October 2019
Installation, Operation and Maintenance Manual
MAN-02-04-97-0713-EN Rev. 1
60
Section 9: Set-Up Routines
Set-Up Routines
Configuration procedure
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press YES to select the "Actuator Setup" menu, press NO to scroll
though the list of available routines, and then press YES to select "Output Relays".
Configure output relays
•
Press YES to change the monitor relay or NO to change auxiliary relays
AS1, 2, 3, 4, 5, 6, 7, 8.
Monitor relay
•
Press YES or NO to enable or disable the following situations from the
conditions that normally de-energize the monitor relay: motor over-temperature,
over-torque, jammed valve, manual override, ESD signal on, low lithium battery
(if present), local STOP pressed, LOCAL/OFF selected.
Auxiliary relays AS1, 2, 3, 4, 5, 6, 7 and 8
•
Press NO to answer prompt “MONITOR RELAY change?”.
•
Press YES to change AS1; otherwise, press NO to select the other relays.
•
Press YES if the condition associated to AS1 relay is correct; otherwise, press NO to
scrolls through the list of conditions and press YES to set.
•
Press YES or NO to either confirm or change the type of contact when the
condition occurs (break, make). Since relay AS8 is a change-over relay (i.e. not a
latching relay like AS1-AS7), this option is not available.
•
Press NO to proceed to AS2 and then repeat the procedure for the other relays.
•
Press NO to exit.
9.1.7
Positioner
The positioning function is only available in positioning (inching) or modulating XTE3000
actuators and allows for positioning of the valve according to a “position request R%”
command signal.
The positioning function compares the present actuator position % with the position
request R%, and if the difference is greater than the dead band the actuator is driven to
reach the new requested position.
The “position request R%” signal may either be received from the bus or the 4-20 mA analog
input. If the XTE3000 is set to receive the position request R% from the bus, the relevant
fieldbus interface card must be present; otherwise, a hardware alarm will be generated. If the
XTE3000 is set to receive the position request R% from the 4-20 mA generator, the Ain/Aout
card must be present; otherwise, a hardware alarm will be generated.