12
AXIMA 2000/4000 Installation Manual
Power Requirements
The AC power connects to a removable connector on the top of the
AXIMA 2000/4000 chassis. The AC power input must be between 96
and 264 VAC, single phase, and 50 to 60 Hertz. At 115 VAC, 1.0 amps
RMS is required, or at 230 VAC, 0.5 amps RMS is required. However,
at power-up the logic supply has an inrush current that is typically
20 amps at 115 VAC and 40 amps at 230 VAC for 2 milliseconds. This
inrush current must be considered when choosing AC power fusing.
Figure 8
AC Power Connector
External Fusing Requirement
The AC power supply must be fused with a 2 amp fuse. Littlefuse's
FLM-2 SLO-BLO® type fuse or an equivalent can be used.
AC Supply
Range
AC Supply
Voltage
Current
Inrush
Current
(2 ms)
Fusing
96 to 264
VAC
115 VAC
1 Amp
20 Amps
FLM-2 or
equivalent
23 VAC
0.5 Amp
40 Amps
2 Amp Slo-Blo
COM
GND
L2
L1
L2
L1
EARTH GROUND
LOGIC COMMON
96 TO 264 VOLTS AC
@ 50 TO 60 Hz
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание AXIMA 2000
Страница 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 7: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 13: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 23: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 59: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...