страница 5: ...r auto recognition to work 3 If 1 minute expires before you have completed quick set up either turn OFF ON power to start set up again or enter parameter as per the instructions and adjust your parameter settings manually see Section 9 Table 1 parameter tC settings Parameter tC Type of Control Required probes 1 On Off thermostat Cooling x 1 2 Off cycle defrost timed x 1 3 Electrical Hot Gas defros...

Страница 6: ...ycle Defrost Controller Parameter tC 3 Forced defrost controller time initiated time terminated Parameter tC 4 Forced defrost controller time initiated temperature terminated Parameter tC 5 Forced defrost controller time initiated temperature terminated with evaporator fan delay after defrost Parameter tC 6 Double evaporator applications Parameter tC 7 Heating applications ...

Страница 7: ...C 2 F 2 0 C 2 F 2 0 C 2 F 2 0 C 2 F 2 0 C 2 F Minimum Set Point limit 55 C to Set Point 67 F to Set Point 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F Maximum Set Point limit Set Point to 150 C Set Point to 302 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F Anti short cycle delay 0 to 50 min 1 1 1 1 1 1 0 Second c...

Страница 8: ... Thermostat probe calibration 12 0 to 12 0 C 21 to 21 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F Evaporator probe presence 0 evaporator probe not present 1 evaporator probe present 1 1 1 Evaporator probe calibration 12 0 to 12 0 C 21 to 21 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F Third probe presence 0 third probe not present 1 third probe present 1 1 1 1 1 1 Third probe calibr...

Страница 9: ...tart regulation with door open alarm 0 No 1 Yes 0 0 0 0 0 0 0 Low temperature alarm of condenser 55 to 150 C 67 to 302 F 40 C 40 F 40 C 40 F 40 C 40 F 40 C 40 F 40 C 40 F High temperature alarm of condenser 55 to 150 C 67 to 302 F 110 C 230 F 110 C 230 F 110 C 230 F 110 C 230 F 110 C 230 F Differential for temperature condenser alarm recovery 0 1 to 25 5 C 1 to 45 F 5 C 5 F 5 C 5 F 5 C 5 F 5 C 5 F...

Страница 10: ...temperature decreases and reaches set point minus differential the regulation output is activated and then turned off when the temperature reaches the set point value again Minimum set point limit 55 C to SET or 67 F to SET sets the lower limit of set point adjustment Maximum set point limit SET to 150 C or SET to 302 F sets the upper limit of set point adjustment Anti short cycle delay 0 to 50min...

Страница 11: ...or second defrost 0 to 255min when P3P 0 not evaporator probe timed defrost it sets the defrost duration when P3P 1 defrost end based on temperature it sets the maximum length for defrost Note The P3 probe will be automatically set as second evaporator probe by the tC parameter Second termination temperature 55 to 50 C or 67 to 122 F sets the temperature measured by the second evaporator probe P3 ...

Страница 12: ...ith label D I 2 Pb3 Input operates as digital input 1 present the third input the one signed with label D I 2 Pb3 Input operates as third probe Third probe calibration 12 0 to 12 0 C or 21 to 21 F adjustment for third probe named Evap 2 on the label offset Display resolution 0 with decimal point 1 without decimal point Temperature measurement unit 0 Celsius 1 Fahrenheit Warning If you alter the se...

Страница 13: ...ed by closing the circuit 1 the digital input is activated by opening the circuit Time interval delay for digital input 1 alarm 0 to 255min it defines the time delay between the detection and the subsequent signalling of the alarm Time interval delay for digital input 2 alarm 0 to 255min it defines the time delay between the detection and the subsequent signalling of the alarm Compressor and fan s...

Страница 14: ...ture alarm of the condenser is active 0 the compressor keeps on working if a low temperature alarm at the condenser is active 1 the compressor is switched off while the low temperature alarm is active The regulation will restart after elapsing AC delay time Temperature set point change during the Energy Saving cycle 30 0 to 30 0 C or 54 to 54 F sets the deviation from the normal set point during t...

Страница 15: ...yboard The display will flash PoF or Pon for a few seconds to confirm locking or unlocking respectively Enter programming mode keep both buttons pressed for 3 sec release them and then press them again for 8 sec The first label of Pr2 level will be displayed Exit programming mode press together to return to normal display 9 PROGRAMMING MODE 9 1 USER PROGRAMMING LEVEL PR1 To enter programming level...

Страница 16: ...it degrees FLASHING Programming mode 11 THERMOSTAT OVERRIDE not available when parameter tC 1 or 7 For rapid chilling or freezing the thermostat can be overridden by pressing the UP button until the icon lights up The compressor will run in continuous mode irrespective of temperature for the time period set in parameter CCt Normal operation will then resume automatically The cycle can also be term...

Страница 17: ... re start if parameter rrd 1 EA Alternating with room temperature Generic external alarm Alarm output ON Other outputs unchanged bAL Alternating with room temperature Serious external alarm Alarm output ON Other outputs OFF 15 1 MUTING ALARM BUZZER RELAY The alarm buzzer can be muted by pressing any button The controller will briefly show the reset rES label Parameter tbA defines how the alarm rel...

Страница 18: ...ectly measure the average room temperature Place the defrost termination probe among the evaporator fins in the coldest place where most ice is formed far from heaters or from the warmest place during defrost to prevent premature defrost termination 20 TECHNICAL DATA Housing Self extinguishing ABS Size Frontal 32x74 mm depth 70 mm Mounting Panel mounting in a 71x29 mm panel cut out Frontal protect...

Страница 19: ...d resistance value Change probe type or alter parameter PbC Fit evaporator probe or alter parameter tC Display flashing EE Data corruption Check for electrical spikes and interference Fit filters DIXL930 DIXL932 Ensure probe cables are separated from power cables Re check all parameter settings Replace controller if still not working Display flashing dA Door has been left open too long Shut the do...