![Emerson Bettis RTS FL Series Скачать руководство пользователя страница 49](http://html.mh-extra.com/html/emerson/bettis-rts-fl-series/bettis-rts-fl-series_user-instructions_102090049.webp)
User Instructions
MAN-02-04-60-0352-EN Rev. 3
February 2019
44
Section 8: Parameter Menu
Parameter Menu
Table 6.
End Limit Table (2)
Menu
Item
Sub Menu
Item
Position
Setting
Notes /Comments
P1.4
End limit
Switch off
Close
by travel (0)
The actuator uses end position signals to switch off and
report the end position.
by torque (1)
The actuator signals the end position or stops the motor
only after reaching the specified torque with the provision
that it has reached the end position. If the end position
signal is not reached, the actuator reports an error.
by torque1 (2)
see P1.3
by torque2 (3)
see P1.3
by torque3 (4)
see P1.3
P1.5
End limit
Closing
directing
right (0)
Actuator is designed for clockwise = closing.
left (1)
Reverse direction of rotation. Counter clockwise = closing.
The crossing of all signals and commands is performed by
the controller.
P1.6
End limit
Rotate sense
position
0
Rotation sense of the Potentiometer. No function in RTS
Fail-Safe Linear FL series.
1
P1.7
End limit
LED function
Close = green
(0)
Definition of the LED color of the CLOSED or OPEN end
postion indication.
Close = red (1)
P1.8
End limit
End limit hyst.
0.1 - 10.0%
Hysteresis range for end position signals:
Example: End position hysteresis 1% means that the End
position OFF is reached when closing 0%, and will be left
when opening only at 1%, i.e., a re-closing can only take
place after leaving this hysteresis.
P1.9
End limit
Ramp
0.1 - 10.0%
When approaching the end position, the speed is reduced.
P1.10
End limit
Range
0 - 10.0%
End position range for torque (P1.3, P1.4). Permissible
range in which the torque is to be achieved. If the actuator
comes to the end of the end position range, the motor
shuts off even if the torque has not been reached.
P1.11
End limit
Overrun
Open
0 - 60 s
Switch-off delay after reaching the end position see
travel1 (P1.3, P1.4)
P1.12
End limit
Overrun
Close
0 - 60 s
Switch-off delay after reaching the end position
travel1 (P1.3, P1.4)
CAUTION: OBSERVE LIMITS AND FACTORS OF GEAR
When installing the actuator on an gear or a thrust unit, please take into account the limits
and ratio of the gear/thrust unit at parameterization.
When using end limit switch off by torque, the end position limit must be set before reach-
ing the torque limit. Accordingly, the actuator will only signal the final end position if the
configured torque and the associated end position are reached. If the end position is not
reached, a torque error is reported (see
Section 17.2.2
).