October 2019
Installation, Operation and Maintenance Manual
MAN-02-04-97-0713-EN Rev. 1
68
Section 9: Set-Up Routines
Set-Up Routines
Figure 64
Actuator Direction: Closing
Closing torque % of nominal
Breakout limit
Ending limit
Position %
Running limit
100% Cl brk% Cl end % 0%
Figure 65
Actuator Direction: Opening
Opening torque % of nominal
Breakout limit
Ending limit
Position %
Running limit
0% Op brk% Op end % 100%
9.1.13.3
Lithium Battery
In the standard version, the actuator is provided with a lithium battery to keep visible the
local position display, to back-up the RTC (real-time-clock) for diagnostic functions, to
test the battery charge, and to update the remote outputs (output relays status when set
as "open limit" or "close limit" and 4-20mA when externally supplied) in case of electrical
power failure and manual override operations.
The program runs the functions relevant to the battery only if the appropriate flag “lithium
battery” is configured with “present”. If the battery is absent or if the above functions are
not requested, the flag "lithium battery" should be configured with “absent”.
Configuration procedure
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press YES to select the "Actuator Setup" menu, press NO to scroll
through the list of available routines, and then press YES to select "Miscellaneous".
•
Press NO to scroll the list of routines and press YES to select "Lithium Battery".
Press YES if the setting is correct; otherwise, press NO to change. Press YES when
the value is correct.