The service state will make the actuator non-responsive to commands and
failsafe triggers blocking commands to be executed. If any work is to be
done to the product, this state needs to be activated to avoid possible
personnel injuries or material damage. When cleared, the actuator resumes
normal or failsafe state, whichever was active before the initiating of service
state. Once the service state is no longer required, it is cleared remotely via
the IAS or E3C.
Service state may be set by manually operating the handwheel or from the
IAS/E3C. The state must be reset from the IAS/E3C.
For information on how to operate the handwheel, please see
on page 45.