IEC 62591 Wireless Interface Instruction Manual (for ControlWave Micro)
Revised October-2019
Configuration and Commissioning
3-15
names in the Commission List, and the long tag names in the Active
List – the iostrTag Name and ibDecommission flag are the only portions
you create or modify.
If, for some reason, you want to temporarily prevent data collection
from a device in your wireless network, you can just set its
decommission flag to TRUE.
3.2.8 Specifying the Join Key
All wireless devices in your wireless network share the same Join Key.
You must also specify the same Join Key in your ControlWave project.
You specify the Join Key in the Wireless worksheet.
Double-click on the Wireless worksheet and specify the Join Key using
the strJoinKey variable.
strJoinKey := '12345678-00000000-00000000-00000000';
3.2.9 Specifying the Network ID and Slot Number
The wireless network of devices detected by the Field Link has a
Network ID.
You must specify the Network ID in the IEC62591_NETID variable in
the WirelessV worksheet of your ControlWave project.
In the same worksheet you use the IEC62591_SLOT variable to specify
the slot number of the ControlWave Micro controller that holds the IEC
62591 module. The IEC 62591 module can reside in any open I/O slot
(slot 3 or higher) except for the last slot in the chassis.
Double-click on the WirelessV worksheet and specify the Network ID
and slot number.
Figure 3-3. Editing the WirelessV Worksheet
3.2.10 Configuring the Statistics List (OPTIONAL)
The optional Statistics List maintains information on the health of IEC
62591 communications for debugging purposes.
Specify the
Network ID here.
Specify the slot that
holds the IEC 62591
module