Parameter Menu
Table 18.
Binary Outputs Table (3)
Menu
Item
Sub Menu
Item
Position
Setting
Notes/Comments
P10.1
Binary
Output
Output 1
40: Fail-safe
OK 1
Fail-safe OK (only for fail-safe actuators)
41: Fail-safe
OK 2
Fail-safe OK and Ready (only for fail-safe actuators)
42: Fail-safe
OK 3
Fail-safe OK, Ready and Remote
(only for fail-safe actuators)
43: Lock
Lock Open or Lock Closed is enabled.
44:
Ready/Torque
OK
Actuator is ready and no torque switch off.
45:
Ready/Remote/
Torque OK
Actuator is ready for operation in REMOTE mode and no
torque switch off.
46:
Position=Int1
Position = Intermediate position 1. The width of the
interval is set with the parameter P8.6.
47:
Position=Int2
Position = Intermediate position 2. The width of the
interval is set with the parameter P8.6.
48:
Position=Int3
Position = Intermediate position 3. The width of the
interval is set with the parameter P8.6.
49:
Position=Int4
Position = Intermediate position 4.The width of the
interval is set with the parameter P8.6.
50: Position
= Emergency
Position
Position = emergency position. The width of the
interval is set with the parameter P8.6.
51: Bus Bit 1
In existing bus interface (hardware option) the
output is set according to the selected bit bus.
52: Bus Bit 2
53: Bus Bit 3
54: Bus Bit 4
55: Bus Bit 5
56: Bus Bit 6
57: Bus Bit 7
58: Bus Bit 8
59: Virtual 1
Configurable output function.
60: Virtual 2
61: Virtual 3
62: Virtual 4
63: Line voltage
OK
Supply voltage for the motor is OK.
64: Control
voltage OK
The auxiliary voltage for the SMARTCON control is
OK. This function is only available if the auxiliary
voltage output is not switched on (P6.5 to 0).
65: Oil pressure
OK
The oil pressure is higher than the minimum
pressure (P6.10)
66: Oil level OK
The oil level is OK.
67: Pump OK
The temperature sensor in the pump motor and the