EES-401 Series Ultrasonic Energy Meter
Revision: 3.0.1
Page 66 of 90
Step3. Pipe Material
Press
keys to enter the window
M14, press
key, press
or
key
to select Pipe Material, and press
key to
confirm.
Step4. Transducers type
Press
keys to enter the window
M23, press
or
key to select transducer
type, and press
key to confirm.
4. Plug
-
in Type WH101 ( WH type insertion
transducer ).
Step5. Transducer mounting methods
Press
keys to enter the window
M24, press
key, press
or
key
to select transducer-mounting method, and press
key to confirm.
Choose according to the pipes on site.
Step6. Adjust Transducer spacing
Press
key to enter Menu 25,
accurately install the transducer according to the
displayed transducer mounting spacing and the selected
mounting method.
L=SP+34
(
unit
:
mm
)
SP for window shows the numerical 25.
Step7. Display measurement result
Press
keys to enter the window
M01.
About other setup, please refer to the related information in the manual.
Special Note
Since the holes needs to be opened when the WH101 insertion sensor is installed, and the hole
position cannot be changed after the opening, the correct setting of the pipe section parameters
must be first confirmed and verified before opening the hole. And then press the SP value
displayed in Menu 25 to calculate the hole center spacing L =SP+34 (mm) for opening, the
opening spacing in this case is 68.83+34=102.83mm.
Pipe Material
[14
0. Carbon Steel
Transducer Type [23
4. Plug-in-WH101
Transducer Mounting
1. Z
Transducer Spacing
68.83 mm
Flow 0.1129 m3/h *R
Vel
1.0415 m/s