Menu 7
106
Commander SK Advanced User Guide
www.controltechniques.com Issue Number: 9
Analog input 2 can be configured as either a 0 to +10V analog input or a +24V digital input (positive logic).
When analog input 2 is set up for analog input, this parameter is used to scale the input (see Pr
). When the input is defined as a digital input, this
parameter has no effect.
When set-up as an analog input, this parameter can be used to invert the analog input reference (i.e. multiply the input scaling result by -1).
For digital input, this parameter selects a digital inversion.
As default, this parameter is set-up automatically according to the drive configuration (see Pr
Only parameters which are not protected can be controlled by analog inputs. If a non valid parameter is programmed to the destination of an analog
input, the input is not routed anywhere.
After a modification to this parameter, the destination is only changed when a reset is performed.
The parameter required to be represented as an analog signal by the analog output on terminal B1, should be programmed in this parameter.
This parameter is used in conjunction with Pr
to determine the analog output signal. Pr
has 4 pre-determined settings for easy set-up of the
analog output. If the user requires to set Pr
to another parameter, then Pr
4
:
USEr.
for further details. If a non valid parameter is programmed as a source, the output will remain at zero.
7.11
Analog input 2 mode (terminal T4)
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Range
VoLt(0) or dig(1)
Default
VoLt(0)
Update rate
Background
Value
Display
Function
0
VoLt
0 to +10V
1
dig
0 to +24V
7.12
Analog input 2 scaling
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
3
1
1
1
Range
0.000 to 4.000
Default
1.000
Update rate
Background
7.13
Analog input 2 invert
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
Range
OFF(0) or On(1)
Default
OFF(0)
Update rate
5 ms
7.14
Analog input 2 destination
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
2
1
1
1
1
Range
Pr
0.00
to Pr
21.51
Default
Pr
Update rate
Read on drive reset
7.15 to 7.18
Unused parameters
7.19
Analog output source
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
2
1
1
1
1
Range
Pr
0.00
to Pr
21.51
Default
Pr
Update rate
Read on drive reset
Содержание 2202