Reference Manual
00809-0100-4793, Rev CA
August 2004
B-3
Rosemount 8742C
HAZARDOUS LOCATION
CERTIFICATIONS
Equivalent Hazardous Location Certifications for flowtube and transmitter
must match in integrally-mounted magnetic flowmeter systems.
Remote-mounted systems do not require matched hazardous location
certification option codes.
Transmitter Approval
Information
North American Certifications
Factory Mutual (FM)
N0
Division 2 Approval
Reference Rosemount Control Drawing 08742-1051 (8742C) or
08732-1052 (8732C).
Class I, Division 2, Groups A, B, C, D
Temp Codes – T4 (8712 at 40°C, 8742 at 60°C),
T5 (8732 at 60°C)
Dust-ignition proof Class II/III, Division 1, Groups E, F, G
Temp Codes – T4 (8712 at 40°C), T6 (8732/8742 at 60°C)
Enclosure Type 4X
K0
Division 2 Approval with
Intrinsically Safe Output
Reference Rosemount Control Drawing 08742-1051
Class I, Division 2, Groups A, B, C, D with IS output for Class I, Division
1, Groups A, B, C, D.
Temp Code – T4 at 60°C
Dust-ignition proof Class II/III, Division 1, Groups E, F, G
Temp Code – T6 at 60°C
Enclosure Type 4X
Table B-1. Transmitter Option Codes
Rosemount 8742 Transmitter
Approval Codes
Fieldbus Output
I.S. fieldbus Output
CE
(1)
N0
•
N5
•
E1
•
E5
•
ED
•
K0
•
•
K1
•
K5
•
•
KD
(2)
•
•
N1
(3)
(1) CE Marking is standard on a Rosemount 8712D, 8742 and 8732. Not available on Rosemount 8712H.
(2) Refer to Table B-3 on page B-11 for relation between ambient temperature, process temperature, and temperature class.
(3) Only available for the 8712D.
Содержание 8700 Series
Страница 2: ......
Страница 4: ......
Страница 12: ...Reference Manual 00809 0100 4793 Rev CA August 2004 1 4 Rosemount 8742C ...
Страница 64: ...Reference Manual 00809 0100 4793 Rev CA August 2004 5 12 Rosemount 8742C ...
Страница 102: ...Reference Manual 00809 0100 4793 Rev CA August 2004 Rosemount 8742C A 32 ...
Страница 116: ...Reference Manual 00809 0100 4793 Rev CA August 2004 Rosemount 8742C B 14 ...
Страница 135: ......