background image

Document Part # 026-4600 Rev 3 23-APR-2008

Page 5 of 8

©2007 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use. 

Visit our website at http://www.emersonretailsolutions.com/ for the latest technical documentation and updates.

Control Link RSC Installation Instructions

technical bulletin

code will continue until the temperature returns to normal (1°F below high temp alarm setpoint or 1°F above low temp set-
point) or until the Alarm Silence button is pressed (alarm is suspended for 5 minutes, then will reoccur if problem is still 
active).

Defrost Operation

Defrost cycles are initiated at the times programmed in the CL-RSC. During defrost, the compressor relay is de-energized, 
and the defrost relay is energized. The defrost relay will be de-energized when the defrost termination temperature is 
reached or until the programmed defrost duration has elapsed (whichever occurs first). While the defrost relay is energized, 
the display will show 

dEF

 instead of the case temperature. 

If a defrost drip duration has been programmed, immediately after defrost termination the compressor relay will remain 
OFF for an amount of time to allow moisture to drain off the coil. During this time, the display will read 

drIP

. When the 

drip time is over, refrigeration will resume. Fans may be either off or on during defrost, based on user programming.

Manual Defrost

A manual defrost may be initiated at any time by holding the SET button for 10 seconds until the 

dEF

 message is shown on 

the display. Defrost will begin immediately and terminate normally. If one of the auxiliary inputs is configured as a manual 
defrost switch, a contact closure on the switch will also initiate a manual defrost.

Compressor Fail-Safe Mode

If the case temperature sensor fails, the CL-RSC will operate in a fail-safe mode that cycles the compressor ON and OFF at 
a user-defined regular interval. The ON/OFF rate is determined by setting parameters 

CSFP

 and 

CSFO

 in the CL-RSC. 

CSFP

 

sets the interval period, and 

CSFO

 sets the amount of time during that period the compressor will be ON.

For example, if during fail-safe you want the compressor to alternate being ON for three minutes and OFF for seven min-
utes, set 

CSFO

 to 3 and 

CSFP

 to 10. This will cause the compressor to be ON for three minutes of the 10 minute interval, and 

OFF for the remaining seven minutes.

Output Board Comm Loss/Power Loss Fail-Safes

The 618-1120 Output Board has Form C contacts. The fan and contactor/solenoid outputs are wired to the normally closed 
(N.C.) contacts on the board, meaning refrigeration and fan outputs will fail to the CLOSED state when power is lost or 
communication with the RSC is lost. The defrost and auxiliary outputs are wired to the normally open (N.O.) contacts, 
meaning these fan outputs will fail to the OPEN state.

Auxiliary Relay Control

The auxiliary relay on the Relay Expansion board, or relay #2 on the Control Link main module, may be used to control 
various functions:

Defrost

 (only an option for relay #2 if no Expansion Board is used).

Lighting Control: 

Up to six ON/OFF times per day may be programmed for case lights. If not connected to an E2, the Control 

Link main module will require a real-time clock module to perform lighting control.

Case Fans:

 Fans can be programmed to be always ON, or ON only when the compressor is ON. Other features include program-

mable fan state during defrost, and suspension of fan activation after defrost based on time and/or case temperature.

Alarm:

 The relay will close when an alarm is active on the Control Link main module.

Содержание Control Link Refrigeration System Controller

Страница 1: ...sors mounted in the case The CL RSC may control two external relays compressor plus one configurable relay directly from its two onboard dry contact relay outputs or it may use a pluggable expansion output board P N 618 1120 for compressor control or 618 2085 for refrigeration solenoid control for activating case system components NOTE For information about networking Control Link RSC with E2 refe...

Страница 2: ...lower right side of the Control Link module Figure 4 The expansion board is powered from the CL RSC and requires no external power connection Power Control Link Module with 618 1120 output board When the 618 1120 output board is used with a Control Link module connect the L and N spade lug terminals on the module to the L and N spade lug terminals on the output board Figure 4 Connect 120 240 VAC 5...

Страница 3: ...gure 7 Refer to Table 1 for relay ratings Compressor Relays The Control Link uses two relays on the output board to control the compressor Line voltage must be connected to the Line 1 and Line 2 connectors on relays 1 and 2 respectively The Load 1 and Load 2 connectors are wired to the compressor Figure 7 shows the wiring diagram Refer to Table 1 for relay ratings Pressure Switch Wiring If desired...

Страница 4: ...p based on the value of the CSUd parameter default 10 minutes After this delay the CL RSC resumes normal refrigeration control To prevent nuisance alarms when the case is first started up no high temperature case alarms will be generated until 120 minutes after the start of the first cooling cycle Normal Operation Refrigeration When in refrigeration mode the CL RSC energizes the compressor relay w...

Страница 5: ...h will also initiate a manual defrost Compressor Fail Safe Mode If the case temperature sensor fails the CL RSC will operate in a fail safe mode that cycles the compressor ON and OFF at a user defined regular interval The ON OFF rate is determined by setting parameters CSFP and CSFO in the CL RSC CSFP sets the interval period and CSFO sets the amount of time during that period the compressor will ...

Страница 6: ...ds or leave controller idle for 60 seconds You will lose all setpoint changes made since you entered general programming mode NOTE Parameters in General Parameters shaded gray are only shown if the real time clock module is being used General Parameters Code Description Min Max Default CSP Temp control set point deg F can be displayed in deg C 40 100 25 CLSt Clock time set military UP button adjus...

Страница 7: ...liary input whose function is determined by SI2d ntc dGt ntc SI2d If input 2 defr term is dGt determines function of digital input SS setpoint shift ON causes the value of CSS to be added to set points IdeF start manual defrost IdeF SS IdeF SI3 Determines type of sensor on input 3 ntc 10K CPC thermistor dGT digital sensor ntc dGt ntc SI3d If input 3 is dGt determines function of digital input SS s...

Страница 8: ... the auxiliary relay ALAr close on alarm LCOn lighting control Visible only if rYbd yES ALAr LCOn ALAr LIOn LIOF L6On L6Of Visible only if ArA LCon or r2Fn LCon There are six ON OFF pairs where you may specify times of day for turning the lighting control relay ON and OFF Enter the first ON time of the day in the L1On field and the first OFF time in the L1OF field If necessary continue entering ON...

Отзывы: