10.23 HEAT RECOVERY DISABLING SIGNAL DUE TO HIGH CONDENSATION
TEMPERATURE/PRESSURE IN COOLING WORKING MODE
Alarm code
b1rC
…b4rC
(circuit n° 1
…4 recovery disabling alarm)
Display in keyboard
Recovery dis.hi t/p C1
…Recovery dis.hi t/p C4
Cause of activation
RC01=3, if the probe for disable heat recovery (configured as condensation
temperature or pressure) measures a value >= rC07 set, alarm occur.
Reset
The condensation pressure or temperature probe measures a value <=
rc07 set
– rC08 differential
Heat recovery disabling function is intervened due to Par. rC09 time
expired.
Reset
Automatic
Icon
flashing
Action
Alarm relay + buzzer NOT activated
Regulators
Alarm
Relay + buzzer NOT activated
Reverse valve
It follows its regulation
Recovery valve
Off
Free-cooling on/off valve
it follows its regulation
Auxiliary relay
It follows its regulation
Idle running valve
It follows its regulation
Supply ventilation
It follows its regulation
Condensation ventilation
It follows its regulation
Support/boiler/anti-freeze
It follows its regulation
Pump/and water evaporator
and condenser
It follows its regulation
Compressors
It follows its regulation
Pump down solenoid valve
It follows its regulation
10.24 UNLOADING SIGNAL DUE TO LOW EVAPORATION PRESSURE IN HEATING WORKING MODE
(Not available)
Display label meaning
b1Eu
(circuit n° 1 unloading from condenser coil signal)
b2Eu
(circuit n° 2 unloading from condenser coil signal)
b3Eu
(circuit n° 3 unloading from condenser coil signal)
b4Eu
(circuit n° 4 unloading from condenser coil signal)
Display in keyboard
Unload lo press.circ1
…Unload lo press.circ4
Cause of activation
When working, if the probe configured as condensation temperature,
configured as pressure control or as evaporation pressure, measures a value <
Un13 set
Reset
if the condensation pressure/temperature or the evaporation pressure
measures a value > Un13 + Un14
With unloading function inserted after the time set Par. Un15
Reset
Automatic
Icon
flashing
Action
Alarm relay + buzzer NOT activated
Regulators
Alarm
Relay + buzzer NOT activated
Reverse valve
It follows its regulation
Recovery valve
it follows its regulation
Free-cooling on/off valve
it follows its regulation
Auxiliary relay
It follows its regulation
Idle running valve
It follows its regulation