Installation, Operation and Maintenance Manual
MAN-02-04-97-0713-EN Rev. 1
October 2019
59
Section 9: Set-Up Routines
Set-Up Routines
Auxiliary output relays
For status indication or diagnostic purposes, 8 voltage-free contacts of 8 relays are available
to be configured individually to switch upon occurrence of the following conditions:
Status
•
open limit
•
closed limit
•
position >= xx %
•
position <= xx %
•
closing
•
opening
•
motor running
•
blinker
•
mid-travel position
•
local selected
•
remote selected
•
local stop active
•
ESD signal on
•
manual operation
•
interlock PST-icon
•
heater-only AS8
Alarm
•
motor over-temperature
•
over-torque
•
over-torque in OP
•
over-torque in CL
•
valve jammed
•
valve jammed in OP
•
valve jammed in CL
•
low lithium battery (if present)
•
mid travel alarm in CL/OP
•
mains-only AS8
Warning
•
warnings
•
PST failed (i.e. Partial Stroke Test failure)
The contacts may be configured to make or break on condition. The options “EFS in
manual”, “EFS mid-travel” and “PST failed” also appear in the menu, but are not available
on the XTE3000.