IEC 62591 Wireless Interface Instruction Manual (for ControlWave Micro)
2-6
Installation
Revised October-2019
Figure 2-6. IEC 62591 Module – Connecting Termination Jumpers
2.4 Configuring Wireless Devices for the Network
See the product data sheet (available on our
) for a list of devices
Emerson has tested with the IEC 62591 Wireless Interface.
You must configure the following for each device in the wireless
network:
▪
A long tag name which is unique in the wireless network
▪
A Network ID (must be the same for every device in the wireless
network)
▪
A Join Key (must be same for every device in the wireless network)
Caution
Configure all devices belonging to a site to use the same Network ID
and join key. To avoid network errors, configure all devices in adjacent
networks to use a different Network ID and join key.
You configure these using the 375 or 475 Field Communicator or using
AMS Device Configurator. If you have AMS Device Configurator
software, see its online help for details on how to do this.
Termination Jumpers