1592031000 Univ-R4 GB - r1.1 - 2012.07.23 Universal-R
5/20
4.
QUICK START UP PROCEDURE – Up and running in 5 easy steps
This Quick Start Up section is designed to get you up and running with the minimum of fuss. Just follow these 5 simple steps.
STEP 1
Install the new Universal-R, connect the correct number of probes and
connect the wiring - See below:
1.
Table 1: parameter tC settings
2.
Section 5: Typical connections
STEP 2
Turn on power,
THEN WITHIN 1 MINUTE COMPLETE STEPS 3, 4 AND 5.
STEP 3
Press the “DOWN” key for 3 seconds and the controller will automatically
recognise and adjust itself to the type of probes connected. (The display
briefly shows tPd followed by ntC or PtC).
STEP 4
Press the “AUX/tC” key for 3 seconds and the setting of parameter tC is
displayed. Use the UP or DOWN keys to adjust to required setting then
confirm by pressing SET (see table 1 below).
STEP 5
Press SET for 3 seconds until the °C or °F icon starts to flash, then adjust
the SET POINT using the UP or DOWN keys, then press SET again to
confirm.
Notes:
1.
All probes must be of the same type, either PTC or NTC;
2.
Probes must be at between -50 to 60°C for auto recognition to work;
3.
If 1 minute expires before you have completed quick set up, either turn OFF / ON power to start set up again or enter
parameter as per the instructions and adjust your parameter settings manually (see Section 9).
Table 1: parameter “tC” settings
Parameter
tC
Type of Control
Required
probes
1
On / Off thermostat – Cooling
x 1
2
Off cycle defrost (timed)
x 1
3
Electrical / Hot Gas defrost, time initiated / time terminated
x 1
4
Electrical / Hot Gas defrost, time initiated / temperature terminated
x 2
5
Electrical / Hot Gas defrost, time initiated / temperature term evap. fan delay
x 2
6
Double evaporators applications (similar to setting 5)
x 3
7
On / Off thermostat – Heating
x 1
Note: “tC” settings 3, 4, 5 and 6 use Electrical defrost as default. Hot Gas is possible by setting parameter “tdF” for gas defrost. Settings
1, 2, 3 & 7 do not require that the 2nd and the 3rd probe to be fitted. Take note of the number of probes to be connected for the selected
application.
As you change parameter tC, defaults change and should be approximately correct for that application but we strongly
recommend you check all parameter default values listed in these instructions to ensure they suit your particular application
and make further adjustments if necessary. Read the following sections for information about programming.