
1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
iProCHILL
174/205
10.8 LOW EVAPORATION PRESSURE ALARM (IF THE EVAPORATOR PRESSURE PROBES ARE
CONFIGURED)
Alarm code
b1lp-
…b4lP
(circuit n° 1-
…circuit n° 4 evaporator low pressure alarm)
Display in keyboard
Low press circuit1-
…Low press circuit4
Cause of activation
The alarm is activated when the probe configures as the evaporator pressure
(AI type=56
…59) < AL03 set in the following conditions.
working in cooling or heating mode
stand-by or OFF-remote if AL08 = 1
In defrost if AL06=1
The alarm is not signalled:
in defrost for time AL07 in correspondence with valve inversion
on compressor switch-on for the time AL01
Reset
If the evaporation control probe measures a temperature > of the AL03 set +
differential AL04
Reset
Automatic
– it becomes manual after AL05 interventions/hour (reset procedure
in functions menu)
Icon
flashing
Action
Relay + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Reverse valve
it follows its regulation
Recovery valve
it follows its regulation
Free-cooling on/off valve
it follows its regulation
Auxiliary relay
It follows/they follow its/their regulation
Idle running valve
It follows its regulation
Supply ventilation
It follows its regulation
Condensation ventilation
Off
Support/boiler/anti-freeze
It follows its regulation
Pump/and water evaporator
and condenser
It follows its regulation
Affected
circuits
compressors
Off
Unaffected
circuits
compressors
It follows its regulation
Unaffected circuits pump
down solenoid valve
It follows its regulation
Affected
circuits
pump
down solenoid valve
off