© 2017 Emerson Climate Technologies, Inc.
23
AE4-1414
Table 4
– Compressor Refrigerant Charge Limits
Model
Charge Limit
120% x Limit*
Tandem Charge Limit
Pounds
Kg
Pound
Kg
Pounds
kg
ZPV066
ZPV096
15
7
18
8
18
8
Table 5
– Speed Adjustment
Speed Range
(RPM
Default (RPM)
Acceleration
RPM/Sec
Deceleration
RPM/Sec
Notes
Range
Default
Range
Default
Start
3600-7200
3600
400-1000
1.0
NA
NA
1
Run
1000-7200
+/- 200 RPM/S
Stop
1000-7200
3600 or Envelope Minimum
NA
NA
50-500
2.0
2, 3, 4
Notes:
1. Once the compressor reaches 3600 RPM, hold for two minutes prior to accelerating or decelerating.
2. If envelope control is active, reduce the speed by 30% for a default of three minutes. After two minutes and
the command has not changed, decelerate to the minimum envelope speed and shut down the
compressor.
3. If envelope control is not active and the speed is above 3600 RPM, decelerate 3600 RPM for a default of
three minutes. After two minutes and the command has not changed, shut down the compressor.
4. If envelope control is not active and the speed is below 3600 RPM, maintain current speed for a default of
three minutes. After two minutes and the command has not changed, shut down the compressor.
The contents of this publication are presented for informational purposes only and are not to be construed as warranties or guarantees, express or implied, regarding
the products or services described herein or their use or applicability. Emerson Climate Technologies, Inc. and/or its affiliates (collectively "Emerson"), as applicable,
reserve the right to modify the design or specifications of such products at any time without notice. Emerson does not assume responsibility for the selection, use or
maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson product remains solely with the purchaser or end user.
Содержание Copeland Scroll ZPV066
Страница 14: ... 2017 Emerson Climate Technologies Inc 14 AE4 1414 ...
Страница 15: ... 2017 Emerson Climate Technologies Inc 15 AE4 1414 ...
Страница 17: ... 2017 Emerson Climate Technologies Inc 17 AE4 1414 ...
Страница 18: ... 2017 Emerson Climate Technologies Inc 18 AE4 1414 ...
Страница 19: ... 2017 Emerson Climate Technologies Inc 19 AE4 1414 ...
Страница 20: ... 2017 Emerson Climate Technologies Inc 20 AE4 1414 Figure 9 Start Up Procedure Figure 10 Shut Down Procedure ...