© 2017 Emerson Climate Technologies, Inc.
22
AE4-1414
Table 2
– Compressor Motor Specifications
Attribute
Unit
ZPV066
ZPV096
Dielectric Strength Leakage Current
mA
6
6
Dielectric Strength Test Voltage
Volts-AC
2,500
2,500
Dielectric Strength Test Time
Seconds
1
1
Motor Poles
#
6
6
Motor Input Frequency
Hertz
50-360
60-360
Recommended Switching Frequency
Hertz
6,000
6,000
Table 3
– Emerson Compressor & Drive Selection
Drive
Model
Compressor
Model
Rated
Voltage
Drive Voltage
Input Range
Drive
Nominal Power
EVC1150B -J1-124
ZPV0662E-5E9
230
200-240
15kW
EVC1150B -K2-124
ZPV0662E-4E9
380
380-480
EVC1150B -K1-124
ZPV0662E-7E9
460
380-480
EVC1150B -L1-124
ZPV0662E-7E9
575
500-575
EVC1185B -J1-124
ZPV0962E-5E9
230
200-240
18kW
EVC1185B -K2-124
ZPV0962E-4E9
380
380-480
EVC1185B -K1-124
ZPV0962E-7E9
460
380-480
EVC1185B -L1-124
ZPV0962E-7E9
575
500-575
Содержание Copeland Scroll ZPV066
Страница 14: ... 2017 Emerson Climate Technologies Inc 14 AE4 1414 ...
Страница 15: ... 2017 Emerson Climate Technologies Inc 15 AE4 1414 ...
Страница 17: ... 2017 Emerson Climate Technologies Inc 17 AE4 1414 ...
Страница 18: ... 2017 Emerson Climate Technologies Inc 18 AE4 1414 ...
Страница 19: ... 2017 Emerson Climate Technologies Inc 19 AE4 1414 ...
Страница 20: ... 2017 Emerson Climate Technologies Inc 20 AE4 1414 Figure 9 Start Up Procedure Figure 10 Shut Down Procedure ...