1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
iProCHILL
147/205
Et 10
Selection of output circuit valve 2 driver 1
0 = Not present
1 = Circuit 1
2 = Circuit 2
3 = Circuit 3
4 = Circuit 4
0
4
Et 11
Selection of output circuit valve 1 driver 2
0 = Not present
1 = Circuit 1
2 = Circuit 2
3 = Circuit 3
4 = Circuit 4
0
4
Et 12
Selection of output circuit valve 2 driver 2
0 = Not present
1 = Circuit 1
2 = Circuit 2
3 = Circuit 3
4 = Circuit 4
0
4
Et 13
Selection of output circuit valve 1 driver 3
0 = Not present
1 = Circuit 1
2 = Circuit 2
3 = Circuit 3
4 = Circuit 4
0
4
Et 14
Selection of output circuit valve 2 driver 3
0 = Not present
1 = Circuit 1
2 = Circuit 2
3 = Circuit 3
4 = Circuit 4
0
4
Et 15
Selection of output circuit valve 1 driver 4
0 = Not present
1 = Circuit 1
2 = Circuit 2
3 = Circuit 3
4 = Circuit 4
0
4
Et 16
Selection of output circuit valve 2 driver 4
0 = Not present
1 = Circuit 1
2 = Circuit 2
3 = Circuit 3
4 = Circuit 4
0
4
Et 17
Number of additional steps to achieve complete closure. When a closing
request is received, the valve starts from the current number of steps and
moves to 0, then closes for the set number of steps
0
250
Et 18
Number of return steps in opening mode after the valve has been closed
completely. These decompress any closing spring inside the valve or to
prevent sealing the circuit
0
250
Et 19
Maximum number of adjusting steps of the valve
Et20
8000
Et 20
Minimum number of adjusting steps of the valve
0
Et19
Et 21
Maximum current value per phase of the stepper motor
0
100
mA
x10 mA
Et 22
Current stand-by value
0
100
mA
x10 mA
Et 23
Maximum number of steps per second of the valve
0
600
Hz
Et 24
Indicates the number of steps the valve has to move before compressor start-
up.
0 = function is disabled
0
Et19
Et 25
Sets valve manual operation mode
0= Automatic
1= Manual
0
1
Et 26
Absolute number of steps the valve has to move in manual mode
0
Et19
Et 27
Low pressure alarm activation delay (LOP)
0
250
Sec
Et 28
High pressure alarm activation delay (MOP)
0
250
Sec
Et 29
High overheating alarm activation delay
0
250
Sec
10 Sec
Et 30
Low overheating alarm activation delay
0
250
Sec
10 Sec
PID regulation in chiller mode
Et 31
PID proportional constant in chiller mode
0.0
50.0
°C
Dec
Et 32
PID integral time in chiller mode
0
500
Sec
Et 33
PID derivative constant in chiller mode
0
250
Sec
Et 34
Overheating regulation set point during chiller mode
0.0
25.0
°C
Dec
Et 35
Overheating regulation dead band in chiller mode
0.0
5.0
°C
Dec
Et 36
High overheating threshold. The alarm status is signaled after the high
overheating alarm activation delay
Et34
80.0
°C
Dec