Code
Description
Cause
Action
Reset
E55
Fan failure
Fan alarm contact open Warning signal only
Check fans protection
E60
Max pressure alarm of superheating
When the temperature
which converts from
suction pressure rises
above the set threshold
(MoP/L08) for the time
dMP/L10
0
The MOP control ends when the superheat is
lower than the superheating setpoint
E61
Min pressure alarm of superheating
When the temperature
which converts from
suction pressure falls
below the set threshold
(LoP/L09) for the time
dLP/L11
0
The LOP control ends when the temperature
rises to 4°C above the threshold of LoP/L09 or
in case of superheating under the SET low
superheat when the temperature is in [LOP,
LOP+4°C]
E62
High superheating alarm
If the superheat
remains above
HSH/L04 for HSd/L06
Valve is opened at (HSt/M01).
Automatically with the SH condition
E63
Low superheating alarm
If superheat below
LSH/L03
Valve will slowly close to the LSt/M02
Automatically with the SH condition
E64
High room temperature alarm
If temperature above
ALU/G48
Warning signal only
If temperature
≤ ALU/G48-AHY/G50 reset
E65
Low room temperature alarm
If temperature below
ALL/G49
Warning signal only
If temperature
≥ ALL/G49+AHY/G50
E66
Door open alarm
If the door is open
longer than dSA/G53
Warning signal only if rrd/G09 is "no"
Alarm and compressor trip if rrd/G09 is
"yes"
Manual or automatic
– see Action
E80
rtC warning, date not correct
HW problem in the
board
Disable the rtC or change the board
0
E81
rtC warning, communication error
HW problem in the
board
Disable the rtC or change the board
0