Control Link RSC Installation Instructions

technical bulletin

CL-RSC Operation

The Display

The primary means of interaction with the CL-RSC system during pro-
gramming and operation will be the display on the front of the Control 
Link module (or the remote display, if one is being used). 

Figure 9 

shows the display used on both the module and the remote display.

Seven-Segment Display

The four-digit seven-segment display is the primary means a technician 
or operator will use for viewing temperatures and alarm codes, and pro-
gramming setpoints. 

Status LEDs

The three LEDs above the seven-segment display show the status of the compressor relay, the fan relay, and whether or not 
a setpoint shift is active (lit if setpoint shift is active).

Buttons

The four buttons to the right of the seven-segment display are used to program the CL-RSC, select temperatures and alarms 
for viewing, and perform other functions such as alarm silencing and manual defrost.

Modes of Operation

Start-Up

Compressor operation will be suspended after power-up based on the value of the 

CSUd

 parameter (default 10 minutes). 

After this delay, the CL-RSC resumes normal refrigeration control. To prevent nuisance alarms when the case is first started 
up, no high temperature case alarms will be generated until 120 minutes after the start of the first cooling cycle.

Normal Operation (Refrigeration)

When in refrigeration mode, the CL-RSC energizes the compressor relay when the case temperature is above the setpoint, 
and de-energizes it when the case temperature setpoint is satisfied. The fan relay is activated and de-activated the same way 
as the compressor relay, unless the CL-RSC has been programmed to keep the fans always ON.

Alarms During Refrigeration

If the case temperature sensor value falls below the low temperature setpoint or rises above the high temperature setpoint, 
the alarm relay (if defined) will energize, and the display will show the alarm code. The energized alarm relay and display 

#

Function

Fail-Safe

Output Board 618-1120

RELAY 3

Defrost

N.O.

10A-N.C. or 12A N.O. @ 120-240 VAC

RELAY 4

Auxiliary

N.C.

10A-N.C. or 12A N.O. @ 120-240 VAC

RELAY 5

Fan

N.C.

1/2 hp N.O. or N.C., 120VAC
1 hp N.O. or N.C., 240VAC

RELAY 6 

&

RELAY 7*

Contactor
or Solenoid

N.C.

Contactor

Solenoid

Pilot Duty

Inrush

Steady-State

Inrush

Steady-State

VA

24VAC

2.5A

0.3A

4A

2A

50

120VAC 0.5A

0.06A

0.8A

0.4A

50

240VAC 0.25A

0.03A

0.4A

0.2A

50

* Relay 7 is not used by the Control Link RSC but has the same ratings as Relay 6

Table 2 - Relay Ratings (Output Board 618-1120)

Figure 9 - CL-RSC Display

Содержание Control Link Refrigeration System Controller

Страница 1: ...sors mounted in the case The CL RSC may control two external relays compressor plus one configurable relay directly from its two onboard dry contact relay outputs or it may use a pluggable expansion output board P N 618 1120 for compressor control or 618 2085 for refrigeration solenoid control for activating case system components NOTE For information about networking Control Link RSC with E2 refe...

Страница 2: ...lower right side of the Control Link module Figure 4 The expansion board is powered from the CL RSC and requires no external power connection Power Control Link Module with 618 1120 output board When the 618 1120 output board is used with a Control Link module connect the L and N spade lug terminals on the module to the L and N spade lug terminals on the output board Figure 4 Connect 120 240 VAC 5...

Страница 3: ...gure 7 Refer to Table 1 for relay ratings Compressor Relays The Control Link uses two relays on the output board to control the compressor Line voltage must be connected to the Line 1 and Line 2 connectors on relays 1 and 2 respectively The Load 1 and Load 2 connectors are wired to the compressor Figure 7 shows the wiring diagram Refer to Table 1 for relay ratings Pressure Switch Wiring If desired...

Страница 4: ...p based on the value of the CSUd parameter default 10 minutes After this delay the CL RSC resumes normal refrigeration control To prevent nuisance alarms when the case is first started up no high temperature case alarms will be generated until 120 minutes after the start of the first cooling cycle Normal Operation Refrigeration When in refrigeration mode the CL RSC energizes the compressor relay w...

Страница 5: ...h will also initiate a manual defrost Compressor Fail Safe Mode If the case temperature sensor fails the CL RSC will operate in a fail safe mode that cycles the compressor ON and OFF at a user defined regular interval The ON OFF rate is determined by setting parameters CSFP and CSFO in the CL RSC CSFP sets the interval period and CSFO sets the amount of time during that period the compressor will ...

Страница 6: ...ds or leave controller idle for 60 seconds You will lose all setpoint changes made since you entered general programming mode NOTE Parameters in General Parameters shaded gray are only shown if the real time clock module is being used General Parameters Code Description Min Max Default CSP Temp control set point deg F can be displayed in deg C 40 100 25 CLSt Clock time set military UP button adjus...

Страница 7: ...liary input whose function is determined by SI2d ntc dGt ntc SI2d If input 2 defr term is dGt determines function of digital input SS setpoint shift ON causes the value of CSS to be added to set points IdeF start manual defrost IdeF SS IdeF SI3 Determines type of sensor on input 3 ntc 10K CPC thermistor dGT digital sensor ntc dGt ntc SI3d If input 3 is dGt determines function of digital input SS s...

Страница 8: ... the auxiliary relay ALAr close on alarm LCOn lighting control Visible only if rYbd yES ALAr LCOn ALAr LIOn LIOF L6On L6Of Visible only if ArA LCon or r2Fn LCon There are six ON OFF pairs where you may specify times of day for turning the lighting control relay ON and OFF Enter the first ON time of the day in the L1On field and the first OFF time in the L1OF field If necessary continue entering ON...

Отзывы: