1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
iProCHILL
142/205
US 23
Analog output 1 maintaining minimum value
0 = no
1 = yes
0
1
Auxiliary proportional output n°2 (0÷10V DC)
US 24
Proportional auxiliary output 2 operation
0 = not enabled
1 = always enabled with direct action
2 = enabled with direct action only with the unit ON
3 = always enabled with inverse action
4 = enabled with inverse action only with the unit ON
0
4
US 25
Analogue input configuration for control of the proportional auxiliary relay 2
1
66
US 26
Set point of proportional auxiliary output 2
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 27
Differential of proportional auxiliary output 2
0.1
1
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
US 28
Minimum value for 0-10V analogue 2 output
0
US29
%
US 29
Maximum value for 0-10V 1 analogue 2 output
US28
100
%
US 30
Analog output 2 maintaining minimum value
0 = no
1 = yes
0
1
Auxiliary proportional output n°3 (0÷10V DC)
US 31
Proportional auxiliary output 3 operation
0 = not enabled
1 = always enabled with direct action
2 = enabled with direct action only with the unit ON
3 = always enabled with inverse action
4 = enabled with inverse action only with the unit ON
0
4
US 32
Analogue input configuration for control of the proportional auxiliary relay 3
1
66
US 33
Set point of proportional auxiliary output 3
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 34
Differential of proportional auxiliary output 3
0.1
1
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
US 35
Minimum value for 0-10V analogue 3 output
0
US36
%
US 36
Maximum value for 0-10V 1 analogue 3 output
US35
100
%
US 37
Analog output 3 maintaining minimum value
0 = no
1 = yes
0
1
Auxiliary proportional output n°4 (0÷10V DC)
US 38
Proportional auxiliary output 4 operation
0 = not enabled
1 = always enabled with direct action
2 = enabled with direct action only with the unit ON
3 = always enabled with inverse action
4 = enabled with inverse action only with the unit ON
0
4
US 39
Analogue input configuration for control of the proportional auxiliary relay 4
1
66
US 40
Set point of proportional auxiliary output 4
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 41
Differential of proportional auxiliary output 4
0.1
1
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
US 42
Minimum value for 0-10V analogue 4 output
0
US43
%
US 43
Maximum value for 0-10V 1 analogue 4 output
US42
100
%
US 44
Analog output 4 maintaining minimum value
0 = no
1 = yes
0
1
Alarms
Parameter Description
min
max
um
Resolution
Low pressure alarm
AL 1
Low pressure alarm delay from a digital/analogue input
0
250
Sec
AL 2
Defines low pressure alarm operation with pump-down enabled
0 = independent from the pump down
1 = blocks the compressors until the pressure switch is disabled
2 = lets the compressors reach peak values
0
2