TESTING & SERVICE

(continued)

2--2

TROUBLE-SHOOTING

Note any optional accessories that may be furnished on

the ACTB and review their operation. Refer to any sepa-

rate drawings and/or instructions that may be packed

with the ACTB.

Table 2-1. Trouble-Shooting Checks.

Hazardous voltage capable of causing shock,

burns, or death is used in this switch.

Do not touch the power or load terminals

of the bypass switch or transfer switch!

PROBLEM

CHECK IN NUMERICAL SEQUENCE

PROBLEM

1 OPERATION

2 GEN-SET

3 VOLTAGE

Engine–generator set does

not start when the

Transfer

Control

switch is turned and

held in

Transfer Test

position

or when normal source fails.

Hold

Transfer Test

switch 15

seconds or the outage must

be long enough to allow for

Feature 1C time delay plus

engine cranking and starting

.

Starting control must be in the

automatic position. Batteries

must be charged and

connected. Check wiring to

engine starting contacts.

Transfer switch does not

transfer the load to the

emergency source after the

engine–generator set starts.

Wait for Feature 2B time delay
to time out.

Generator output circuit

breaker must be closed.

Generator frequency must be

at least 95% of nominal (57 Hz
for a 60 Hz system.) *

Voltmeter should read at least

90% of nominal phase to

phase voltage between

terminals EA and EC (or EL1

and EL2 for 2 pole switches)*

Transfer switch does not

transfer the load to normal

source when normal returns

or when the

Transfer Control

switch is released.

Wait for Feature 3A time delay

to time out.

Voltmeter should read at least

90% of nominal phase to

phase voltage between

terminals NB and NC, NC and

NA, and NA and NB (or NL1

and NL2 for 2 pole switches).

Gen. does not stop after load

retransfer to normal source.

Wait for Feature 2E time delay

to time out.

Starting control must be in the

automatic position.

Failure to Synchronize

light comes on.

Conditions of Normal or Emergency Sources not suitable for closed transition transfer.

Recheck voltage and frequency of both sources. Press

Alarm Reset

pushbutton.

Extended Parallel Time

light comes on.

CN and CE contacts are closed longer than setting in the Control Panel. Open the discon-

nected source circuit breaker, then call your nearest ASCO Service Center for assistance.

TS Locked Out

light comes on.

Transfer lockout operation has occured; transfer switch is disabled from automatic operation.

Open the disconnected source circuit breaker, then call your nearest ASI for assistance.

* These are factory settings. Refer to

Controller User’s Guide

.

If the problem is isolated to circuits on the controller or the transfer switch, call your local ASCO Power Technologies sales

office or ASI at 1–800–800–2726. Furnish the Serial No. and Catalog No. from the transfer switch nameplate.

MANUAL LOAD TRANSFER

This procedure manually transfers load to other source if

the Transfer Switch or Control Panel are out of service.

Close enclosure doors to prevent personal

injury in case of electrical system fault.

1. Be sure that the Bypass Handle is

CLOSED

on either

Emergency or Normal (see page 3–1).

2. Be sure that the Isolation Handle is in the

TEST

or

ISOLATE

position (see page 3–2).

3. Turn the Bypass Handle counterclockwise to

OPEN

the Bypass Switch. Then Bypass to the other source

(see page 3–1).

MAINTENANCE HANDLE

Bypass and isolate the Transfer Switch before

using the maintenance handle! See pages 3–1

and 3–2. Remove the hub and handle after

using them and store on frame.

Turn counterclockwise

to OPEN contacts.

Turn clockwise to

CLOSE contacts.

insert

handle

into hole

Grasp

handle

firmly

slide hub

onto shaft

& insert pin

Pull out shaft to operate

Emergency contacts.

Push in shaft to operate

Normal contacts.

Содержание ASCO 7000 Series

Страница 1: ...ies ACTB for all installation and connection details and accessories Refer to Group 5 Controller User s Guide 381333 126 for ATS status display messages time delays pickup dropout settings and adjustments An experienced licensed electrician must install the 7ACTB Rating Label Each 7000 Series 7ACTB contains a rating label to define the load and fault circuit withstand closing ratings Refer to the ...

