A significant AC power problem occurs when the secondary of the AC
distribution transformer is not electrically referenced to earth
ground (i.e., left floating). In this case, the voltages that develop
between the AC power lines and earth ground can continuously
exceed the rated voltage of 264 VAC. When this happens the
protection circuit in the AXIMA 2000/4000 will try to suppress this
excess voltage. If the condition is prolonged, the AXIMA 2000/4000
protection circuits will fail.