Menu 10
130
Commander SK Advanced User Guide
www.controltechniques.com Issue Number: 9
Indicates that the normal current limits are active. The drives display will flash AC.Lt to indicate that normal current limits are active.
Indicates that power is being transferred from the motor to the drive.
Indicates that the braking IGBT is active. If the IGBT becomes active this parameter is held on for at least 0.5s so that it can be seen on the display.
This parameter is set when the braking IGBT is active and the braking energy overload accumulator is greater than 75% (Pr
). This parameter is
held on for at least 0.5s so that it can be seen on the display.
This parameter is set if the pre-ramp reference (Pr
1.03
) is negative (reverse), reset if pre-ramp reference is positive (forward).
This parameter is set if the post-ramp reference (Pr
2.01
) is negative (reverse), or reset if post-ramp reference is positive (forward).
Indicates that the drive has detected mains loss from the level of the DC bus voltage. This parameter can only become active if mains loss ride
through or mains loss stop modes are selected (see Pr
10.09
Drive output is at current limit
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Range
OFF(0) or On(1)
Update rate
Background
10.10
Regenerating
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Range
OFF(0) or On(1)
Update rate
Background
10.11
Dynamic brake active
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Range
OFF(0) or On(1)
Update rate
Background
10.12
Braking resistor alarm
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Range
OFF(0) or On(1)
Update rate
Background
10.13
Direction commanded
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Range
OFF(0) or On(1)
Update rate
Background
10.14
Direction running
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Range
OFF(0) or On(1)
Update rate
Background
10.15
Mains loss detected
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Range
OFF(0) or On(1)
Update rate
Background
10.16
Unused parameter
Содержание 2202