background image

Document Part # 026-4600 Rev 3 23-APR-2008

Page 8 of 8

©2007 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use. 

Visit our website at http://www.emersonretailsolutions.com/ for the latest technical documentation and updates.

Control Link RSC Installation Instructions

technical bulletin

Restore to Defaults

The blue button located on the top of the Control Link main module (see 

Figure 10)

 may be used to 

restore the Control Link RSC to its “default setpoints,” which can be either the RSC’s factory default 
setpoints (as shown in the “Default” columns of the General and Advanced Parameters) or a cus-
tomer-specific set of defaults programmed using the Control Link PC tool. 

Do NOT press the 

Restore to Defaults button unless you are sure what default values will be restored.

To perform a restore, press and hold this button for 15 seconds. The display will flicker briefly to 
indicate the command to reset was received. 

Power down the Control Link, 

wait 5 seconds,

 

and 

restore power.

Alarms

There are ten different alarms that may occur in a CL-RSC. When an alarm is detected, CL-RSC takes the following actions:

Displays a four-character error code on the LED display (unless parameter “

Add

” is set to “

yES

Closes the Aux relay (if parameter “

ArA

” is set to “

ALAr

”)

Uses fail-safe modes and settings to compensate for the alarm condition and attempt to keep the system running until repair can be done.

Clearing Alarms

T

o clear an alarm and cause the CL-RSC to resume normal operation, press the Alarm Silence button. The alarm message will disap-

pear, the Aux relay will open (if parameter “

ArA

” is set to “

ALAr

”), and the CL-RSC will attempt to resume normal operation. If the 

condition or conditions that caused the alarm are still present, the alarm will reoccur after the appropriate alarm delays have elapsed.

ArA

For the expansion board, sets the function of the auxiliary relay. 

ALAr

 =close on alarm, 

LCOn

 = lighting control.

Visible only if 

rYbd

=

yES

.

ALAr

LCOn

ALAr

LIOn LIOF

.
.

L6On L6Of

Visible only if 

ArA

=

LCon

 or 

r2Fn

=

LCon

. There are six ON/OFF pairs where you may specify times of day for 

turning the lighting control relay ON and OFF. Enter the first ON time of the day in the 

L1On

 field and the first 

OFF time in the 

L1OF

 field. If necessary, continue entering ON/OFF times in the 

L2On

 / 

L2Of

 fields, then 

L3On

 / 

L3Of

, etc. Leave all unused schedule time pairs set to 0:00 to disable them.

0:00

23:59

0:00

LOC

General parameter password enable. If 

yES

, user must enter password to change general parameters.

no

yES

no

PASS

Password for general programming. If 

0000

, no password is required.

0000

9999

0000

APAS

Password for advanced programming.

0000

9999

0000

rbtp

Relay board type. 

0-St

 for the “standard” (618-2085) board, 

1-gp

 for the “general purpose” (618-1120) board.

0-St

1-gp

0-st

Alarm Codes

Code

Description

tS1O ts20 ts30

Open sensor alarm for sensor #1 (case temp), sensor #2 (defr. term), or sensor #3. When 

tS1O

 is active, CL-RSC uses 

CSFP

 and 

CSFO

 to pulse the 

compressor ON and OFF as a fail-safe. When 

ts20

 is active, defrosts will not terminate by temperature and will last the full duration (

dEFd

).

tS1S ts2s ts3s

Short sensor alarm for sensor #1 (case temp), sensor #2 (defr. term), or sensor #3. When 

tS1S

 is active, CL-RSC uses 

CSFP

 and 

CSFO

 to pulse the 

compressor ON and OFF as a fail-safe. When 

ts2s

 is active, defrosts will not terminate by temperature and will last the full duration (

dEFd

).

HtP

High temperature alarm setpoint was reached after the 

Adtd

(def. delay) or 

AdEL

 (normal delay) elapsed. No fail-safe actions.

LtP

Low temperature alarm setpoint was reached after the 

Adtd

(defrost delay) or 

AdEL

 (normal delay) elapsed. No fail-safe actions.

dtt

The case temperature did not reach the defrost termination temperature setpont (

dEFt

) before the defrost cycle time finished. No fail-safe actions.

rLy

Compressor fault detected.

Advanced Parameters

Code

Description

Min

Max

Default

CONTROL LINK
(FRONT VIEW)

SETPOINT RESET BUTTON
(PRESS & HOLD 15 SECONDS)

Figure 10 - Reset Button

Содержание Control Link Refrigeration System Controller

Страница 1: ...sors mounted in the case The CL RSC may control two external relays compressor plus one configurable relay directly from its two onboard dry contact relay outputs or it may use a pluggable expansion output board P N 618 1120 for compressor control or 618 2085 for refrigeration solenoid control for activating case system components NOTE For information about networking Control Link RSC with E2 refe...

Страница 2: ...lower right side of the Control Link module Figure 4 The expansion board is powered from the CL RSC and requires no external power connection Power Control Link Module with 618 1120 output board When the 618 1120 output board is used with a Control Link module connect the L and N spade lug terminals on the module to the L and N spade lug terminals on the output board Figure 4 Connect 120 240 VAC 5...

Страница 3: ...gure 7 Refer to Table 1 for relay ratings Compressor Relays The Control Link uses two relays on the output board to control the compressor Line voltage must be connected to the Line 1 and Line 2 connectors on relays 1 and 2 respectively The Load 1 and Load 2 connectors are wired to the compressor Figure 7 shows the wiring diagram Refer to Table 1 for relay ratings Pressure Switch Wiring If desired...

Страница 4: ...p based on the value of the CSUd parameter default 10 minutes After this delay the CL RSC resumes normal refrigeration control To prevent nuisance alarms when the case is first started up no high temperature case alarms will be generated until 120 minutes after the start of the first cooling cycle Normal Operation Refrigeration When in refrigeration mode the CL RSC energizes the compressor relay w...

Страница 5: ...h will also initiate a manual defrost Compressor Fail Safe Mode If the case temperature sensor fails the CL RSC will operate in a fail safe mode that cycles the compressor ON and OFF at a user defined regular interval The ON OFF rate is determined by setting parameters CSFP and CSFO in the CL RSC CSFP sets the interval period and CSFO sets the amount of time during that period the compressor will ...

Страница 6: ...ds or leave controller idle for 60 seconds You will lose all setpoint changes made since you entered general programming mode NOTE Parameters in General Parameters shaded gray are only shown if the real time clock module is being used General Parameters Code Description Min Max Default CSP Temp control set point deg F can be displayed in deg C 40 100 25 CLSt Clock time set military UP button adjus...

Страница 7: ...liary input whose function is determined by SI2d ntc dGt ntc SI2d If input 2 defr term is dGt determines function of digital input SS setpoint shift ON causes the value of CSS to be added to set points IdeF start manual defrost IdeF SS IdeF SI3 Determines type of sensor on input 3 ntc 10K CPC thermistor dGT digital sensor ntc dGt ntc SI3d If input 3 is dGt determines function of digital input SS s...

Страница 8: ... the auxiliary relay ALAr close on alarm LCOn lighting control Visible only if rYbd yES ALAr LCOn ALAr LIOn LIOF L6On L6Of Visible only if ArA LCon or r2Fn LCon There are six ON OFF pairs where you may specify times of day for turning the lighting control relay ON and OFF Enter the first ON time of the day in the L1On field and the first OFF time in the L1OF field If necessary continue entering ON...

Отзывы: