1592031000 Univ-R4 GB - r1.1 - 2012.07.23 Universal-R
12/20
Fan delay after defrost: (0 to 255min) the time interval between end of defrost and evaporator fans starting. Runs
concurrently with Fdt (Drain down time). Always keep Fnd longer that Fdt.
Fan ON time: (0 to 15min) used to set an On/Off cycle of the evaporator fans while the compressor is off. With FnC = 0 or
FnC = 2, it sets the evaporator fan ON cycling time when the compressor is OFF. With Fon = 0 and FoF
≠ 0
, the fans are
always off. With Fon = 0 and FoF = 0 the fans are always off.
Fan OFF time: (0 to 15min) used to set an On/Off cycle of the evaporator fans while the compressor is off. With FnC = 0 or
FnC = 2, it sets the evaporator fan OFF cycling time when the compressor is OFF. With Fon = 0 and FoF
≠ 0
, the fans are
always off. With Fon = 0 and FoF = 0 the fans are always off.
Thermostat probe calibration: (-12.0 to 12.0°C or -21 to 21°F) adjustment for thermostat probe (named Room) offset.
Evaporator probe presence (probe named Evap on the label):
0 = not present;
1 = present.
Evaporator probe calibration: (-12.0 to 12.0°C or -21 to 21°F) adjustment for evaporator probe (named Evap) offset.
Third probe presence (probe named Evap.2 on the label):
0 = not present, the third input (the one signed with label “D.I.2 / Pb3”) Input operates as digital input;
1 = present, the third input (the one signed with label “D.I.2 / Pb3”) Input operates as third probe.
Third probe calibration: (-12.0 to 12.0°C or -21 to 21°F) adjustment for third probe (named Evap.2 on the label) offset.
Display resolution:
0 = with decimal point;
1 = without decimal point.
Temperature measurement unit:
0 = Celsius;
1 = Fahrenheit.
Warning: If you alter the setting of parameter rES ( decimal point on/off ) re-check the settings of all temperature related
parameters Set Point, HY, LS, US, ALU, ALL, dtE, FSt, ot & oE, as they can be effected.
Probe for Display:
0 = Thermostat probe;
1 = Evaporator probe;
2 = Third probe;
3 = DISPLAY ONLY SHOWS THE SET-POINT.
Display delay: (0 ÷ 20min0sec; resolution 10 sec) when the temperature increases, the display is updated of 1°C or 1°F
after this time.
Type of action: 0 = cooling; 1 = heating.
Compressor ON time with faulty probe: (0 to 255min) If there is a P1 probe failure the controller will automatically cycle
the compressor on/off according to Con & CoF to maintain basic cooling. Con is the compressor “ON” time.
Compressor OFF time with faulty probe: (0 to 255min) If there is a P1 probe failure the controller will automatically cycle
the compressor on/off according to Con & CoF to maintain basic cooling. CoF is the compressor “OFF” time.
Alarm muting:
0 = Alarm relay remains active when alarm buzzer is muted;
1 = Alarm relay is cancelled when alarm buzzer is muted.