1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
iProCHILL
191/205
10.29 CONDENSER WATER PUMPING OVERLOAD ALARM
Alarm code
AtC1
(condenser n° 1 water pump overload alarm)
AtC2
(condenser support n° 2 water pump overload alarm)
Display in keyboard
Cond.pump 1 overl
Cond.pump 2 overl
Cause of activation
DI configured as Condenser main pump Overload (AI type=58) active.
DI configured as Condenser support pump Overload (AI type=59) active.
Reset
With DI not active
Reset
Manual.
Icon
flashing
Action
Alarm relay (DO type=1) + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Reverse valve
It follows its regulation
Recovery valve
it follows its regulation
Free-cooling on/off valve
it follows its regulation
Auxiliary relay
it follows its regulation
Idle running valve
It follows its regulation
Supply ventilation
Off if no pump is available
Condensation ventilation
Off if no pump is available
Support/boiler/anti-freeze
It follows its regulation
Evaporator water pump
It follows its regulation
Condenser water pump
Off if no pump is available
Compressors
Off if no pump is available
Pump down solenoid valve
Off if no pump is available
10.30 GENERIC ALARM 1
Alarm code
ALc1
(Generic alarm 1)
Display in keyboard
Generic AL1
Cause of activation
DI configured as Generic alarm 1 digital input (DI type=89) active for the time
set in the Par AL54
Reset
DI configured as Generic alarm 1 digital input (DI type=89) not active for the
time set in the Par AL55
Reset
Automatic
– becomes manual after AL53 interventions/hour. It is recorded in
the historical alarms only with manual reset
Icon
flashing
Action
Alarm relay (DO type=166) + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Other loads
Off