C6.1.9/0219/E
40
Appendix 2: Alarm menu
Code
Description
Cause
Action
Reset
E01
AI1 error (Probe 1/Suction pressure
transducer failure alarm)
Probe failure or out of
range
Only in digital unit - Compressor is
activated according to C23, and
compressor on & off time according to
D02 & D03
Automatically as soon as the probe restarts
working
E02
AI2 error (Probe 2/mid-coil
temperature sensor failure alarm)
Probe failure or out of
range
The fans speed control is disabled
Automatically as soon as the probe restarts
working
E03
AI3 error (Probe 3/discharge line
temperature sensor failure alarm)
Probe failure or out of
range
Discharge temperature control is
disabled
Automatically as soon as the probe restarts
working
E04
AI4 error (Probe 4/PHE vapour inlet
temperature sensor failure alarm)
Probe failure or out of
range
PHE superheat control is disabled
Automatically as soon as the probe restarts
working
E05
AI5 error (Probe 5/PHE vapour
outlet temperature sensor failure
alarm)
Probe failure or out of
range
PHE superheat control is disabled
Automatically as soon as the probe restarts
working
E06
AI6 error (Probe 6/ambient
temperature sensor failure alarm)
Probe failure or out of
range
The functions related to Probe 6
(ambient sensor) are disabled
Automatically as soon as the probe restarts
working
E07
AI7 error
Probe failure or out of
range
The functions related to Probe 7 are
disabled
Automatically as soon as the probe restarts
working
E08
Battery error
The internal back up
battery is not working
properly
Disable the clock function to restart the
unit
No reset required
E09
Current sensor 1 error
Probe out of range
The functions related to current sensor
are disabled
Automatically as soon as the probe restarts
working
E10
Current sensor 2 error
Probe out of range
The functions related to current sensor
are disabled
Automatically as soon as the probe restarts
working
E11
Voltage sensor 1 error
Probe out of range
The functions related to voltage sensor
are disabled
Automatically as soon as the probe restarts
working
E12
Voltage sensor 2 error
Probe out of range
The functions related to voltage sensor
are disabled
Automatically: as soon as the probe restarts
working
E13
Voltage sensor 3 error
Probe out of range
The functions related to voltage sensor
are disabled
Automatically as soon as the probe restarts
working
E14-E19
Reserved
E20
Lost phase error
Power supply phase
loss (3-phase unit)
The compressor will trip
Automatically as soon as lost phase is
recovered and H08 delay time-out