64
AXIMA 2000/4000 Installation Manual
24 VDC Power Supply Loading
You are responsible for determining if your 24 VDC supply can
handle the additional current load.
When using 24 VDC modules:
Inputs (on): 45 mA per input.
Outputs (on): (Load c 21 mA) per output.*
Outputs (off): 3 mA per output.
When using 120 VAC modules:
Inputs (on): 29 mA per input.
Outputs (on): 21 mA per output.
Outputs (off): 2.4 mA per output.
* The load current for the output modules must be limited to
no more than 3 amps.
Figure 51
Power Wiring for External I/O Mounting Racks
EMERSON Motion Control recommends that you use twisted pairs
for the 24 VDC power wiring.