System and Control Options
47
7.7
Setup System - Setup Outputs
The AC8 has eight outputs that may be configured individually. These outputs correspond to the
eight numbered inputs. For example, Device_1 is the unit connected to Input 1 and to Output 1.
The output name is the same as the input name, as described in
7.3.1 -
Change Label (Name of Input)
.
To configure an output:
Log In and Choose Setup System
• From the Main Menu, use the arrows
↑↓
to
choose
System and
Control
, then press Enter
↵
(see
7.1 - Login
for help)
.
• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows
↑↓
to
choose
Setup System
, then press Enter
↵
.
Select an Output to Configure
• From the Setup System Menu, shown at right, use the arrows
↑↓
to
choose
Setup Outputs
and press Enter
↵
.
• From the Select Output Menu, choose an output—for example,
Device_1
—and press Enter
↵
.
Table 19
shows digital output features and their default settings: you
may define an output as Normally Open or Normally Closed, set the
device’s mode—operating, standby or not used—and specify whether to
disable the device during emergency power operation.
Use the steps following
Table 19
to change the default settings for any
digital output.
7.7.1 Define Output as Normally Open or Normally Closed
Each output may be set up as Normally Open (NO) or Normally Closed
(NC). The default setting for all output points is NO (Normally Open).
• From the Setup Outputs Menu, shown at right, use the arrows
↑↓
to
choose
Norm Open/Close
and press Enter
↵
.
• To change the normal state for this output, use the arrows
↑↓
to
choose the state:
•
NO
(Normally Open)
•
NC
(Normally Closed)
• Press Enter
↵
.
Table 19
Default settings - digital outputs
Feature
Default
Other Options
NORM OPEN/CLOSE
NO
(Normally Open)
NC (Normally Closed)
MODE*
Outputs 1-2:
Outputs 3-4:
Outputs 5-8:
OP
(Operating)
ST
(Standby)
NU
(Not Used)
OP (Operating)
ST (Standby)
NU (Not Used)
IN ALARM
E
(Enable)
D (Disable)
EMERG OP
E
(Enable)
D (Disable)
* Outputs defined as Not Used should be kept in a separate zone that does not include
any outputs defined as Operating or Standby. The Auto Sequencing feature will not
function properly in a zone with outputs defined as Not Used. See
7.10.1 - Turn
Automatic Sequencing On or Off
for more information.
Setup System Menu
SETUP INPUTS
SETUP COMMON ALARM
SETUP SENSOR
↑↓
=NEXT
↵
=SELECT
SETUP ZONES
> SETUP OUTPUTS
SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP OPERATION
SETUP I/O MATRIX
Select Output Menu
SELECT OUTPUT
> DEVICE_1
NO-OP-E-E
DEVICE_2
NO-ST-E-E
↑↓
=NEXT
↵
=SELECT
DEVICE_3
NO-ST-E-E
DEVICE_4
NO-ST-E-E
DEVICE_5
NO-NU-E-E
DEVICE_6
NO-NU-E-E
DEVICE_7
NO-NU-E-E
DEVICE_8
NO-NU-E-E
Setup Outputs Menu
SETUP DEVICE_1
> NORM OPEN/CLOSE: NO
MODE: OPERATING
↑↓
=NEXT
↵
=SELECT
IN ALARM: ENABLE
EMERG OP: ENABLE
Change State
SET TO NORMAL OPEN
OR NORMAL CLOSE? NO
↑↓
=NO/NC
↵
=END