Страница 2: ...00 Series ACTB for all mounting details including door opening space If bottom cable entry is used the foundation must be prepared so that the conduit stubs are located correctly Refer to the appropriate enclosure outline drawing for specified cable entrance area and location Provide cable bending space and clearance to live metal parts When a concrete floor is poured use interlocking conduit spac...

Страница 3: ...ply joint compound to conductor then carefully wipe away excess compound Tighten the cable lugs to the torque specified on the rating label Be sure that the Normal and Emergency power connections are in proper phase rotation Bus Connections If bus connection is used use SAE grade 5 hardware to connect bus to appropriate terminal plates on bypass switching device Wipe off bus surfaces before they a...

Страница 4: ...s See Figure 1 3 Black square means light is on White square means light is off If necessary adjust voltage regulator on generator per the manufacturer s recommendations The ACTB will respond only to rated voltage specified on the nameplate Now continue to 2 Electrical Operation on next page 1 Close the normal source circuit breaker The Transfer Switch Connected To Normal and the Normal Source Acc...

Страница 5: ...ans light is on White square means light is off 3 Turn the Isolation Handle clockwise approximately 16 turns to the CONN connected position 4 Push in the Bypass Handle and turn it counterclock wise until the OPEN indicator shows green This completes the Functional Test of the ACTB 1 Turn and hold Transfer Control switch clockwise to Transfer Test until the engine starts and runs within 15 sec The ...

Страница 6: ...closure Brush and vacuumaway any excessive dust accumulation Remove any mois ture with a clean cloth Check the transfer switch contacts Remove transfer switch barriers and check the condition of the contacts Replace contacts when pitted or worn excessively Reinstall the barriers carefully Maintain transfer switch lubrication If switch is subjected to severe dust or abnormal operating con ditions r...

Страница 7: ... Feature 2E time delay to time out Starting control must be in the automatic position Failure to Synchronize light comes on Conditions of Normal or Emergency Sources not suitable for closed transition transfer Recheck voltage and frequency of both sources Press Alarm Reset pushbutton Extended Parallel Time light comes on CN and CE contacts are closed longer than setting in the Control Panel Open t...

Страница 8: ... ATS is bypassed to Normal Source Figure 3 1 Bypass Handle and position indicators To Bypass Normal Source Load connected to Normal Source The Transfer Switch Connected To Normal light is on and Transfer Switch Connected To Emergency light is off Push in the Bypass Handle all the way then turn it clockwiseuntil Bypass Switch Positionshows CLOSEDon NORMAL yellow indicator The red light Unit Not In ...

Страница 9: ...tch Bypass Switch Figure 3 5 TEST to ISOLATE position 4 Open the lower enclosure door Pull out the side rail carriage then roll out the transfer switch It can be safely inspected in this position The transfer switch can also be removed for easier maintenance opera tions unfold crank position window CONN TEST ISOLATE counterclockwise draws out transfer switching device Figure 3 6 Isolation Handle N...

Страница 10: ...s black NORMAL or EMERGENCY at the Bypass Switch Handle This indicates the source connected to the load 4 Observe which Transfer Switch Connected To light is on Normal or Emergency on the door This is the positionoftheTransferSwitch If itis notin thesame position as the Bypass Handle change the position of the Transfer Switch as follows To change the position of transfer switch Operate to NORMAL O...

Страница 11: ...assed to Emergency or yellow NORMAL when ATS is bypassed to Normal Source Figure 3 11 Bypass Handle and position indicators To Un Bypass Normal Source Load connected to Normal Source The Transfer Switch Connected To Normal light is on and Transfer Switch Connected To Emergency light is off Push in the BypassHandle thenturn itcounterclockwise until Bypass Switch Position shows OPEN green indica tor...

Страница 12: ...1 maintenance handle 2 2 warning 2 2 manual load transfer 2 2 warning 2 2 N nameplate cover Normal Source Accepted light 1 3 O operation electrical 1 4 manual 2 2 warning 2 2 P parts 2 1 phase rotation check 1 3 preventive maintenance 2 1 problem 2 2 R rating label cover removal of shipping angles 1 1 removal of shipping skid 1 1 replacement parts 2 1 return to service 3 3 S service ASCO Services ...

Отзывы: