8
C6.1.9/0219/E
2.7.7 P&I diagram for OMTE-76D & OMTE-90D units
Figure 7: P&I diagram for OMTE-76D & OMTE-90D
Position
Description
Comments
B1
PT P1 Pressure transmitter suction (AI1)
PPR15
B2
Condensing pressure transmitter (AI2)
PPR30
B3
DLT Discharge line temperature sensor (AI3)
NTC 86k
B6
Ambient temperature probe (AI6)
NTC 10k
B7
Liquid receiver with liquid level watch
LW4-L120 Alco
B10
PSL >> LP Mechanical low-pressure switch PS1 (PSL)
PS1-A3A Alco
B11
TT >> DLT Discharge line thermostat 130°C compressor 1
B12
TT >> DLT Discharge line thermostat 130°C compressor 2
B21
PSH >> High-pressure cut-out device compressor 1
PS3-W6S Alco
B22
PSH >> High-pressure cut-out device compressor 2
PS3-W6S Alco
E1
Crankcase heater compressor 1
E2
Crankcase heater compressor 2
M1
High-efficiency Digital Scroll compressor ZBD family
Compressor 1
M2
High-efficiency standard Scroll compressor ZB family
Compressor 2
M3
High-efficiency EC fan
FN071-ZIQ
M4
High-efficiency EC fan
FN071-ZIQ
Y1
Digital control solenoid valve
Table 5: Legend of the P&I diagram for OMTE-76D & OMTE-90D units