C6.1.9/0219/E
46
Code
Description
Cause
Action
Reset
E82
Probe configuration error
Same probe
configuration present in
Probe Configuration
List (P3, P4, P5, P6,
P7). For example,
A13 = Ambient Temp
(NTC10K),
A15 = Ambient Temp
(NTC10K)
Correct the configuration
Board must be reset
E83
DI configuration error
Same digital input
configuration present in
DI Input Configuration
List (DI1, DI2, DI3). For
example,
R04 = Door switch,
R07 = Door switch
Correct the configuration
Board must be reset
E84
Compressor configuration error
Case 1 0: Digital
compressor relay is
configured, no digital
solenoid configuration;
Case 1: Digital
compressor relay is
configured, no digital
solenoid configuration;
Case 2: no Digital
compressor relay
configuration, digital
solenoid is configured;
Case 3: C05 = 3,
Digital compressor
relay and digital
solenoid are configured
Correct the configuration
Board must be reset
E85
Injection probe configuration error
Injection EXV output
mode is selected, but
no relevant sensors
Injection EXV will not work
Automatically as soon as the injection EXV is
configured exactly
Table 23: Alarm code overview