25
6.2 - Connecting the
power supply cable
To connect the electrical power supply cable,
follow the steps below while referring to figure 18:
remove the boiler casing following the
instructions given in section 13.2 or 13.3;
press the two plastic springs tabs labeled “B”
on the bottom side;
open panel “A” in the “C” direction;
remove the three screws labeled “D”;
open door “E” in the “F” direction;
install the power supply wires, “G” as shown;
strip the power supply wires being careful to
leave the ground wire 1in (25 mm) longer than
the other two;
connect the ground wire to the ground terminal;
connect the 120 volt hot wire to terminal “L1”;
connect the 120 volt neutral wire to terminal
“N”.
NOTICE! If the 120 volt power wires are
inverted, the boiler will block, displaying
error code E21.
NOTICE! If the boiler is not properly
grounded, the boiler will block, displaying
error code E23
6.3 - Choosing the room
thermostat
This boiler is designed to function with any type
of room thermostat which has
an electrical contact with the following
specifications:
- open (end call for heat); closed (call for heat);
- clean dry contact (not powered);
- electrical capacity of 24Vac, 1A.
6.4 - Thermostat wiring
Install the room thermostat in a part of the house
where the temperature is as near to average as
possible. Avoid areas subject to sudden
temperature changes such as outside windows or
doors, above radiation elements, near lamps,
etc., (see figure 19).
Connect the room thermostat to the boiler by
following the steps below:
remove the boiler casing according to the
instructions given in section 13.2 or 13.3 and
open the junction box per section 6.2;
use a two conductor cable with a minimum
cross section of # 18 AWG between the boiler
and the room thermostat;
A = Junction box
B = Plastic spring
C = Opening direction
D =
Screws for junction box cover
E = Junction box cover
F = Junction box cover opening direction
G = Electrical supply cable
H = Room thermostat cable (optional)
L = Outside temperature sensor cable (optional)
M = Storage tank temperature sensor
N = Remote command cable (optional)
Figure 18 - Junction box