4.3.2
Piping recommendations
Typical installation for a Series 1500 LTM
Figure 4-3:
•
Note the direction of flow indicated on the plate near the inlet flange and install accordingly.
•
New installations: Flush lines thoroughly to rid piping of potentially damaging foreign material
such as welding bead, pipe scale, etc. before the turbine meter is placed into service.
Important
A spool piece installed in place of the turbine meter is recommended for this procedure.
NOTICE
Comply with local government regulations and company requirements.
Important
Ensure that piping or other attachments connected to the turbine meter are not under stress.
Important
Provide fire prevention measures and equipment per local regulations.
4.3.3
Calibration options for the turbine meter
Daniel offers a standard six-point calibration (from 10% to 100%); or can provide other
customer requested calibration data.
Prepare the turbine meter for use
User manual
47
Содержание daniel 1500 series
Страница 1: ...User manual P N 3 9008 515 Rev D July 2016 Daniel Series 1500 Liquid Turbine Meter NPS 3 through 24 ...
Страница 8: ......
Страница 12: ...Plan 2 Daniel Series 1500 Liquid Turbine Meter NPS 3 24 ...
Страница 64: ...Prepare the turbine meter for use 54 Daniel Series 1500 Liquid Turbine Meter NPS 3 24 ...
Страница 66: ...Install 56 Daniel Series 1500 Liquid Turbine Meter NPS 3 24 ...
Страница 72: ...Installation procedure 62 Daniel Series 1500 Liquid Turbine Meter NPS 3 24 ...
Страница 74: ...Testing 64 Daniel Series 1500 Liquid Turbine Meter NPS 3 24 ...
Страница 75: ...Part III Operate Operate User manual 65 ...
Страница 76: ...Operate 66 Daniel Series 1500 Liquid Turbine Meter NPS 3 24 ...
Страница 80: ...Maintain 70 Daniel Series 1500 Liquid Turbine Meter NPS 3 24 ...
Страница 101: ...Decommission the turbine meter User manual 91 ...
Страница 102: ...Decommission the turbine meter 92 Daniel Series 1500 Liquid Turbine Meter NPS 3 24 ...
Страница 103: ...Decommission the turbine meter User manual 93 ...