Setup Menu
118
Table 36
AC8 - other default settings
DEFAULT SETTINGS - operation features (FROM Table 28)
Feature
Default
Other Options
AUTO SEQUENCING
OFF
(Deactivated)
ON (Activated), 12h (Activated for 12-hour intervals)
STANDBY TESTING
OFF
(Deactivated)
ON (Activated)
FAILED STANDBY
N
(Deactivated)
Y (Activated)
HOLD DELAY
10:00
(No delay)
Any time (in minutes and seconds) from 00:00 to 99:59
RESTART
00:06
(No delay)
Any time (in minutes and seconds) from 00:00 to 99:59
STAGING
OFF
(Deactivated)
ON (Activated)
JUMPER SETTINGS
Feature
Default
Other Options
Digital output loss-of-power jumpers
OFF - Normally Open
ON - Normally Closed
NOTE:
The jumper position has no effect on the contact when the AC8 has power.
12VDC/24VDC analog input jumper
24VDC
Acceptable voltage for all four two-wire analog sensors
422 TERM jumper
Default: jumpered
(connected)
None—do NOT change factory default
485 TERM jumper
Default: jumpered
(connected)
None—do NOT change factory default
EPOP jumper
Disabled
Enable to use the EPOP input
Audible horn
Enabled
May be disabled via the audible horn jumper
Manual Override switch
Off (outputs controlled by
programming)
On (Turn on all output relays)
DEFAULT SETTINGS - MODEM (FROM Table 21)
Feature
Default
Other Options
Initialization String (InitString)
ATS0=1
Any string (up to 40 characters); for international
dialing, add
+GCI=xx
, where
xx
is the country code
(except B5 countries—see
Table 22
)
Enable Modem Diagnostic Messages
N
(disable)
Y (enable)
Modem Dial Prefix
ATE0X4DT
Any string
Modem Hang Up Delay After a Call
10
seconds
Any number (up to 99 seconds)
DIP SWITCH SETTINGS
Feature
Default
Other Options
8-position DIP switch
All are OFF (down)
May be used to reset password to factory default (see
9.9.1- Change Password
)
OTHER SETTINGS
Feature
Default
Other Options
Change state of outputs - automatic
or manual control
AUTO (automatic control) Force an output ON / OFF via Manual Output Ctrl menu
Force all outputs ON via hardware switch
Password
AAAA
Any 4 characters (see
Table 14
for valid characters)
Reset common alarm with silence
N
(not reset)
Y (reset with silence)
Battery connected
Y
(connected)
N (not connected)