User Instructions
MAN-02-04-60-0352-EN Rev. 3
February 2019
86
Section 17: Technical Data and Certifications
Technical Data and Certifications
17.5
Auxiliary Voltage Input and Output
Table 40.
Auxiliary voltage input and output
Characteristic
Value
Input voltage range (auxiliary voltage input)
20. . . 30VDC
Maximum current consumption
(auxiliary voltage input)
500mA
Maximum current consumption in power-save
mode (auxiliary voltage input)
120mA
Output voltage (auxiliary voltage output)
typ. 23 V
Maximum output current (auxiliary voltage
output)
200mA
Resistance of common ground vs. earth
typ. 500 k Ohms
Resistance of common ground vs. earth
(floating version)
> 10M Ohms
Capacitance of common ground vs. earth
typ. 100 nF
Maximum allowed voltage of common ground
vs. earth
max. 40 Vs
Fuse (Fuse F1, see Figure 69)
1 A slow
(Littelfuse 454 NANO2 Slo-Blo R )
Ground potential is the common ground of the controller and the analog inputs
and outputs.
The auxiliary voltage output can be set in menu P6.5 (see Section 8.5).
The power-save mode is defined as follows:
•
No power supply (the controller is powered exclusively through the 24V auxiliary
voltage input).
•
The backlight of the LCD display switches off automatically.
•
No additional hardware options included (Profibus Interface, DeviceNet interface,
relay board, etc).
•
Binary outputs and the mA output are not enabled; when activating, the
respective currents must be added to the total current consumption.